Description

Revision Index 2201801BMCHS0485 ENI MUARA BAKAU B.V PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

Rev. Number

Validity Status

01

CD-FE

REVISION List 00

Issued for Information

01

Re-Issued for Information

This document is property of Eni Muara Bakau B.V.. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

Sheet of Sheets

3/35

Sheet of Sheets

Revision Index 2201801BMCHS0458 ENI MUARA BAKAU B.V

Rev. Number

Validity Status

01

CD-FE

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

4/35

TABLE OF CONTENTS COVER

1

DOC VERIFICATION

2

REV LIST

3

TABLE OF CONTENT PRELIMINARY HVAC COOLING LOAD

4 5-35

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

Revision Index 2201801BMCHS0458 ENI MUARA BAKAU B.V PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

Rev. Number

Validity Status

01

CD-FE

Sheet of Sheets

5/35

1.0

INTRODUCTION

1.1

Project Background Jangkrik Field (JKK) is a gas discovery made in March 2009. It is located about 70 km from the coast, in the MuaraBakau permit area, Makassar Strait, offshore Kalimantan, at a water depth ranging from 250 to 500 m. Eni, through its Indonesian subsidiary, operates the MuaraBakau PSC with a 55% interest, in joint venture with GDF Suez, holding the remaining 45% interest. The selected concept is based on a subsea development with seven wells, full treatment facilities on a spread moored FPU and export line to shore at Sapi landfall. Jangkrik North East (JNE), located at about 25 km NNE from JKK Main, is a recent gas discovery, made in July 2011. The selected concept together with the tie in of Jangkrik North East to the FPU has been studied in detail during the basic engineering phase completed in April 2012. The concept studied in this FEED foresees: • • • •

7 Subsea Wells for JKK tied back to the FPU; 4 Subsea Wells for JNE, tied back to the FPU (as option) a Barge Shaped FPU, performing Full Offshore Process; Export treated gas and condensate to onshore near Sapi existing plant.

Final destination of Jangkrik gas is Bontang LNG Plant and local market. Final destination of Jangkrik condensate is Senipah Plant. 1.2

Scope of the document This document defines preliminary cooling load and ventilation requirements for sizing HVAC equipment for Topside Local Equipment Room (LER), warehouse, workshop and laboratory at JANGKRIK FPU. The preliminary cooling load is calculated in accordance with ASHRAE FUNDAMENTALS / ASHRAE GRP 158 using excel form. The detail HVAC cooling load nee to be performed during detail engineering.

2.0 2.1

REFERENCES Industrial Standard -. ASHRAE Handbook

HVAC Fundamentals

-. ASHRAE GRP 158 -. ANSI/ASHRAE Standard 62.1-2010

Cooling and Heating Load Calculation Manual Ventilation for Acceptable Indoor Air Quality

2.2

Project Document

2.21

Project Specification 220801BMRBS0486 Drawing

HVAC Design Philosophy

220800BTDPS0804

EQUIPMENT LAYOUT - FPU - AREA 1-CELLAR DECK

220801BEDPS0706 Sheet 1-4

ELECTRICAL EQUIPMENT LAYOUT AND GENERAL ELECTRIC POSITIONING IN FPU TOPSIDE LAYOUT

220801BMFQS0464

HVAC FLOW DIAGRAM (FOR TOPSIDE BUILDING)

2.22

3.0

AIR CONDITIONING CALCULATION

3.1

Design Input The component that contribute to room heat gains and losses consist of the following: -. Conduction through external walls, partitions, doors, roof and floors. -. Lighting heat gain as per sec. 10.1 220801BMRBS0486 HVAC Design Philosophy -. People / occupancy assumed 2 and 4 people per room. -. Heat dissipation of equipment in Electrical building obtained (preliminary and will be updated during detail design). -. Safety factor 10% is provided in the calculation.

3.2

Outdoor Design Condition Outdoor design condition used for the cooling load calculations are: Maximum outside temperature

39.4 deg C / 102.92 Deg F Dry bulb

Minimum design temperature

18.9 deg C / 66.2 Deg F Dry bulb

Maximum humidity

90% RH

Minimum humidity

78% RH

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

Company Document Identification 2201801BMCHS0458 PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

ENI MUARA BAKAU B.V

3.3

3.4

Sheet of Sheets

Revision Index Rev. Number

Validity Status

01

CD-FE

6/35

Indoor Design Condition Level (Meter)

Room

Temp Design (°C)

Temp Tolerance (°C)

Temp Set point range (°C)

Relative Humidity (%)

Room DP (Pa)

Room Maximum

Elevation 103.500 Elevation 103.500 Elevation 108.500 Elevation 113.500 Elevation 113.500 Elevation 118.500 Elevation 103.500 Elevation 103.500 Elevation 103.500

Transformer Room

24

0-2

24 - 26

40 - 65

30

NC 55

Normal Room

24

0-2

24 - 26

40 - 65

30

NC 55

Battery Room

24

0-2

24 - 26

45 - 65

30

NC 55

Emergency Room

24

0-2

24 - 26

45 - 65

30

NC 55

Normal Room

24

0-2

24 - 26

40 - 65

30

NC 55

Instrument Room

24

0-2

24 - 26

40 - 65

30

NC 55

Warehouse

24

0-2

24 - 26

50 - 65

NC 55

Workshop

24

0-2

24 - 26

40 - 65

NC 55

Laboratory

22

0-2

22 - 24

50 - 65

30

NC 55

People/Occupancy for Calculation Room

No of persons inside rooms

Activity Type

Transformer Room

2

Light work

Normal Room

2

Light work

Battery Room

2

-

Emergency Room

2

Light work

Instrument Room Instrument Room

2 2

Light work Light work

Warehouse

4

Light work

Workshop

4

Light work

Laboratory

4

Light work

Heat gains on 24 deg C for light work activity as per 220801BMRBS0486 HVAC Design Philosophy (For Topside Building) Section 10. Sensible and Latent Heat Gains. Sensible heat (W/Person) Latent heat (W/Person) 3.4

86 133

U-Values the U-Values are taken from 220801BMRBS0486 HVAC Design Philosophy (for Topside Building) Sec. 6 Building Type. Wall Reference U-value in W/m2/°C External walls 0.6

3.5

Roof

0.6

Floor

0.6

Partitions/internal walls

2.2

Door

3.5

Windows

2.7

Summary Calculation Floor Name

Floor Area (milimeter)

Sensible Heat (kW)

Sensible Heat (mbtu/hr)

First Floor

21000 x 16000

145

Second Floor

20000 x 16000

22

494 74

Total Heat (kW)

Total Heat (mbtu/hr)

186

Supply Air (cfm)

Make Up Air (cfm)

Exhaust Air (cfm)

633 165

2968

505

NA

49

1180

471

1180

Third Floor

20000 x 16000

58

196

90

306

2824

505

NA

Fourth Floor

20000 x 16000

171

582

213

724

2824

471

NA

Warehouse

14200 x 10000

9

27

21

69

1253

208

NA

Workshop

14200 x 10000

23

77

37

124

1253

209

1253

Laboratory

8795 x 6000

Total

27

92

93

316

1242

1242

1242

455

1542

689

2338

13544

3611

3675

Note: this calculation is preliminary. The calculation will be updated during detail design. This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

Company Document Identification ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0485

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

3.6 CALCULATION

This document is property of Eni Muara Bakau B.V.. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

Sheet of Sheets

7/35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR FIRST FLOOR (Elevation 103.500) GENERAL INFORMATION Project No. Project Name

: :

Zone Name

:

Location Latitude Time & Month Elevation [ft]

: : : :

Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%]

870111 Jangkrik FPU Complex Project Electrical Floor (Normal Room & Transformer Room) Makasar Strait 1.28 1500 & July 19 m

Reference Calculation

Inside Ratio Humidity [lb/lb dry air]

: :

75.0 45

:

0.0084

o

Outside Design Dry Bulb Temperature [ F]: Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 68.90 Zone Size [L x W x H] (feet) :

103 90.0 0.0416 9 52.50 16.40

L ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

W

H

ROOF (N/A) FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

CLTDCorr LM K CLTDCorr

Roof Without Ceiling 0.100 3617.25 14 ( w/o suspended ceiling ) 0.00

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 1 ( dark color ) f : 23.21 (corr. With daily range) : 26.3

9,495.28

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: : 0.100 3,617.25 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

Tiles (Raised Floor)

10,128.30 WALL & PARTITION

FORMULA

U CLTD Correction

: :

U x A x (CLTD or CLTD Correction) U x A x TD : Sec 6. of 220801BMRBS0486 HVAC Design Philosophy : ASHRAE GRP 158, Table 3.10 : ASHRAE GRP 158, Table 3.13 & 3.12

Assume : for Temperature Different between conditioning space 0 with unconditioning space(TD) : 28.0 F

CLTD Correction : (Table 3.10 ASHRAE GRP 158) LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

:

CLTDCorr :

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)]

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

8 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR FIRST FLOOR (Elevation 103.500) NO.

