1200 kV system

September 7, 2017 | Author: rspwr | Category: N/A
Share Embed Donate


Short Description

Download 1200 kV system...

Description

DESIGN OF 1200 KV TRANSMISSION LINE R. N. Nayak, Executive Director M. Krishnakumar, General Manager Anish Anand, Chief Design Engineer

Power Grid Corporation of India Ltd. Gurgaon, INDIA

Indian Power System – 2025 & Beyond

KISHENPUR

MOGA

TEHRI

MEERUT

MUNDKA

BAREILLY

AGRA LUCKNOW

JAIPUR

SILIGURI BALIA

GWALIOR KOTA

PURNEA GAYA

FATEHPUR SASARAM SASAN BINA

DEHGAM

NKSTPP

SATNA

INDORE ITARSI

RANCHI SEONI

SIPAT

WARDHA

DHULE

IB VALLEY MUMBAI JEYPORE PUNE SOLAPUR

HYDERABAD

VIJAYAWADA

LEGEND

RAICHUR

1200KV UHVAC LINES 765KV UHVAC LINES 800kV HVDC BIPOLE BANGALORE MADRAS

NER POOLING POINT

• Peak Demand : 4,50,000 MW (3 times of 2012) • Installed Capacity : 6,00,000MW (3 times of 2012) • Power from ER/NER to NR/WR/SR : 80,000-90,000 MW (4 times of 2012) • Inter Regional Capacity : 1,40,000MW (3.5 times of 2012) • Next Level Transmission Network i.e. 1200kV UHVAC Network • Main Transmission Level : 1200kV UHVAC/800kV HVDC Network • 765kV EHVAC and 500kV HVDC System would be used as support Tr. Network • 400kV AC System would be used as Sub-transmission Network

DESIGN & OPTIMIZATION OF 1200 KV TRANSMISSION LINE

TYPICAL TRANSMISSION LINE DESIGN OPTIMIZATION FLOW CHART Tower Design Study

Bundle Conductor studies Review of Existing systems & Practices

Selection of clearances

Tower Configuration Analysis

Line Cost & Optimization

Insulator string design Tower Fdn. Design/Study

Economic Evaluation Of Line

Results

1200 KV TRANSMISSION LINE DESIGN - STUDIES UNDERTAKEN PRELIMINARY STUDIES UNDERTAKEN ¾ Clearances & Tower Configuration Analysis ¾ Thermal Rating & Surge Impedance Loading ¾ Conductor Surface Gradients & Corona Onset-gradients ¾ Insulation / insulator string design ¾ Electric Fields at ground ¾ Interference Performance ƒ Radio Interference ƒ Audible Noise

1200 KV TRANSMISSION LINE DESIGN - STUDIES UNDERTAKEN CONDUCTOR-BUNDLES ANALYSED ¾ Hexagonal ACSR Lapwing (Conductor Dia. 38.16 mm)

¾ Octagonal ACSR Moose (Conductor Dia. 31.77 mm)

¾ Octagonal ACSR Bersimis (Conductor Dia. 35.05 mm)

¾ Octagonal ACSR Lapwing (Conductor Dia. 38.16 mm)

1200 KV TRANSMISSION LINE DESIGN - CONFIGURATION FEATURES

¾ Basic Configuration : I – V – I ; Delta ¾ Air-gap / Live – metal Clearance Requirements ƒ Power Frequency Clearance : 2.3 m (under Maxm. Swing – 55 deg)

ƒ Switching Surge Clearance : 10 m (under stationary condition / Swing – 10 deg)

1200 KV TRANSMISSION LINE DESIGN - CONFIGURATION FEATURES ¾ Insulation Requirements ƒ Total Required Creepage Distance : 21600 mm (18 mm/kV) ƒ Insulation / String length : 10 / 11 m ƒ Required Number of Insulators 320 kN : 55 Nos. (195 mm spacing, 390/400 mm creepage) 420 kN : 50 Nos. (205 mm spacing, 525 mm creepage)

1200 KV TRANSMISSION LINE DESIGN - CONFIGURATION FEATURES ¾ Phase to Phase Spacing ƒ Minimum Electrical Requirement : 12 m ƒ Phase to Phase spacing based on Live-metal clearances : 27.5 - 30 m

¾ Ground Clearance ƒ Minimum Ground Clearance as per IE Rules : 16 m ƒ Ground Clearance proposed : 23 m (based on 10 kV/m electric field limit)

