SETTING CALCULATION FOR LINE PROTECTION RELAYS 220KV BUDHIL LINE PROTECTIONS
PROJECT
:220KV LANCO INFRATECH LIMITED CHAMERA
GRID
Page 1 of 5
Length of protected line Positive Sequence Resistance per KM Positive Sequence Reactance per KM Positive sequence impedance per KM Zero Sequence Resistance per KM Zero Sequence Reactance per KM Zero Sequence Impedance per KM Positive Sequence Resistance for Protected line Positive Sequence Reactance for Protected line Positive Sequence Impedence for Protected line Positive sequence Impedence angle Zero Sequence Resistance for Protected line Zero Sequence Reactance for Protected line Zero Sequence Impedence for Protected line Zero Sequence Impedence Angle
Length of the adjacent line Pos.Seq. Resistance of Adj. Line per KM Pos.Seq. Reactance of Adj. Line per KM Pos.Seq. Impedence of Adj. Line per KM Positive Sequence Resistance for adj.line Positive Sequence Reactance for adj.line Positive Sequence Impedence for adj.line Positive sequence Impedence angle
Length of the adjacent longest line Pos.Seq. Resistance of Adj. Line per KM Pos.Seq. Reactance of Adj. Line per KM Pos.Seq. Impedence of Adj. Line per KM Positive Sequence Resistance for adj. line Positive Sequence Reactance for adj. line Positive Sequence Impedence for adj. line Positive sequence Impedence angle
CT Primary CT Secondary PT Primary PT Secondary CT/PT Ratio
ALSTOM T&D INDIA LTD FOR M/S CHAMERA-III HEP
19/1 G.S.T ROAD
220KV BUDHIL LINE PROTECTION REV-1
PALLAVARAM
Page 2 of 5
CHENNAI-600043
Grounding Factor kg = (Z0/Z1)/(3*Z1) (SQRT((X0(arc Tan((X0KZ1,KZ2,KZ3…..PS1 Angle Kg
0.666 -0.022 0.666 -0.022
DIST DIST DIST DIST
80% 50% 100% 25%
Z1 Z2 Z3 Z4
(100 of Protected line + (100 of Protected line +
80% of Protected line
Degree Degree of of of of
protected line shortest line longest line zone 1 impedence
Ohm
100% of protected line + 50% of shortest line
Ohm
100% of protected line + 100 % of longest
Ohm
25% of Zone 1 Impedence
Ohm
Primary full load current, CTR considered as Full load
1800
Amp
Resistance at this current=(0.8*(PT Primary * 10^3) / (1.732) / (1.2*Primary full load current)
47.045
Ohm
Load Resistance (RL) in Secondary DIST R1,PP(Circle) Ps1 (60% of RL) DIST R2,PP(Circle) Ps1 (60% of RL) DIST R3,PP(Circle) Ps1 (60% of RL) DIST R1,PG(Circle) Ps1 (80% of RL) DIST R2,PG(Circle) Ps1 (80% of RL) DIST R3,PG(Circle) Ps1 (80% of RL)
42.340 25.404 25.404 25.404 33.872 33.872 33.872
Ohm Ohm Ohm Ohm Ohm Ohm Ohm
0.00 0.30 0.75 1.00
SEC SEC SEC SEC
5.081
Ohm
ZONE ZONE ZONE ZONE
1 2 3 4
OPERATING OPERATING OPERATING OPERATING
TIME(t1) TIME(t2) TIME(t3) TIME(t4)
∆R
& ∆X ∆R = 10 to 30% of Z3 R3, PP
ALSTOM T&D INDIA LTD FOR M/S CHAMERA-III HEP
19/1 G.S.T ROAD
220KV BUDHIL LINE PROTECTION REV-1
PALLAVARAM
Page 3 of 5
CHENNAI-600043
∆X
5.081
= 10 to 30% of Z3 R3, PP
Ohm
Unblocking stages using to trip if any fault when relay blocked on PSB The three unblocking current thresholds namely, IN>, I2> and Imax should be set IN> 40% I2> 30 % Value of Imax line = 3 Inom PSB Allowed to trip – Zone 1 To be set to 2s typically to un block in case of a prolonged power swing. Program Mode Standard Mode Z1Ext Fail Trip mode
Standard Scheme PUR Permissive under reach scheme Disabled 1 pole Z1 , CR Received
Switch on to fault logic is pre-set in MiCOM P442 I>3 Current Set I>3 Time delay I>4 Status Operation on pick up of level detector method and
3.00A 3sec Disabled activation of all zones is
Enable I> Current setting tI>1 Time delay IN>1 Current Setting IN>1 Time delay
Yes 3A 1.2 sec 0.3A 1.2 sec
IN>1 IN>1 IN>1 IN>1 IN>1 IN>1 IN>2
IDMT Directional Forward Non Directional 0.3 A 1.0 sec 1.0 sec Disabled
Function Directional VTS Block current set Time Delay Time VTS status