1 2 3 4 5 6 7 8

MATERIAL

H60 Fire wall H60 Fire wall H60 Fire wall Steel Door H60 Fire wall Steel Door Steel Door H60 Fire wall (wall partition)

Type

Face

Wall

W

Wall

S

Wall

N

Single Door

W

Wall

E

Dbl. Door

E

Dbl. Door

E

Wall

N

22,963.73

Total heat gain through from roof, floor, wall, partition :

A

U

(ft2)

CLTD

(Btu/hr.ft2.0F) (0F)

TD

CLTD Corr.

(0F)

(0F)

28 28 28 28 28 28 28 0

31.79 26.81 26.81 31.79 31.79 31.79 31.79 0.00

1129.96 0.100 14.00 861.00 0.100 14.00 861.00 0.100 14.00 18.08 0.600 14.00 1129.96 0.100 14.00 36.16 0.600 14.00 36.16 0.600 14.00 861.00 0.600 28.00 Total Wall & Door Sensible [Btu/hr] 6.7

BTU/hr (

Sensible (Btu/hr)

3592.14 2308.34 2308.34 344.82 3592.14 689.64 689.64 0.00 12,835.43

:

kW )

VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Transformer Room Space Ventilation (Vbz)

: (Rp x Pz) + (Ra x Az)

Transformer Room Size: (Feet)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

Ez (Air distribution effectiveness) Zone Outdoor Airflow (Voz)

: Vbz / Ez

: : :

2 5 0.06

Person cfm/person

Az

:

1034

ft2

Ez

:

1

19.7 L

52.5 W

16.4 H

52.50 W

16.4 H

cfm/ft2

Minimum Air Change Volume

848

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 72.06

cfm

Outdoor Air Flow Rate

141

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Up Air (CFM)

: 141.35

cfm Ventilation and Fresh Flow Rate for Normal Room

Space Ventilation (Vbz)

: (Rp x Pz) + (Ra x Az)

Normal Room Size: (Feet)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

2 5 0.06

Person cfm/person

Az

:

2584

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

: Vbz / Ez

49.2 L

cfm/ft2

Minimum Air Change Volume

2118.92

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 165.04

cfm

Outdoor Air Flow Rate

353.15

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Up Air (CFM)

: 353.15

cfm

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

9 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR FIRST FLOOR (Elevation 103.500)

Sensible Cooling Load

Total Sensible and Latent Cooling Load Electrical Floor 28.00 : 1.1 x CFM x DT DT : (Outside - Inside Temperature)

Latent Cooling Load

: 4680 x CFM x Dw

Dw

0.033

:

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 504.65 : (Two Double Leaf 2.1 x 1.6 m and One leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) Q CFM

Room Category

:

No. Of People Total Make-Up Air(CFM)

Electrical Floor (Normal Room & Transformer Room)

: :

4 504.65

Latent [Btu/hr]

:

Sensible [Btu/hr] Total Heat [Btu/hr]

: :

78,256.94 15,543.22 93,800.16

INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11 ASHARE GRP 152) Sensible Cooling Load 18 CFM Wind Speed Average : 8 MPH (Approx.) Latent Cooling Load From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) Total Crack Length in the room : 73 feet CFM Leakage through wall and partition

Internal Load Lighting qs

:

0.286

People : Sensible

: 3.41 x qs x Fo x Fs x CLF :

11340

Fo

: 0.7 (100% or all lamp are used)

Fs

: (Table 4.1) 1.2 : 1

CLF

Appliance Data (Approx.) No. Item

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

: Total lamp wattage

: 1.1 x CFM x DT

no's of people x qs x CLF

:

no's of people x ql

Latent :

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

: Power Consumption Watt

See Appliance data table

123,400

Efficiency %

100

Heat Release/Unit [Btu/Hr]

3.41214

(

Total Heat Release [Btu/Hr]

421,058.08

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 421,058.08 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

COOLING LOAD 1. 2. 3. 4.

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

: : : : :

18.150 559.02 2,910.78 344 532

TOTAL COOLING LOAD FOR : ROOM LOAD : : : :

478,335.18 3,442.78 48,177.80 529,955.76

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Electrical Floor (Normal Room & Transformer Room) VENTILATION + MAKE-UP AIR 15,543.22 78,256.94 9,380.02 103,180.18

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

421,058 0 33,410.36 458,814.23

TOTAL 493,878.40 81,699.72 57,557.81 633,135.94

10 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR FIRST FLOOR (Elevation 103.500)

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 psia) Pws : 7.0061 (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure

at Area

Humidity Ratio with

RH

14.7

(

psia)

90%

P

: 101.3529 kPa

w :

0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 psia) Pws : 2.9647 (Saturated Water = kPa Saturation Vapor Press at 75 oF 14.7 Barometric Pressure at Area ( psia) P : 101.3529 kPa 45% 0.0084 Humidity Ratio with RH w : lb/lb

U (Door)

Lamp

0.6

Steel

amount

Tranformer Room + Normal Room

each lamp

Watt

Total wattage

15

0

Total Wattage (as per HVAC Design Philosophy); 15 w/m2 11340

Door Dimension (Double leaf) 6.8 Length : ft Height

:

5.3

ft

Item

Tag Number

1.1

009300EH001

6000 V Switchboard

Equipment

Sensible Heat 8000

1.2

009200EP002

400 V Power Distribution PMCC

6800

Remark

7600 1.5

00470EC001A

Control Panel Turbo Generator-A

1.6

00470EC001B

Control Panel Turbo Generator-B

800

1.7

00470EC001C

Control Panel Turbo Generator-C

800

1.8

009200EC001

EMS Control Management System

800

1.9

009200EC001

LSS Load Shedding System

400

1.10

009200EZ001

EMS Control Desk

400

1.11

003601EM001

Booster Turbo Compressor MCC Train-1

0

1.12

003602EM001

Booster Turbo Compressor MCC Train-2

800

1.13

003603EM001

Booster Turbo Compressor MCC Train-3

800

1.14

003601EM003

Export Gas Turbo Compressor MCC Train-1

800

1.15

003602EM003

Export Gas Turbo Compressor MCC Train-2

800

1.16

003603EM003

Export Gas Turbo Compressor MCC Train-3

800

1.17

004700EM001A

Turbo Generator-A MCC

800

1.18

004700EM001B

Turbo Generator-B MCC

800

1.19

004700EM001C

Turbo Generator-C MCC

800 800

2.1

009200ET001

Power Transformer 6000/400 V

2.2

009200ET002

Power Transformer 6000/400 V

37500

2.3

004700EY001A

Earthing Resistor Turbo Generator-A

37500

2.4

004700EY001B

Earthing Resistor Turbo Generator-B

0

2.5

004700EY001C

Earthing Resistor Turbo Generator-C

0

2.6

009200ET007

Power Transformer 160 kVA

0

2.7

009200ET008

Power Transformer 160 kVA

4800

009200ET011

Power Transformer 100 kVA

4800

009200ET011

Power Transformer 100 kVA

3000 3000

Note: this data will be finalize during detail engineering

123400.00 W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

11 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 108.500) GENERAL INFORMATION Project No. Project Name Zone Name Location Latitude Time & Month Elevation [ft]

