CUMMINS DIESEL GENERATOR SET

WWW.V-FLO.COM

CUMMINS DIESEL GENERATOR SET 50HZ 33kVA—-550kVA > Description of products: ———Intelligent PCC2100/1301 control system 1.Generator sets of basic characteristic ◆ Low cost, high efficiency, compact structure, environment friendly. ◆ Heavy load durable, four-stroke, water cooled engine. ◆ Excellent transient response. ②STAMFORD Alternator ◆Brushless, four-pole revolving field, single bearing and drop proof screen protected. ◆Class H insulation ◆IP21-IP23 protection standard ◆Super short-circuit the affordability ◆Nonlinear distortion small load voltage waveform ③PCC digital control system The highly integrated control system: ◆Micro-processor control module. ◆To achieve the best reliable operation of generating units ◆Integrated engine speed and voltage regulator function ◆Comply with RFI/EMI standard and surge testing specification Units monitoring and alarm functions: ◆Monitoring engine and generator running ◆Self-diagnosis system function ◆Real-time display engine and generator operating parameters ◆system real–time warning Battery monitoring system: ◆Generators each time you start, monitor battery capacity ◆Weak battery warning ◆Battery high/low voltage alarm Interface ◆Equipped with communication interface ④Integrity of the supporting equipment Generating units installed built-in shock absorber, control system, starting system and others Base ◆ Built-in shock absorption pad used rubber materials ◆Does not require the installation of shock absorption pad for the base and connect with the foundations of fixed Cooling ◆50 ℃ ambient temperature design

WWW.V-FLO.COM

WWW.V-FLO.COM

①CUMMINS DIESEL ENGINE

①Voltage regulator rate The following cases voltage regulator in the rate of less than ±0.5%-±1% ◆Power factor 0.8(logging)-1.0 ◆From the no-load to full load, and in any load condition stable operation ◆From the cooler to the heat engine ◆Speed drop(%) Control system PCC2100 1. AmpSentry TM Protection function ①Cummins’s patented products ②Over current alarm/shut down ③High/Low AC voltage shutdown ④Low frequency shutdown ⑤Over frequency shutdown/alarm ⑥Overload alarm

⑦Reverse power shutdown ⑧Inverse reactive shutdown ⑨Sensor signal loss shutdown

IEC34 NEMA MG1-22

WWW.V-FLO.COM

WWW.V-FLO.COM

5. Other functions

● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ● ●

Digital control engine speed Digital voltage regulation AmpSentry TM protection Analog and digital AC output instrument display Battery weak monitoring system Digital alarm and state information display Generator sets monitoring function Self-diagnosis system function Communication network Advanced PC software application services capabilities Remote auto starting up Control the number of units launched Digital display output Voltage, Current phase of the selection keys “Operating-shutdown-auto” knobs switches Urgent shutting off control Custom interface box Disk background lights Reset button Unified global network of services

3. Parameter Indication ● ● ● ● ● ● ● ● ● ● ● ● ● ●

Generator sets parameter Starting/operating data record Generator sets output voltage Generator sets output current Generator sets output frequency Generator sets output power Generator sets output electricity Battery voltage Engine lube oil pressure Engine cool water temperature System Data display Adjustment of historical data Failure historical data Load parameter

4. Internal control function ①Engine control ● Remote start mode ● Sleep mode ● Data record ● Failure analog mode ● Engine starting ● Turning circle ● Delayed start-up and shutdown ②Engine regulation speed ● Speed sync function ● With the temperature adjustment ● Smart idling mode ③Alternator control ● Digital output voltage adjustment rate ● Torque match voltage overload control ● Fault current adjustment

5. Standard protection function ①Generator sets protection

WWW.V-FLO.COM

WWW.V-FLO.COM

2. Standard Control Function

Fault alarm Urgent shutting off Programmable alarm and state input ②Engine protection ● Over-speed protection ● Lube low pressure alarm/shutdown ● High water temperature alarm/shutdown ● Low level water alarm/shutdown ● Starting /Turning failure ● Turning locking ● Sensor fault display ● Low/high battery voltage alarm ● Leak battery /fault alarm ● Starter not connected

