170108-Kula Belgrade-Domestic Hot Water Demand Calculations-Rev00

March 1, 2018 | Author: smiletrinadh | Category: Spa, Restaurants, Energy And Resource, Nature
Share Embed Donate


Short Description

My Documents...

Description

Rev.00

Public Health Engineering Services Calculations

Project Name Work Order Prepared By Date

WAT.01B

Kula Belgrade Greg Jaroszewicz 1/8/2017

Checked By Date

Subject:

Toufic Itani 6/1/2017

Approved By Date

Mohammad Alam 6/1/2017

Stage

Revision Date

SD

Domestic Hot Water Daily Demand - Calculation

Hotel

Guest Rooms

Statutory Storage Requirements

Units per Floor

Occupants per Unit

Total Population Number of meals

Storage per group

[litres per capita per day] / [litres per sq m]

Number

Number

Number

[litres]

1.5

180

24,300

No.'s Sq m

120

Remarks

135

120 keys

TOTAL

24,300

[litres per day]

DHW STORAGE

8,100

[litres]

Hotel Staff

5

270

1,350

Number of staff equal to 150% number of guests

Restaurants

3

540

1,620

Number of meals equal number of gueast x 3 meals per day

Restaurant Staff

5

18

90

Number of staff equal 10% of guests

900

Typical wash cycle in commercial wasching machine requires 15 litres of DHW DHW allowance for a typical stay for 2 days

Laundry

120

7.5

Spa - Customers

20

90

1,800

Number of customers equeal 50% of guests

Spa - Staff

5

9

45

Number of staff equae 10% of Spa Customers

Meeting Rooms

202

2

51

102

Density 1 person per 4m2 DHW allowance only for hand washing

Ballroom

1707

8

427

3,416

Density 1 person per 4m2 DHW allowance for hand washing 2 litres and for meals preparation 6 litres

TOTAL

9,323

[litres per day]

DHW STORAGE

3,108

[litres]

Page 1

Rev.00

Public Health Engineering Services Calculations

Project Name Work Order Prepared By Date

WAT.01B

Kula Belgrade Greg Jaroszewicz 1/8/2017

Checked By Date

Subject:

Toufic Itani 6/1/2017

Approved By Date

Mohammad Alam 6/1/2017

Stage

Revision Date

SD

Domestic Hot Water Daily Demand - Calculation Statutory Storage Requirements

Units per Floor

Occupants per Unit

Total Population Number of meals

Storage per group

[litres per capita per day] / [litres per sq m]

Number

Number

Number

[litres per day]

Residential, Observatory and Landlord Services

No.'s Sq m

1 Bedroom

102

125

12,750

Nominal allowance per bedroom

2 Bedroom

82

210

17,220

Nominal allowance per bedroom

2 Bedroom Duplex

10

210

2,100

Nominal allowance per bedroom

3 Bedroom

16

300

4,800

Nominal allowance per bedroom

3 Bedroom Duplex

10

300

3,000

Nominal allowance per bedroom

Remarks

TOTAL

Retail - Ground Floor

615

3

372

39,870

1,116

TOTAL

1,116

[litres] 615m2 total GFA - 60% seating area, 1 person per 4m2 density Each seat to searve 4 meals per day [litres]

Observatory

1076

1

3228

538

Density 1 person per 2 m2 6 time slots per day DHW allowance only for hand washing

Rooftop Restaurant

813

3

366

813

813m2 total GFA - 60% seating area, 1 person per 4m2 density Each seat to searve 3 meals per day

5

13

65

Number of staff equal 10% of Obervation Deck visitors at any one time

Restaurant Staff

TOTAL

1,416

Parking

0

Services in the Building / MEP

0

Residential Staff

5

4

20

TOTAL

20

[litres]

Nominal number of staff (ie. electricican, plumber, etc.)

[litres]

Page 2

Rev.00

Public Health Engineering Services Calculations

Project Name Work Order Prepared By Date Subject:

WAT.01B Kula Belgrade

Greg Jaroszewicz 1/8/2017

Checked By Date

Incoming Cold Water Temperature: Domestic Hot Water Storage Temperature: Specific Heat Capacity:

10 60 4.187

Toufic Itani 6/1/2017

Approved By Mohammad Alam Stage Date 6/1/2017 Domestic Hot Water Generation - Calculations

Revision Date

CD

[C] [C] [kJ/kg*C]

Hotel and Spa

Hotel

DHW Demand [Litres]

DHW Storage [Litres]

Re-heat Time [seconds]

LTHW Load [kW]

Guest Rooms Kitchen / Spa

8,100 3,108

8,167 3,104

3600 3600

474.9 180.5

TOTAL

11,208

11,272

3600

655.5

Residential Units - Option 2 (primary LTHW and electrical back-up)

Residential

Number of Units [No.]

DHW Storage [Litres]

Re-heat Time [seconds]

LTHW Load [kW]

Electrical Back-up [kW]

[hr]

[min]

Electrical Load [kW]

1 Bedroom 2 Bedroom

102 92

125 210

7200 7200

3.6 6.1

3 3

2 4

25 4

306 276

3 Bedroom

26 0

300

7200

8.7

3

5

49

78 0

220

39,870

7200

1,159

DHW Demand [Litres]

DHW Storage [Litres]

Re-heat Time [seconds]

LTHW Load [kW]

1,416

1,500

3600

87

L

W

H

Capacity

Circulation Time

LTHW Load

[m] 16

[m] 4

[m] 1.5

[m3] 96

[hr] 12

[kW] 134.0

TOTAL

Re-heat time

660

Observatory and Restaurant

Observatory and Restaurant Observatory Rooftop Restaurant Restaurant Staff TOTAL Swimming Pool

Swimming Pool Level 02

TOTAL

Return Water Temperature: [C] 24

Supply Water Temperature: [C] 28

134

Page 3

CIBSE Guide G 2014: Unit Type 1 bedroom 2 bedroom 3 bedroom 4 bedroom

min

DHW Strorage with stratification (20% shall be added to total storage) 109 165 221 277

DHW Storage [Litres] 136 206 276 346

Dia Height Utilization Capacity

Cylider Size: 1.7 4 90.00% 8,167

Dia Height Utilization Capacity

Cylider Size: 1.3 2.6 90.00% 3,104

m m litres

m m litres