: : : : : : :

: Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%] : Inside Ratio Humidity [lb/lb dry air] : Outside Design Dry Bulb Temperature [oF] : Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 65.61 Zone Size [L x W x H] (feet) :

870111 Jangkrik FPU Electrical Floor (Battery Room) Makasar Strait 1.28 1500 & july 19 m

75.0 45 0.0084 103 90.0 0.0416 9 52.49 16.40

L

H

ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

Reference Calculation

W

ROOF (N/A) FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

CLTDCorr LM K CLTDCorr

Roof Without Ceiling 0.100 3443.87 14 ( w/o suspended ceiling ) 0.00

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 1 ( dark color ) f : 23.21 (corr. With daily range) : 26.3

9,040.16

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: Tiles (Raised Floor) : 0.100 3,443.87 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

9,642.83 WALL & PARTITION

FORMULA

: :

U x A x (CLTD or CLTD Correction) U x A x TD

CLTD Correction :

U CLTD Correction

: : :

Sec 6. of 220801BMRBS0486 HVAC Design Philosophy ASHRAE GRP 158, Table 3.10 ASHRAE GRP 158, Table 3.13 & 3.12

LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

Assume : for Temperature Different between conditioning space with unconditioning space(TD) : 28 0F

CLTDCorr NO. 1 2 3 4 5 6

MATERIAL H60 Fire wall H60 Fire wall H60 Fire wall Steel Door Steel Door H60 Fire wall

Type

Face

Wall

W

Wall

S

Wall

N

Dbl. Door

W

Single Door

S

Wall

E

Total heat gain through from roof, floor, wall, partition :

(Table 3.10)

A

:

: U

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)] CLTD

TD

(ft2) (Btu/hr.ft2.0F) (0F) (0F) 1076.00 0.100 14.00 28 860.84 0.100 14.00 28 860.84 0.100 14.00 28 36.16 0.600 14.00 28 18.08 0.600 14.00 28 1076.00 0.100 14.00 28 Total Wall & Door Sensible [Btu/hr] :

22,575.45

BTU/hr (

6.6

CLTD Corr. (0F) 31.79 26.81 35.94 31.79 43.81 31.79

Sensible (Btu/hr) 3420.62 2307.90 3093.84 689.64 475.20 3420.62 12,932.62

kW )

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

12 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 108.500)

VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Battery Room : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

2 5 0.06

Person cfm/person

Az

:

3444

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

65.6 L

Battery Room Size: (Feet)

: Vbz / Ez

52.5 W

16.40 H

cfm/ft2

11296

Minimum Air Change Volume

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 216.63

cfm

Outdoor Air Flow Rate

471

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

: 470.66

Make Up Air (CFM)

cfm

Exhaust Air for Battery Room (Assume for Nicad Battery, exhaust ventilation following as per 5.3.7. Room Air Flow Rates) with Q (m3/h) = (0.05 x n x l) ; Q = Air flow rate (m3/h) ; n = number of cells (800 cells x 0.5 utility factor = 400) I = charging current at end of high rate charging, but not less that 25% of rated charge input (200A x 0.5 utility factor = 100A) Q = 2000 m3/h =

1180

CFM N/A : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Room Size: (Feet) L

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

Person cfm/person

Az

:

ft2

Ez (Air distribution effectiveness)

Ez

:

Zone Outdoor Airflow (Voz)

: Vbz / Ez

W

H

cfm/ft2

Minimum Air Change Volume

0

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

:

cfm

0

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Up Air (CFM)

:

cfm

Sensible Cooling Load

Total Sensible and Latent Cooling Load Electrical Floor 28.00 : 1.1 x CFM x DT (Outside - Inside Temperature) DT :

Latent Cooling Load

: 4680 x CFM x Dw

Dw

:

0.033

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 302.65 : (One Double Leaf 2.1 x 1.6 m and one Single Leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) CFM Q

Room Category No. Of People Total Make-Up Air(CFM)

: Electrical Floor (Battery Room) : 2 470.66 :

Latent [Btu/hr] Sensible [Btu/hr] Total Heat [Btu/hr]

: : :

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

72,986.38 14,496.39 87,482.77

13 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 108.500) INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11) 18.15 CFM Wind Speed Average : 7.5 MPH (Approx.) From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) 72.6 Total Crack Length in the room : feet

Internal Load Lighting qs

0.228547

:

CFM Leakage through wall and partition

: 1.1 x CFM x DT

Latent Cooling Load

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

People : Sensible :

:

3.41 x qs x Fo x Fs x CLF

:

Total lamp wattage

Fo

:

0.7 (100% or all lamp are used)

Fs CLF

: :

(Table 4.1) 1.2 1

:

Sensible Cooling Load

10800

Latent

no's of people x qs x CLF no's of people x ql

:

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

:

Appliance Data (Approx.) No. Item

Power Consumption Watt

See Appliance data table

Efficiency %

100

1,330

Heat Release/Unit [Btu/Hr]

(

3.41214

Total Heat Release [Btu/Hr]

4,538.15

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 4,538.15 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

: : : : :

TOTAL COOLING LOAD FOR : ROOM LOAD

COOLING LOAD 1. 2. 3. 4.

18.150 559.02 2,910.78 172 266

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Electrical Floor (Battery Room) VENTILATION + MAKE-UP AIR

59,664.01 3,176.78 6,284.08 69,124.86

: : : :

14,496.39 72,986.38 8,748.28 96,231.05

4,538 0 31,819.39 40,265.33

TOTAL 74,160.40 76,163.15 15,032.36 165,355.91

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 7.0061 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure Humidity Ratio with

at Area RH

(

14.7

psia)

90%

P

:

w :

101.3529 kPa 0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 2.9647 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 75 oF Barometric Pressure Humidity Ratio with

at Area RH

( 45%

14.7

psia)

P

:

w :

101.3529 kPa 0.0084 lb/lb

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

14 of 35

Company Document Identification

ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 108.500)

U (Door)

Lamp

0.6

Steel

amount

Battery Room

each lamp

Watt

Total wattage

15

0

Total Wattage (as per HVAC Design Philosophy); 15 w/m2 10800

Door Dimension Length

:

6.8 ft

Height

:

5.3 ft

Item

Tag Number

1.1

009000EB001A

230 Vac Instrumentation UPS Batteries-A

Equipment

0

1.2

009000EB001B

230 Vac Instrumentation UPS Batteries-A

0

1.3

009000EB002A

230 Vac Electrical UPS Batteries-A

0

1.4

009000EB002B

230 Vac Electrical UPS Batteries-A

0

1.5

007200EC001

Navigation Aids Batteries

0

1.6

003601EB001

Booster Turbo Compressor Battery Train-1

0

1.7

003602EB001

Booster Turbo Compressor Battery Train-2

0

1.8

003603EB001

Booster Turbo Compressor Battery Train-3

0

1.9

003601EB003

Export Gas Turbo Compressor Battery Train-1

0

1.10

003602EB003

Export Gas Turbo Compressor Battery Train-2

0

1.11

003603EB003

Export Gas Turbo Compressor Battery Train-3

0

1.12

004700EB001 A

Turbo Generator-A Battery

0

1.13

004700EB001 B

Turbo Generator-B Battery

0

1.14

004700EB001 C

Turbo Generator-C Battery

1.15

HOLD

Instrument UPS Battery CB-A

200

1.16

HOLD

Instrument UPS Battery CB-B

200

1.17

HOLD

Electrical UPS Battery CB-A

130

1.18

HOLD

Electrical UPS Battery CB-B

130

1.19

HOLD

Navigation Aids Battery CB

130

1.2

HOLD

Booster Compressor Battery CB-A Train-1

60

1.21

HOLD

Booster Compressor Battery CB-B Train-2

60

1.22

HOLD

Booster Compressor Battery CB-C Train-3

60

1.23

HOLD

Export Gas Turbo Compr. Battery CB-A Train-1

60

1.24

HOLD

Export Gas Turbo Compr. Battery CB-B Train-2

60

1.25

HOLD

Export Gas Turbo Compr. Battery CB-C Train-3

60

1.26

HOLD

Turbo Generator-A Battery CB-A

60

1.27

HOLD

Turbo Generator-B Battery CB-B

60

1.28

HOLD

Turbo Generator-C Battery CB-C

60 1330.00

Note: this data will be finalize during detail engineering

Sensible Heat

Remark

0

W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

15 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR THIRD FLOOR (Elevation 113.500) GENERAL INFORMATION Project No. Project Name