6. EMC Standard PCC2100 control system in line with EMC international standard. ①Communication interface ● Equipped with RS232 communication interface. ● Supported Cummins GOAL agreement. ● Customer monitoring system can be used to obtain data . ● Cummins services can also be used for monitoring software or software INPOWER ②Standard: NFPA110-1 EN50081-1 UL508 EN50081-2 CSA C282-M1999 EN50082-1 CSA 22.2-14 EN50082-2 ISO 8528-4;1993 MIL STD 202C NFPA99 ANSI C62.41 ISO 7637-#2b.4 EC MARKING IEC 801.2.3.4.5 ③Software ● InPower TM service software, implementation services to the unit control system Settings and fault diagnosis. ● Power Command for Windows TM monitoring software, implementation computer monitoring and control. ④Optional parts and accessories ● Key model selection switch ● Fault alarm module ● Exhaust temperature monitoring ● Digital remote alarm box ● Digital output module relay ● Power conversion control ● LonWorks network interface ● Engine oil temperature display

> Control system PCC1301 1. Standard function ● ● ● ● ● ●

Precise voltage regulator 3 phase voltage and current detection Engine starting Generator sets monitoring Generator sets protection Operating display

WWW.V-FLO.COM

WWW.V-FLO.COM

● ● ●

● ● ●

Advanced maintainability Ability to adapt to the environment To set the input and output signals

①Engine control ● Automatic operation mode ● Urgent shutdown ● Sleep mode ● Engine starting ● Multiple-turning ● Engine speed detection ● Mechanical/ electrical speed regulator ● Emergency operation mode ②Alternator control ● Output voltage regulating ● Torque match voltage/frequency overload control

3. Standard protection ①Generator sets protection ● Programmable alarm and status input ● Urgent shutdown ②Engine protection ● Over-speed shutdown ● Lube low pressure alarm/shutdown ● High water temperature alarm/shutdown ● Low water level alarm ● High/low Battery voltage alarm ● Leak battery alarm ● Starting/ turning failure shutdown ● Sensor fault display ③Alternator ● Low/high alternator voltage shutdown ● Over-current alarm/shutdown ● Less frequent shutdown ● Over frequent shutdown ● Voltage signal loss shutdown ● Exciting magnetic field overload shutdown

4. Control system components ● ● ● ● ● ●

Control switch—-RUN/OFF/AUTO “Failure /status” indicator Digital display Screen menu to select button Menu button at the next higher level Engine electronic control module

5. Adjustment parameters ● ● ●

Delayed start:0—300sec Output voltage:±5% Shutdown delay:0-600sec

WWW.V-FLO.COM

WWW.V-FLO.COM

2. Internal controls

Model

unit

C33D5

C38D5

C55D5

C70D5

C80D5

standby

33

38

55

70

80

Prime

30

35

50

63

72

standby

26.4

30.4

44

56

64

prime

24

28

40

50

58

Control model

PCC1301

PCC1301

PCC1301

PCC1301

PCC1301

Manufacture

cummins

cummins

cummins

cummins

cummins

Engine model

4B3.3G1

4B3.3G1

4BT3.3G2

4BT3.9G4

4BTA3.9G1

cylinders

4

4

4

4

4

Cylinders arrangement

L

L

L

L

L

Governor type

mechanism

mechanism

mechanism

mechanism

mechanism

inspiration

natural

natural

turbocharged

turbocharged

Turbocharged intercooled

95*115

95*115

95*115

102*120

102*120

18.2:1

18.2:1

17.0:1

16.5:1

16.5:1

3.3

3.3

3.3

3.92

3.92

No-assist/-12

No-assist/-12

kVA

Bore*stroke

mm

Compression ratio

displacement

L ·

C

Min. temperature cold start

No-assist/-4 No-assist/-4 No-assist/-4

Battery capacity

A/Hr

70

70

70

100

100

Engine prime power

kWm

32

32

46

58

66

Engine standby power

kWm

36

36

51

64

73

Speed

r/min

1500

1500

1500

1500

1500

Engine voltage regulator

±1%

±1%

±1%

±1%

±1%

Engine insulation class

H

H

H

H

H

Prime L/h

7.1

8.4

11.5

15

15

Standby L/h

8

9.4

12.9

16

17

Lube volume

L

7.5

7.5

8.0

10.9

10.9

Base tank volume

L

144

144

144

112

112

Coolant volume

L

7.9

7.9

7.9

17.2

17.9

Exhaust temp.