: :

Zone Name

:

Location Latitude Time & Month Elevation [ft]

: : : :

Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%]

870111 Jangkrik FPU Electrical Floor (Normal Room & Emergency Room) Makasar Strait 1.28 1500 & july 19 m

Inside Ratio Humidity [lb/lb dry air]

: :

75.0 45

:

0.0084

o

Outside Design Dry Bulb Temperature [ F] : Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 65.61 Zone Size [L x W x H] (feet) :

103 90.0 0.0416 9 52.49 16.40

L

W

H

ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

Reference Calculation

ROOF (N/A) FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

Roof Without Ceiling 0.100 3443.87 14 ( w/o suspended ceiling )

CLTDCorr LM K CLTDCorr

0.00

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 1 ( dark color ) f : 23.21 (corr. With daily range) : 26.3

9,040.16

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: Tiles (Raised Floor) : 0.100 3,443.87 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

9,642.83 WALL & PARTITION

FORMULA

: :

U x A x (CLTD or CLTD Correction) U x A x TD

CLTD Correction :

U CLTD Correction

: : :

Sec 6. of 220801BMRBS0486 HVAC Design Philosophy ASHRAE GRP 158, Table 3.10 ASHRAE GRP 158, Table 3.13 & 3.12

Assume : for Temperature Different between conditioning space with unconditioning space(TD) : 28 0F

NO. 1 2 3 4 5 6 7 8

MATERIAL H60 Fire wall H60 Fire wall H60 Fire wall Steel Door Steel Door H60 Fire wall H60 Fire wall (wall partition) Steel Door

Type

Face

Wall

W

Wall

S

Wall

N

Dbl. Door

E

Single Door

S

Wall

E

Wall

N

Dbl. Door

E

Total heat gain through from roof, floor, wall, partition :

A

(Table 3.10)

LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

:

CLTDCorr

: U

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)] CLTD

TD

(ft2) (Btu/hr.ft2.0F) (0F) (0F) 1076.00 0.100 14.00 28 860.84 0.100 14.00 28 860.84 0.100 14.00 28 36.16 0.600 14.00 28 18.08 0.600 14.00 28 1076.00 0.100 14.00 28 860.84 0.100 28.00 0 36.16 0.600 14.00 28 Total Wall & Door Sensible [Btu/hr] : 22,575.45 BTU/hr ( 6.6 kW )

CLTD Corr. (0F) 31.79 26.81 35.94 31.79 0.00 31.79 0.00 31.79

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

Sensible (Btu/hr) 3420.62 2307.90 3093.84 689.64 0.00 3420.62 0.00 689.64 12,932.62

16 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR THIRD FLOOR (Elevation 113.500)

VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Emergency Room : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

2 5 0.06

Person cfm/person

Az

:

1722

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

32.8 L

Emergency Room Size: (Feet)

: Vbz / Ez

52.5 W

16.40 H

52.5 W

16.40 H

cfm/ft2

1411.8

Minimum Air Change Volume

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 113.30

cfm

Outdoor Air Flow Rate

235

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

: 235.30

Make Air (CFM)

cfm

Ventilation and Fresh Air Flow Rate for Normal Room : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

2 5 0.06

Person cfm/person

Az

:

1722

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

32.8 L

Normal Room Size: (Feet)

: Vbz / Ez

cfm/ft2

Minimum Air Change Volume

1411.771

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 113.30

cfm

Outdoor Air Flow Rate

235

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Air (CFM)

: 235.30

Sensible Cooling Load

Total Sensible and Latent Cooling Load Electrical Floor 28.00 : 1.1 x CFM x DT (Outside - Inside Temperature) DT :

Latent Cooling Load

: 4680 x CFM x Dw

cfm

Dw

:

0.033

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 504.65 : (Two Double Leaf 2.1 x 1.6 m and one single leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) CFM Q

Room Category No. Of People Total Make-Up Air(CFM)

Electrical Floor (Normal Room & Emergency Room) : 4 504.65 : :

Latent [Btu/hr]

:

Sensible [Btu/hr] Total Heat [Btu/hr]

: :

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

78,256.94 15,543.22 93,800.16

17 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR THIRD FLOOR (Elevation 113.500) INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11) 18.15 CFM Wind Speed Average : 7.5 MPH (Approx.) From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) 72.6 Total Crack Length in the room : feet

Internal Load Lighting qs

0.228547

:

CFM Leakage through wall and partition

: 1.1 x CFM x DT

Latent Cooling Load

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

People : Sensible :

:

3.41 x qs x Fo x Fs x CLF

:

Total lamp wattage

Fo

:

0.7 (100% or all lamp are used)

Fs CLF

: :

(Table 4.1) 1.2 1

:

Sensible Cooling Load

10800

Latent

no's of people x qs x CLF no's of people x ql

:

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

:

Appliance Data (Approx.) No. Item

Power Consumption Watt

See Appliance data table

Efficiency %

100

36,710

Heat Release/Unit [Btu/Hr]

(

3.41214

Total Heat Release [Btu/Hr]

125,259.66

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 125,259.66 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

: : : : :

TOTAL COOLING LOAD FOR : ROOM LOAD

COOLING LOAD 1. 2. 3. 4.

18.150 559.02 2,910.78 344 532

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Electrical Floor (Normal Room & Emergency Room) VENTILATION + MAKE-UP AIR

180,557.52 3,442.78 18,400.03 202,400.33

: : : :

15,543.22 78,256.94 9,380.02 103,180.18

125,260 0 31,819.39 161,424.85

TOTAL 196,100.74 81,699.72 27,780.05 305,580.51

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 7.0061 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure Humidity Ratio with

at Area RH

(

14.7

psia)

90%

P

:

w :

101.3529 kPa 0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 2.9647 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 75 oF Barometric Pressure Humidity Ratio with

at Area RH

( 45%

14.7

psia)

P

:

w :

101.3529 kPa 0.0084 lb/lb

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

18 of 35

Company Document Identification

ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

COOLING LOAD CALCULATION FOR THIRD FLOOR (Elevation 113.500)

U (Door)

Lamp

0.46

Steel

amount

each lamp

Normal Room and Emergency Room

Watt

Total wattage

Total Wattage (as per HVAC Design Philosophy); 15 w/m2 10800

15

Door Dimension Length

:

6.8 ft

Height

:

5.3 ft

Item

Tag Number

Equipment

Sensible Heat

1.1

009200EL002

230 V Lighting & Small Power Switchboard

400

1.2

009300EL001

230 V Distribution Board

400

1.3

009200HM001

Fuel Gas Electrical Heater Thyristor Panel

500

1.4

HOLD

Essential Distributaion Board

1.5

HOLD

Turbo Generator-A VFD Panel

0

1.6

HOLD

Turbo Generator-B VFD Panel

0

1.7

HOLD

Turbo Generator-C VFD Panel

0

1.8

HOLD

Turbo Generator-A Line Reactor

0

1.9

HOLD

Turbo Generator-B Line Reactor

0

1.10

HOLD

Turbo Generator-C Line Reactor

0

1.11

HOLD

Booster Turbo Compressor Train-1 VFD Panel

0

1.12

HOLD

Booster Turbo Compressor Train-2 VFD Panel

0

1.13

HOLD

Booster Turbo Compressor Train-3 VFD Panel

0

1.14

HOLD

Booster Turbo Compressor Train-1 Line Reactor

0

1.15

HOLD

Booster Turbo Compressor Train-2 Line Reactor

0

1.16

HOLD

Booster Turbo Compressor Train-3 Line Reactor

0

1.17

HOLD

Export Gas Turbo Compr. Train-1 VFD Panel

0

1.18

HOLD

Export Gas Turbo Compr. Train-2 VFD Panel

0

1.19

HOLD

Export Gas Turbo Compr. Train-3 VFD Panel

0

1.2

HOLD

Export Gas Turbo Compr. Train-1 Line Reactor

0

1.21

HOLD

Export Gas Turbo Compr. Train-2 Line Reactor

0

1.22

HOLD

Export Gas Turbo Compr. Train-3 Line Reactor

0

2.1

009300EP001

400 V Emergency Power Distribution PMCC

5000

2.2

009300EP002

400 V Emergency Power Distribution PMCC

2000

2.3

009300EL002

230 V Emergency Lighting & Small Power Switchboard

1400

2.4

009200EP005

400 V Essential Top Side Power Distribution PMCC

800

2.5

009300ES001

220 V Distribution Board

2.6

00900EK001A/B

230 Vac Instrumentation UPS

11500

2.7

00900EK002A/B

230 Vac Electrical UPS

3600

2.8

007200EC001

Navigation Aids Control Panel

400

2.9

003601ED001

DC Panel Booster Turbo Compressor Train-1

740

2.10

003602ED001

DC Panel Booster Turbo Compressor Train-2

740

2.11

003603ED001

DC Panel Booster Turbo Compressor Train-3

740

2.12

003601ED003

DC Panel Export Gas Turbo Compressor Train-1

740

2.13

003601ED003

DC Panel Export Gas Turbo Compressor Train-2

740

2.14

003601ED003

DC Panel Export Gas Turbo Compressor Train-3

740

2.15

004700ED001A

DC Panel Turbo Generator-A

740

2.16

004700ED001B

DC Panel Turbo Generator-B

740

2.17

004700ED001C

DC Panel Turbo Generator-C

740

2.18

HOLD

Booster Compressor Battery Charger Train-1

450

2.19

HOLD

Booster Compressor Battery Charger Train-2

450

2.20

HOLD

Booster Compressor Battery Charger Train-3

450

2.21

HOLD

Export Gas Turbo Compr. Battery Charger Train-1

450

2.22

HOLD

Export Gas Turbo Compr. Battery Charger Train-2

450

2.23

HOLD

Export Gas Turbo Compr. Battery Charger Train-3

450

2.24

HOLD

Turbo Generator-A Battery Charger

450

HOLD

Turbo Generator-B Battery Charger

450

HOLD

Turbo Generator-C Battery Charger

Note: this data will be finalize during detail engineering

Remark

450 36710.00 W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

19 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 118.500) GENERAL INFORMATION Project No. Project Name Zone Name Location Latitude Time & Month Elevation [ft]

: : : : : : :

: Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%] : Inside Ratio Humidity [lb/lb dry air] : Outside Design Dry Bulb Temperature [oF] : Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 65.61 Zone Size [L x W x H] (feet) :

870111 Jangkrik FPU Instrument Floor Makasar Strait 1.28 1500 & july 19 m

75.0 45 0.0084 103 90.0 0.0416 9 52.49 16.40

L

H

ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

Reference Calculation

W

ROOF FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

CLTDCorr LM K CLTDCorr

Roof Without Ceiling 0.100 3443.87 14 ( w/o suspended ceiling ) 8,425.43

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 0.8 ( dark color ) f : 21.43 (corr. With daily range) : 24.5

8,425.43

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: Tiles (Raised Floor) : 0.100 3,443.87 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

9,642.83 WALL & PARTITION

FORMULA

: :

U x A x (CLTD or CLTD Correction) U x A x TD

CLTD Correction :

U CLTD Correction

: : :

Sec 6. of 220801BMRBS0486 HVAC Design Philosophy ASHRAE GRP 158, Table 3.10 ASHRAE GRP 158, Table 3.13 & 3.12

LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

Assume : for Temperature Different between conditioning space with unconditioning space(TD) : 28 0F

CLTDCorr NO. 1 2 3 4 5 6

MATERIAL H60 Fire wall H60 Fire wall H60 Fire wall Steel Door Steel Door H60 Fire wall

Type

Face

Wall

W

Wall

S

Wall

N

Dbl. Door

E

Single Door

S

Wall

E

Total heat gain through from roof, floor, wall, partition :

(Table 3.10)

A

:

: U

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)] CLTD

TD

(ft2) (Btu/hr.ft2.0F) (0F) (0F) 1076.00 0.100 14.00 28 860.84 0.100 14.00 28 860.84 0.100 14.00 28 36.16 0.600 14.00 28 18.08 0.600 14.00 28 1076.00 0.100 14.00 28 Total Wall & Door Sensible [Btu/hr] :

31,000.88

BTU/hr (

9.1

CLTD Corr. (0F) 31.79 26.81 35.94 31.79 0.00 31.79

Sensible (Btu/hr) 3420.62 2307.90 3093.84 689.64 0.00 3420.62 12,932.62

kW )

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

20 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 118.500)

VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Instrument Floor : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

2 5 0.06

Person cfm/person

Az

:

3444

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

65.6 L

Instrument Room Size: (Feet)

: Vbz / Ez

52.5 W

16.40 H

W

H

cfm/ft2

2824

Minimum Air Change Volume

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 216.63

cfm

Outdoor Air Flow Rate

471

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

: 470.66

Make Up Air (CFM)

cfm

N/A : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Normal Room Size: (Feet) L

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

Az

:

Ez (Air distribution effectiveness)

Ez

:

Zone Outdoor Airflow (Voz)

: Vbz / Ez

Person cfm/person cfm/ft2 0

ft2

Minimum Air Change Volume

0

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

:

cfm

0

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Air (CFM)

:

cfm

Sensible Cooling Load

Total Sensible and Latent Cooling Load Instrument Floor 28.00 : 1.1 x CFM x DT (Outside - Inside Temperature) DT :

Latent Cooling Load

: 4680 x CFM x Dw

Dw

:

0.033

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 302.65 : (One Double Leaf 2.1 x 1.6 m and one single leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) CFM Q

Room Category

: Instrument Floor

Latent [Btu/hr]

:

No. Of People Total Make-Up Air(CFM)

: :

Sensible [Btu/hr] Total Heat [Btu/hr]

: :

2 470.66

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

72,986.38 14,496.39 87,482.77

21 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 118.500) INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11) 18.15 CFM Wind Speed Average : 7.5 MPH (Approx.) From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) 72.6 Total Crack Length in the room : feet

Internal Load Lighting qs

0.228547

:

CFM Leakage through wall and partition

: 1.1 x CFM x DT

Latent Cooling Load

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

People : Sensible :

:

3.41 x qs x Fo x Fs x CLF

:

Total lamp wattage

Fo

:

0.7 (100% or all lamp are used)

Fs CLF

: :

(Table 4.1) 1.2 1

:

Sensible Cooling Load

10800

Latent

no's of people x qs x CLF no's of people x ql

:

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

:

Appliance Data (Approx.) No. Item

Power Consumption Watt

See Appliance data table

Efficiency %

100

147,770

Heat Release/Unit [Btu/Hr]

(

3.41214

Total Heat Release [Btu/Hr]

504,211.93

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 504,211.93 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

: : : : :

TOTAL COOLING LOAD FOR : ROOM LOAD

COOLING LOAD 1. 2. 3. 4.