Prime 100%·C

448

448

380

523

475

Exhaust flow

Prime 100% L/s

89

89

124

170

166

Max. exhaust pressure

Standby mmHg

75

75

75

76

76

Cool air flow

50·C radiator m3/s

1.45

1.45

1.45

1.71

1.71

Fan pressure head

50·C radiator mmWg

10

10

10

13

13

Burning air flow

M3/h

120

126

172.8

237.6

248

Units total radiant heat

kWm

6.3

6.3

10.2

17.1

12.6

100% load fuel

WWW.V-FLO.COM

WWW.V-FLO.COM

KWe

unit

C110D5

C150D5

C180D5

standby

110

150

180

Prime

100

138

164

standby

88

120

144

prime

80

109

131

Control model

PCC1301

PCC1301

PCC1301

Manufacture

cummins

cummins

cummins

Engine model

4ISBeG1

6BTA5.9G2

6ISBeG1

cylinders

4

6

6

Cylinders arrangement

L

L

L

Governor type

electrical

electrical

electrical

kVA

WWW.V-FLO.COM

KWe

inspiration

Turbocharged inter- Turbocharged intercooled

Bore*stroke

mm

Compression ratio displacement

L ·

C

Min. temperature cold start

Turbocharged intercooled

102*120

102*120

102*120

17.3:1

16.5:1

16.5:1

3.92

5.88

5.88

No-assist/-12

No-assist/-12

No-assist/-12

Battery capacity

A/Hr

100

150

150

Engine prime power

kWm

94

131

150

Engine standby power

kWm

102

145

164

Speed

r/min

1500

1500

1500

Engine voltage regulator

±1%

±1%

±1%

Engine insulation class

H

H

H

Prime L/h

23

33

36

Standby L/h

25

35

40

Lube volume

L

13.0

16.4

19.5

Base tank volume

L

112

340

340

Coolant volume

L

19.5

21.9

22

Exhaust temp.

Prime 100%·C

550

578

551

Exhaust flow

Prime 100% L/s

170

391

363

Max. exhaust pressure

Standby mmHg

76

75

75

Cool air flow

50·C radiator m3/s

3.38

5.43

5.29

Fan pressure head

50·C radiator mmWg

13

13

13

Burning air flow

M3/h

309.6

518.4

518.4

Units total radiant heat

kWm

13.7

21

28.4

100% load fuel

WWW.V-FLO.COM

Model

C200D5

C220D5

C250D5

C275D5

C300D5

standby

200

220

250

275

300

Prime

182

200

227

250

275

standby

160

176

200

220

240

prime

146

160

182

200

220

Control model

PCC1301

PCC1301

PCC1301

PCC1301

PCC1301

Manufacture

cummins

cummins

cummins

cummins

cummins

Engine model

6CTAA8.3G1

6CTAA8.3G1

6CTAA8.3G2

QSL9G5

QSL9G5

cylinders

6

6

6

6

6

Cylinders arrangement

L

L

L

L

L

Governor type

electrical

electrical

electrical

Electrical spray

Electrical spray

inspiration

Turbocharged intercooled

Turbocharged intercooled

Turbocharged intercooled

turbocharge

turbocharge

114*135

114*135

114*135

114*145

114*145

16.8:1

16.8:1

16.8:1

16.8:1

16.8:1

8.3

8.3

8.3

8.8

8.8

No-assist/-12

No-assist/-12

kVA

WWW.V-FLO.COM

KWe

Bore*stroke

mm

Compression ratio displacement

L ·

Min. temperature cold start

C

No-assist/-12

No-assist/- No-assist/-12 12

Battery capacity

A/Hr

150

150

150

150

150

Engine prime power

kWm

183

183

210

268

268

Engine standby power

kWm

203

203

231

310

310

Speed

r/min

1500

1500

1500

1500

1500

Engine voltage regulator

±1%

±1%

±1%

±1%

±1%

Engine insulation class

H

H

H

H

H

Prime L/h

41

45

51

52.3

57.3

Standby L/h

45

50

57

58.2

66.2

Lube volume

L

23.8

23.8

23.8

26.5

26.5

Base tank volume

L

350

350

350

604

604

Coolant volume

L

24.3

24.3

24.3

28.6

28.6

Exhaust temp.