18.150 559.02 2,910.78 172 266

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Instrument Floor VENTILATION + MAKE-UP AIR

567,763.22 3,176.78 57,094.00 628,033.99

: : : :

14,496.39 72,986.38 8,748.28 96,231.05

504,212 0 31,819.39 539,939.12

TOTAL 582,259.61 76,163.15 65,842.28 724,265.04

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 7.0061 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure Humidity Ratio with

at Area RH

(

14.7

psia)

90%

P

:

w :

101.3529 kPa 0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 2.9647 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 75 oF Barometric Pressure Humidity Ratio with

at Area RH

( 45%

14.7

psia)

P

:

w :

101.3529 kPa 0.0084 lb/lb

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

22 of 35

Company Document Identification

ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

COOLING LOAD CALCULATION FOR SECOND FLOOR (Elevation 118.500)

U (Door)

Lamp

0.46

Steel

amount

each lamp

Normal Room and Emergency Room

Watt

Total wattage

15

0

Total Wattage (as per HVAC Design Philosophy); 15 w/m2 10800

Door Dimension Length

:

6.8 ft

Height

:

5.3 ft

Item

Tag Number

Equipment

Sensible Heat

3.0

New

ICSS Server Cabinet

6000

3.1

009700JV001

DCS System Cabinet

10000

3.2

009700JJ001

DCS Marshalling Cabinet

7200

3.3

009800JK001

ESD System Cabinet

12000

3.4

009800JJ001

ESD Marshalling Cabinet

4000

3.5

007000JK001

F&G System Cabinet

8000

3.6

007000JJ001

F&G Marshalling Cabinet

7000

3.7

003601JK001

Booster Gas Compressor UCP-Train 1

2000

3.8

003602JK001

Booster Gas Compressor UCP-Train 2

2000

3.9

003603JK001

Booster Gas Compressor UCP-Train 3

2000

3.10

003601JK002

Export Gas Compressor UCP-Train 1

2000

3.11

003602JK002

Export Gas Compressor UCP-Train 2

2000

3.12

003603JK002

Export Gas Compressor UCP-Train 3

2000

3.13

03601JK003

Flash Gas Compressor UCP

1000

3.14

008800JV001

Electrical Power Unit

3000

3.15

008800JV002

Master Control Station

1000

3.16

New

ICSS Network Cabinet

32000

PABX Cabinet

2000

CCTV Cabinet

2750

Crane Radio System Cabinet

400

Meteo& Helideck Motion Cabinet

715

Server Cabinet

3200

Network LAN Cabinet-1

2145

Network LAN Cabinet-2

715

Network LAN Cabinet-3

6870

Network LAN Cabinet-4

715

Network LAN Cabinet-5

715

Network LAN Cabinet-6

715

PAGA-A System Cabinet

4180

PAGA-B System Cabinet

4180

Navigational System Cabinet

800

HLO Cabinet

1150

UHF Radio System Cabinet

2280

GMDSS Console

300

Operator Radio Console

960

ARPA Radar Console

200

Field Equipment on LQ Roof

580

UHF Radio Base Station (E&I Building)

350

Telecom Equipment Supplied by UPS Socket

100

Entertainment Cabinet

6250

Remark

2300

Note: this data will be finalize during detail engineering

147770.00

W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

23 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR WAREHOUSE (Elevation 103.500) GENERAL INFORMATION Project No. Project Name Zone Name Location Latitude Time & Month Elevation [ft]

: : : : : : :

: Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%] : Inside Ratio Humidity [lb/lb dry air] : Outside Design Dry Bulb Temperature [oF] : Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 46.58 Zone Size [L x W x H] (feet) :

870111 Jangkrik FPU Warehouse Makasar Strait 1.28 1500 & july 19 m

75.0 45 0.0084 103 90.0 0.0416 9 32.80 16.40

L

H

ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

Reference Calculation

W

ROOF FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

CLTDCorr LM K CLTDCorr

Roof Without Ceiling 0.100 1527.82 14 ( w/o suspended ceiling ) 4,010.54

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 1 ( dark color ) f : 23.21 (corr. With daily range) : 26.3

4,010.54

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: Tiles (Raised Floor) : 0.100 1,527.82 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

4,277.91 WALL & PARTITION

FORMULA

: :

U x A x (CLTD or CLTD Correction) U x A x TD

CLTD Correction :

U CLTD Correction

: : :

Sec 6. of 220801BMRBS0486 HVAC Design Philosophy ASHRAE GRP 158, Table 3.10 ASHRAE GRP 158, Table 3.13 & 3.12

LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

Assume : for Temperature Different between conditioning space with unconditioning space(TD) : 28 0F

CLTDCorr NO. 1 2 3 5

MATERIAL H60 Fire wall H60 Fire wall Steel Door H60 Fire wall

Type

Face

Wall

W

Wall

S

Dbl. Door

E

Wall

E

Total heat gain through from roof, floor, wall, partition :

(Table 3.10)

A

:

: U

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)] CLTD

TD

(ft2) (Btu/hr.ft2.0F) (0F) (0F) 763.91 0.100 14.00 28 537.92 0.100 14.00 28 36.16 0.600 14.00 28 763.91 0.100 14.00 28 Total Wall & Door Sensible [Btu/hr] :

15,277.20

BTU/hr (

4.5

CLTD Corr. (0F) 31.79 26.81 31.79 31.79

Sensible (Btu/hr) 2428.48 1442.16 689.64 2428.48 6,988.76

kW )

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

24 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR WAREHOUSE (Elevation 103.500) VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Warehouse : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

4 5 0.06

Person cfm/person

Az

:

1528

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

46.6 L

Warehouse Size: (Feet)

: Vbz / Ez

32.8 W

16.40 H

W

H

cfm/ft2

1252.8

Minimum Air Change Volume

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 111.67

cfm

208.8

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

: 208.80

Make Air (CFM)

cfm

N/A : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Size: (Feet) L

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

Az

:

Ez (Air distribution effectiveness)

Ez

:

Zone Outdoor Airflow (Voz)

: Vbz / Ez

Person cfm/person cfm/ft2 0

ft2

Minimum Air Change Volume

0

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

:

cfm

0

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Air (CFM)

:

cfm

Sensible Cooling Load

Total Sensible and Latent Cooling Load Warehouse 28.00 : 1.1 x CFM x DT (Outside - Inside Temperature) DT :

Latent Cooling Load

: 4680 x CFM x Dw

Dw

:

0.033

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 202.00 : (One Double Leaf 2.1 x 1.6 m and one single leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) CFM Q

Room Category No. Of People Total Make-Up Air(CFM)

: Warehouse : 2 208.80 :

Latent [Btu/hr] Sensible [Btu/hr] Total Heat [Btu/hr]

: : :

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

32,379.38 6,431.12 38,810.50

25 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR WAREHOUSE (Elevation 103.500) INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11) 18.15 CFM Wind Speed Average : 7.5 MPH (Approx.) From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) 72.6 Total Crack Length in the room : feet

Internal Load Lighting qs

0.121879

:

CFM Leakage through wall and partition

: 1.1 x CFM x DT

Latent Cooling Load

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

People : Sensible :

:

3.41 x qs x Fo x Fs x CLF

:

Total lamp wattage

Fo

:

0.7 (100% or all lamp are used)

Fs CLF

: :

(Table 4.1) 1.2 1

:

Sensible Cooling Load

1704

Latent

no's of people x qs x CLF no's of people x ql

:

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

:

Appliance Data (Approx.) No. Item

Power Consumption Watt

See Appliance data table

Efficiency %

100

0

Heat Release/Unit [Btu/Hr]

(

3.41214

Total Heat Release [Btu/Hr]

-

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 0.00 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

: : : : :

TOTAL COOLING LOAD FOR : ROOM LOAD

COOLING LOAD 1. 2. 3. 4.

18.150 559.02 2,910.78 172 266

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Warehouse VENTILATION + MAKE-UP AIR

21,028.61 3,176.78 2,420.54 26,625.93

: : : :

6,431.12 32,379.38 3,881.05 42,691.55

0 0 5,020.39 8,928.19

TOTAL 27,459.73 35,556.16 6,301.59 69,317.48

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 7.0061 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure Humidity Ratio with

at Area RH

(

14.7

psia)

90%

P

:

w :

101.3529 kPa 0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 2.9647 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 75 oF Barometric Pressure Humidity Ratio with

at Area RH

( 45%

14.7

psia)

P

:

w :

101.3529 kPa 0.0084 lb/lb

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

26 of 35

Company Document Identification

ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

COOLING LOAD CALCULATION FOR WAREHOUSE (Elevation 103.500)

U (Door)

Lamp

amount

each lamp

Watt

Total wattage

Total Wattage (as per HVAC Design Philosophy); 15 w/m2

0.46

Steel

Warehouse

12

0

1704

Door Dimension Length

:

6.8 ft

Height

:

5.3 ft

Item

Tag Number

Note: this data will be finalize during detail engineering

Equipment

Sensible Heat

0.00

Remark

W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

27 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR WORKSHOP (Elevation 103.500) GENERAL INFORMATION Project No. Project Name Zone Name Location Latitude Time & Month Elevation [ft]

: : : : : : :

: Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%] : Inside Ratio Humidity [lb/lb dry air] : Outside Design Dry Bulb Temperature [oF] : Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 46.58 Zone Size [L x W x H] (feet) :

870111 Jangkrik FPU Workshop Makasar Strait 1.28 1500 & july 19 m

75.0 45 0.0084 103 90.0 0.0416 9 32.80 16.40

L

H

ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

Reference Calculation

W

ROOF FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

CLTDCorr LM K CLTDCorr

Roof Without Ceiling 0.100 1527.82 14 ( w/o suspended ceiling ) 4,010.54

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 1 ( dark color ) f : 23.21 (corr. With daily range) : 26.3

4,010.54

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: Tiles (Raised Floor) : 0.100 1,527.82 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

4,277.91 WALL & PARTITION

FORMULA

: :

U x A x (CLTD or CLTD Correction) U x A x TD

CLTD Correction :

U CLTD Correction

: : :

Sec 6. of 220801BMRBS0486 HVAC Design Philosophy ASHRAE GRP 158, Table 3.10 ASHRAE GRP 158, Table 3.13 & 3.12

LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

Assume : for Temperature Different between conditioning space with unconditioning space(TD) : 28 0F

CLTDCorr NO. 1 2 3 4

MATERIAL H60 Fire wall H60 Fire wall Steel Door H60 Fire wall

Type

Face

Wall

W

Wall

S

Dbl. Door

E

Wall

E

Total heat gain through from roof, floor, wall, partition :

(Table 3.10)

A

:

: U

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)] CLTD

TD

(ft2) (Btu/hr.ft2.0F) (0F) (0F) 763.91 0.100 14.00 28 537.92 0.100 14.00 28 36.16 0.600 14.00 28 763.91 0.100 14.00 28 Total Wall & Door Sensible [Btu/hr] :

15,277.20

BTU/hr (

4.5

CLTD Corr. (0F) 31.79 26.81 31.79 31.79

Sensible (Btu/hr) 2428.48 1442.16 689.64 2428.48 6,988.76

kW )

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

28 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR WORKSHOP (Elevation 103.500) VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Workshop : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

46.6 L

Workshop Size: (Feet)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

4 5 0.06

Person cfm/person

Az

:

1528

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

: Vbz / Ez

32.8 W

16.40 H

W

H

cfm/ft2

1252.8

Minimum Air Change Volume

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 111.67

cfm

208.8

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

: 208.80

Make Air (CFM)

cfm

N/A : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Size: (Feet) L

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

Az

:

Ez (Air distribution effectiveness)

Ez

:

Zone Outdoor Airflow (Voz)

: Vbz / Ez

Person cfm/person cfm/ft2 0

ft2

Minimum Air Change Volume

0

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

:

cfm

0

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Air (CFM)

:

cfm

Sensible Cooling Load

Total Sensible and Latent Cooling Load Workshop 28.00 : 1.1 x CFM x DT (Outside - Inside Temperature) DT :

Latent Cooling Load

: 4680 x CFM x Dw

Dw

:

0.033

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 202.00 : (One Double Leaf 2.1 x 1.6 m and one single leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) CFM Q

Room Category No. Of People Total Make-Up Air(CFM)

: Workshop : 4 208.80 :

Latent [Btu/hr] Sensible [Btu/hr] Total Heat [Btu/hr]

: : :

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

32,379.38 6,431.12 38,810.50

29 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR WORKSHOP (Elevation 103.500) INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11) 18.15 CFM Wind Speed Average : 7.5 MPH (Approx.) From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) 72.6 Total Crack Length in the room : feet

Internal Load Lighting qs

0.121879

:

CFM Leakage through wall and partition

: 1.1 x CFM x DT

Latent Cooling Load

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

People : Sensible :

:

3.41 x qs x Fo x Fs x CLF

:

Total lamp wattage

Fo

:

0.7 (100% or all lamp are used)

Fs CLF

: :

(Table 4.1) 1.2 1

:

Sensible Cooling Load

2130

Latent

no's of people x qs x CLF no's of people x ql

:

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

:

Appliance Data (Approx.) No. Item

Power Consumption Watt

See Appliance data table

Efficiency %

100

14,000

Heat Release/Unit [Btu/Hr]

(

3.41214

Total Heat Release [Btu/Hr]

47,769.96

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 47,769.96 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

: : : : :

TOTAL COOLING LOAD FOR : ROOM LOAD

COOLING LOAD 1. 2. 3. 4.

18.150 559.02 2,910.78 344 532

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Workshop VENTILATION + MAKE-UP AIR

70,225.67 3,442.78 7,366.84 81,035.29

: : : :

6,431.12 32,379.38 3,881.05 42,691.55

47,770 0 6,275.49 58,391.25

TOTAL 76,656.79 35,822.16 11,247.89 123,726.84

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 7.0061 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure Humidity Ratio with

at Area RH

(

14.7

psia)

90%

P

:

w :

101.3529 kPa 0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 2.9647 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 75 oF Barometric Pressure Humidity Ratio with

at Area RH

( 45%

14.7

psia)

P

:

w :

101.3529 kPa 0.0084 lb/lb

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

30 of 35

Company Document Identification

ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

COOLING LOAD CALCULATION FOR WORKSHOP (Elevation 103.500)

U (Door)

Lamp

0.46

Steel

amount

Workshop

each lamp

Watt

Total wattage

15

0

Total Wattage (as per HVAC Design Philosophy); 15 w/m2 2130

Door Dimension Length

:

6.8 ft

Height

:

5.3 ft

Item

Tag Number

Note: this data will be finalize during detail engineering

Equipment

Sensible Heat

Drilling Machine Portable

1000

Grinding Machine Portable

1000

Welding Machine Portable

5000

Cutting Machine Portabe

2000

Injection Pump/Hydraulic Pump

3000

Vacuum Pump

2000

14000.00

Remark

W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

31 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR LABORATORY (103.500) GENERAL INFORMATION Project No. Project Name Zone Name Location Latitude Time & Month Elevation [ft]

: : : : : : :

: Inside Design Dry Bulb Temp. [0F] Inside Relative Humidity [%] : Inside Ratio Humidity [lb/lb dry air] : Outside Design Dry Bulb Temperature [oF] : Outside Relative Humidity [%] : Outside Ratio Humidity [lb/lb dry air] : Daily Range [K] : 28.85 Zone Size [L x W x H] (feet) :

870111 Jangkrik FPU Laboratory Makasar Strait 1.28 1500 & july 19 m

75.0 45 0.0084 103 90.0 0.0416 9 19.68 16.40

L

H

ASHRAE GRP 158 (COOLING & HEATING LOAD CALCULATION MANUAL)

:

Reference Calculation

W

ROOF FORMULA

:

U x A x CLTD

Material U [Btu/hr.ft2.0f] Roof Area (A) [ft2] CLTD [0F]

: : : :

Roof Sensible [Btu/hr]

:

CLTDCorr LM K CLTDCorr

Roof Without Ceiling 0.100 567.77 14 ( w/o suspended ceiling ) 1,490.39

: [(CLTD + LM) x K + (78 - TR) + (TO - 85)] x f : 0 (big one) 0.75 : 1 ( dark color ) f : 23.21 (corr. With daily range) : 26.3

1,490.39

(no Corr)

FLOOR FORMULA

:

U x A x TD

Material U [Btu/hr.ft2.0f] Floor Area (A) [ft2] Temp Diff. (TD) [0F]

: Tiles (Raised Floor) : 0.100 567.77 : : 28 (Assume)

Floor Sensible [Btu/hr]