Prime 100%·C

553

553

565

500

500

Exhaust flow

Prime 100% L/s

530

530

681

490

490

Max. exhaust pressure

Standby mmHg

76

76

76

76

76

Cool air flow

50·C radiator m3/s

5.43

5.43

5.43

7.93

7.93

Fan pressure head

50·C radiator mmWg

13

13

13

13

13

Burning air flow

M3/h

720

720

918

1116

1116

Units total radiant heat

kWm

24

28

28

30

30

100% load fuel

WWW.V-FLO.COM

unit

Model

C330D5

C350D5

C400D5

C440D5

C500D5

C550D5

standby

330

350

400

440

500

550

Prime

300

320

360

400

450

500

standby

264

280

320

352

400

440

prime

240

256

280

320

360

400

PCC1301 PCC2100

PCC2100

PCC2100

PCC2100

PCC2100

Manufacture

cummins

cummins

cummins

cummins

cummins

cummins

Engine model

QSL9G5

NT855G6

NTA855G4 NTA855G7 QSX15G8

QSX15G8

cylinders

6

6

6

6

6

6

Cylinders arrangement

L

L

L

L

L

L

Governor type

Electrical spray

electrical

electrical

electrical

Electrical spray

Electrical spray

turbocharge

Turbocharged intercooled

Turbocharged intercooled

Turbocharged intercooled

Turbocharged intercooled

140*152

140*152

140*162

137*169

137*169

14.0:1

14.0:1

14.0:1

17.0:1

17.0:1

14

14

14

15

15

No-assist/4

No-assist/-4

No-assist/4

kVA

KWe

WWW.V-FLO.COM

Control model

turbocharge

inspiration

Bore*stroke

114*145

mm

16.8:1

Compression ratio displacement

8.8

L ·

Min. temperature cold start

C

No-assist/- No-assist/- No-assist/12 4 7

Battery capacity

A/Hr

150

200

200

200

200

200

Engine prime power

kWm

268

280

317

355

444

444

Engine standby power

kWm

310

310

351

391

500

500

Speed

r/min

1500

1500

1500

1500

1500

1500

Engine voltage regulator

±1%

±0.5%

±0.5%

±0.5%

±0.5%

±0.5%

Engine insulation class

H

H

H

H

H

H

Prime L/h

63

69

76

75

80

103

Standby L/h

75

76

84

98

87

123

Lube volume

L

26.5

38.6

38.6

36.7

91

91

Base tank volume

L

604

750

750

900

900

900

Coolant volume

L

28.6

63.9

65.8

65.8

65.9

65.9

Exhaust temp.