:

1,589.75 WALL & PARTITION

FORMULA

: :

U x A x (CLTD or CLTD Correction) U x A x TD

CLTD Correction :

U CLTD Correction

: : :

Sec 6. of 220801BMRBS0486 HVAC Design Philosophy ASHRAE GRP 158, Table 3.10 ASHRAE GRP 158, Table 3.13 & 3.12

LM (Latitude Correction) : (ASHRAE GRP 158, Table 3.12) -1 4 W : N : -7 -1 S : E :

K

Assume : for Temperature Different between conditioning space with unconditioning space(TD) : 28 0F

CLTDCorr NO. 1 2 3 4 5

MATERIAL H60 Fire wall H60 Fire wall Steel Door H60 Fire wall H60 Fire wall

Type

Face

Wall

W

Wall

S

Dbl. Door

E

Wall

E

Wall

N

Total heat gain through from roof, floor, wall, partition :

(Table 3.10)

A

:

: U

0.83

(Medium Wall Colored)

[(CLTD + LM) x K + (78 - TR) + (TO - 85)] CLTD

TD

(ft2) (Btu/hr.ft2.0F) (0F) (0F) 473.14 0.100 14.00 28 322.75 0.100 14.00 28 36.16 0.600 14.00 28 473.14 0.100 14.00 28 322.75 0.100 14.00 28 Total Wall & Door Sensible [Btu/hr] : 9,351.95

BTU/hr (

2.7

CLTD Corr. (0F) 31.79 26.81 31.79 31.79 52.94

Sensible (Btu/hr) 1504.11 865.30 689.64 1504.11 1708.65 6,271.81

kW )

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

32 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR LABORATORY (103.500) VENTILATION AND FRESH AIR FLOW RATE Ventilation and Fresh Air Flow Rate for Laboratory : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

28.9 L

Laboratory Size: (Feet)

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

4 5 0.06

Person cfm/person

Az

:

568

ft2

Ez (Air distribution effectiveness)

Ez

:

1

Zone Outdoor Airflow (Voz)

: Vbz / Ez

19.7 W

16.40 H

W

H

cfm/ft2

1241.5

Minimum Air Change Volume

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

: 54.07

cfm

1241.5

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

: 1241.52

Make Air (CFM)

cfm

N/A : (Rp x Pz) + (Ra x Az)

Space Ventilation (Vbz)

Normal Room Size: (Feet) L

Pz (Zone Population) Rp (Outdoor Air Flowrate required per person) Ra (Outdoor Air Flowrate required per area) Az (Zone floor area)

Pz Rp Ra

: : :

Az

:

Ez (Air distribution effectiveness)

Ez

:

Zone Outdoor Airflow (Voz)

: Vbz / Ez

Person cfm/person cfm/ft2 0

ft2

Minimum Air Change Volume

0

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Zone Outdoor Airflow (Voz)

:

cfm

0

Outdoor Air Flow Rate

CFM

(As per Sec. 3.7 220801BMRBS0486 HVAC Design Philosophy)

Make Air (CFM)

:

cfm

Sensible Cooling Load

Total Sensible and Latent Cooling Load Electrical Floor 28.00 : 1.1 x CFM x DT (Outside - Inside Temperature) DT :

Latent Cooling Load

: 4680 x CFM x Dw

Dw

:

0.033

(Outside - Inside humidity ratio)

Leakage through door (As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy) 302.65 : (One Double Leaf 2.1 x 1.6 m and one single leaf 2.1 x 0.8 m door type with diff. pressure 30 Pa) CFM Q

Room Category No. Of People Total Make-Up Air(CFM)

: Laboratory : 4 1241.52 :

Latent [Btu/hr] Sensible [Btu/hr] Total Heat [Btu/hr]

: : :

192,524.54 38,238.80 230,763.34

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

33 of 35

Company Document Identification

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

ENI MUARA BAKAU B.V

COOLING LOAD CALCULATION FOR LABORATORY (103.500) INFILTRATION & INTERNAL LOAD Infiltration CFM

:

Total Crack Length x (Q/P from Fig. 5.11) 18.15 CFM Wind Speed Average : 7.5 MPH (Approx.) From Fig. 5.11 (Q/P) : 0.25 (k assumed : 1) 72.6 Total Crack Length in the room : feet

Internal Load Lighting qs

0.074873

:

CFM Leakage through wall and partition

: 1.1 x CFM x DT

Latent Cooling Load

: 4680 x CFM x Dw

(As per Sec. 5.3.3. 220801BMRBS0486 HVAC Design Philosophy, 10-5 m3/h per m2)

CFM

People : Sensible :

:

3.41 x qs x Fo x Fs x CLF

:

Total lamp wattage

Fo

:

0.7 (100% or all lamp are used)

Fs CLF

: :

(Table 4.1) 1.2 1

:

Sensible Cooling Load

633.24

Latent

no's of people x qs x CLF no's of people x ql

:

Appliance & Power Equipment : Heat losses from instrument & electrical equipments

:

Appliance Data (Approx.) No. Item

Power Consumption Watt

See Appliance data table

Efficiency %

100

12,100

Heat Release/Unit [Btu/Hr]

(

3.41214

Total Heat Release [Btu/Hr]

41,286.89

)

Note a : taken from existing data (see Carrier Calculation R-1820-004129-013) 41,286.89 : Total Appliance Sensible [Btu/hr.ft2.0F] Total CFM Of Infiltration Infiltration Sensible [Btu/hr] Infiltration Latent [Btu/hr] People Sensible [Btu/hr] People Latent [Btu/hr]

: : : : :

TOTAL COOLING LOAD FOR : ROOM LOAD

COOLING LOAD 1. 2. 3. 4.

18.150 559.02 2,910.78 344 532

Sensible [Btu/hr] Latent [Btu/hr] Safety Factor (10%) TOTAL [Btu/hr]

Appliances Sensible[Btu/hr] Appliances Latent [Btu/hr] Lamp Sensible [Btu/hr]

: : :

Total Heat [Btu/hr]

:

Laboratory VENTILATION + MAKE-UP AIR

53,407.54 3,442.78 5,685.03 62,535.35

: : : :

38,238.80 192,524.54 23,076.33 253,839.67

41,287 0 1,865.68 47,498.37

TOTAL 91,646.34 195,967.32 28,761.37 316,375.03

ATTACHMENTS Calculation Outside Humidity Ratio at 103 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 1.016152 7.0061 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 103 oF Barometric Pressure Humidity Ratio with

at Area RH

(

14.7

psia)

90%

P

:

w :

101.3529 kPa 0.0416

lb/lb

Calculation Inside Humidity Ratio at 75 deg. F : w = 0.62198 x (Pws) / (P - Pws) (Refer to ASHRAE Fundamentals Handbook, Chapter 6 - Psychrometrics, Equation 21) 0.43 2.9647 psia) Pws : (Saturated Water = kPa Saturation Vapor Press at 75 oF Barometric Pressure Humidity Ratio with

at Area RH

( 45%

14.7

psia)

P

:

w :

101.3529 kPa 0.0084 lb/lb

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.

34 of 35

Company Document Identification

ENI MUARA BAKAU B.V

Revision Index

2201801BMCHS0458

Rev. Number

Validity Status

PRELIMINARY HVAC COOLING LOAD (TOPSIDE BUILDING)

01

CD-FE

COOLING LOAD CALCULATION FOR LABORATORY (103.500)

U (Door)

Lamp

amount

each lamp

Watt

Total wattage

12

0

Total Wattage (as per HVAC Design Philosophy); 12 w/m2

0.46

Steel

Laboratory

633.24

Door Dimension Length

:

6.8 ft

Height

:

5.3 ft

Item

Tag Number

Note: this data will be finalize during detail engineering

Equipment

Sensible Heat

Computer

6000

Electric Kettle

1000

Gas Cooker

600

Refrigeration

1000

Strilizer

3500

12100.00

Remark

W

This document is property of Eni Muara Bakau B.V. It shall neither be shown to Third Parties not used for purposes other than those for which it has been sent.