Prime 100%·C

500

574

524

553

488

488

Exhaust flow

Prime 100% L/s

490

1071

1128

1433

1255

1255

Max. exhaust pressure

Standby mmHg

76

76

76

76

76

76

Cool air flow

50·C radiator m3/s

7.93

4.92

5.99

5.99

10.44

10.44

Fan pressure head

50·C radiator mmWg

13

13

13

13

13

13

Burning air flow

M3/h

1116

1300

1468.8

1468.8

1944

1944

Units total radiant heat

kWm

30

50

46

53

33

33

100% load fuel

WWW.V-FLO.COM

unit

Model

Generator sets model

Engine model

C11D5

Overall dimensions

NET Weight

WET Weight

A

B

C

kg

kg

D1703-BG

1300

730

1130

361

376

C15D5

D1703-BG

1300

730

1130

370

385

C22D5

4B3 3G1

1753

930

1256

544

609

C33D5

4B3.3G1

1753

930

1256

580

645

C38 D5

4B3.3G1

1753

930

1256

640

705

C55D5

4BT3.3G2

1753

930

1256

711

776

C70D5

4BT3 9G4

1950

10^6

1221

1002

1038

C80D5

4BTA3.9G1

1950

1046

1221

1014

1050

C110D5

4ISB&G1

1977

1046

1311

1162

1200

C150D5

6BTA5-9G2

2404

1100

1472

1167

1216

C180D5

6ISBeG1

2404

1100

1487

1400

1444

C200D5

6CTAA8.3G1

2686

1300

1547

1840

1900

C220D5

6CTAA8.3G1

2686

1300

1547

1840

1900

C250D5

6CTMS.3G2

2686

1300

1547

1940

2000

C275 D5

QSL9G5

3135

1100

1928

2119

2171

C300D5

QSL9G5

3135

1100

1928

2342

2394

C330D5

OSL9G5

3135

1100

1928

2422

2474

C350D5

NT855G6

3549

1100

2078

2860

3050

C400D5

NTA855G4

3549

1100

2078

3037

3227

C440D5

NTA855G7

3549

1100

2115

3157

3347

C500D5

OSX-5G8

3433

1500

2065

4022

4117

C550D5

QSX15G8

3433

150O

2065

4125

4220

WWW.V-FLO.COM

WWW.V-FLO.COM

> Overall dimension and weight

Model

Engine model

C11 DS C15 D5 C22D5 C33D5 C38 D5 C55D5 C70D5 C60D5 C110D5 C150D5 C180 D5 C200D5 C220D5 C250D5 C275 D5 C300D5 C330 D5 C350D5 C400D5 C440 D5 C500D5 C550D5 C650D5A 565DFG8 660DFGD C840D5 C900D5 833DFHC 888DFHD 906DFJD C1250D5A C1400 D5 C167S D5A C2000D5 C2250D5 C2500 D5A 2660DQLB

D1703-BG D1703-BG 4B3.3G1 4B3.3G1 4B3 3G1 4BT3.3G2 4BT3 9G4 4BTA3.9G1 4ISBeG1 6BTA5.9G2 6ISBeG1 6CTAAS.3G1 6CTAA8.3G1 6CTAAH3G2 QSL9G5 QSL9G5 QSL9GS NT855G6 NTA855G4 NTA855G7 QSX16G8 OSX1SG8 KTA19G8 VTA28GS VIA28G6 OSK23G3 OSK23G3 QST30G3 QST30G4 KTA38G5 KTA38G9 KTA50G3 KTA50GS8 QSK60G3 QSK60G4 QSK60G8 QSK78G6

100% fuel Standby power Prime power consume (kw) (kw) (L/hr) 8.8 8 2.7 12 10.4 3.5 17.6 16 4.9 264 24 7.1 30.4 28 8.4 44 40 11.5 56 60 15 64 58 16 B8 80 23 120 109 33 144 131 36 160 146 41 176 160 45 203 182 51 220 20O 63 240 220 573 264 240 63 280 256 69 320 288 76 352 320 68 400 360 93 440 400 103 520 472 122 565 512 140 660 600 147 672 608 151 720 656 161 833 751 184 888 800 202 906 823 209 1000 900 231 1120 1000 261 1340 1200 309 1650 1500 355 1800 1600 394 2000 1800 446 2660 2400 592

N.W(kg)

Wet weight (kg)

361 370 544 580 640 711 1002 1014 1162 1167 1400 1840 1840 1940 2119 2342 2422 2860 3037 3157 4022 4125 4225 5730 6389 6550 6700 7152 7712 7960 8650 9099 10324 14649 14863 16690 24637

376 385 609 64 5 705 776 1038 1060 1200 1216 1444 1900 1900 2OU0 2171 2394 2474 3O50 3227 3347 4117 4220 4350 6040 6699 6873 7023 7450 8000 8350 9400 10075 10626 15152 15366 17217 25280

Overall dimensions (L*W*H)(mm) 1300*730*1130 1300*730*1130 1753*930*256 1753*930*1256 1753*930*1256 1753*930*1256 1950*1046*1221 1950*1046*1221 1977*1046*1311 2404*1100*1472 2404*1100*1487 2686*1300*1547 2686*1300*1547 2686*1300*1547 3135*1100*1928 3135*1100*1928 3135*1100*1928 3549*1100*2078 3549*1100*2078 3549*1100*2115 3433"1500*2065 3433*1500*2065 3419*1285*1906 3900*1423*1942 4047*1423*1942 4593*1502*2066 4593*1502*2086 4297*1448*2082 4547*1702*2332 4470*1785*2229 4565*2083*2225 5105*2000*2238 5811*2033*2756 6175*2287*2537 6175*2287*2537 6175*2494*3116 7158*2251*2535

WWW.V-FLO.COM

WWW.V-FLO.COM

>Cummins diesel generator sets 50HZ , 230V/400V,11kVA-3225kVA

View more...