1200 kV Tower Configuration Configuration Considered: I V I – Delta 25 m 20 m 4° 16 m

10 m

55° 77m

10°

15 m

12 m

2.3 m

11 m

15 m

15 m Sag

GCL = 23 m

1200 KV TRANSMISSION LINE DESIGN - CONFIGURATION FEATURES ¾ Right of Way Requirements ƒ Minimum Horizontal Clearance as per IE Rules : 13 m ƒ Right of way Requirement : 100 m (based on 13 m clearance & maximum Swing – 55 deg)

ƒ Right of way Requirement based on Electric Field Limitation : 110 m (considering 2 kV/m electric field limit)

Distance from Centre Line (m ) 1200 kV TL

765 kV TL

60

50

40

30

20

10

0

-1 0

-3 0 -2 0

-5 0 -4 0

12 10 8 6 4 2 0 -6 0

Electric Field at 1.8m above ground (kV/m)

Lateral Distribution of Electric Field for 1200 kV & 765 kV Transmission Line

1200 kV Transmission Line Right of Way 25 m 20 m 4° 16 m

10 m

55° 77m

10°

15 m

12 m

2.3 m

55°

11 m

Minm. Clearance

15 m Sag

15 m

13 m GCL = 23 m

50 m

Right of Way = 100 m

35 m

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES Conductor Surface Gradients & Corona Onset Gradients for 1200 kV Line Alt

Conductor-bundle

Conductor Surface Corona On-set Gradient Gradient (kV/cm) (kV/cm) Mean

Max

Fair Weather

Foul Weather

1

Hexa Lapwing

14.76

17.84

20.73

14.64

2

Octa Moose

14.34

17.01

21.10

14.89

3

Octa Bersimis

13.02

15.70

20.89

14.75

4

Octa Lapwing

12.00

14.67

20.73

14.64

Quad Bersimis (765 kV)-Horizontal

15.77

18.33

20.89

14.75

Quad Bersimis (765 kV)- Delta

14.9

17.3

20.89

14.75

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES Radio Interference for 1200 kV Line Alt

Conductor-bundle

Radio Interference (dB/1uV/m) Max.

At 50m ROW

1

Hexa Lapwing

45.8

38.4

2

Octa Moose

39.1

31.6

3

Octa Bersimis

36.5

29.1

4

Octa Lapwing

34.8

27.4

Quad Bersimis (765 kV)-Horizontal

50.9

38.5 (at 42.5m)

Quad Bersimis (765 kV)- Delta

46.8

40.4 (at 32m)

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES Audible Noise for 1200 kV Line Alt

Audible Noise (dBA) Audible Noise (dBA) –L5 level –L50 level

Conductor-bundle

Max

At 50m ROW

Max

At 50m ROW

1

Hexa Lapwing

64.6

62.0

62.5

59.8

2

Octa Moose

61.3

58.6

57.6

54.9

3

Octa Bersimis

60.3

57.6

55.9

53.2

4

Octa Lapwing

59.4

56.7

54.4

51.6

60.5

56.9 (at 42.5m)

57.8

54.2 (at 42.5m)

59.1

56.9 (at 32m)

55.9

53.7 (at 32m)

Quad Bersimis Horizontal

(765

kV)-

Quad Bersimis (765 kV)- Delta

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES Lateral Distribution of Radio Interference for 1200 kV Transmission Line

Acceptable Radio Interference levels : 40-45 dB/1uV/m

35

Octa Bersimis

30

Octa Moose

25

60

45

30

15

0

-1 5

-3 0

20 -6 0

Acceptable Audible Noise levels : 55 – 58 dBA

40

-4 5

Radio Interference (dB/1uV/m)

45

Distance from Centre Line (m )

Lateral Distribution of Audible Noise for 1200 kV Transmission Line

ACCEPTABLE ALTERNATIVE OPTIONS

58 56

Octa Bersimis

54

Octa Moose

¾ Octagonal ACSR Moose

52

¾ Octagonal ACSR Bersimis Distance from Centre Line (m )

60

45

30

15

0

-1 5

-3 0

-4 5

50 -6 0

Audible Noise - L50 Wet (dBA)

60

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES Conductor Current Carrying Capacity & Thermal rating of 1200 kV Line Alt Conductor-bundle

Maxm. Conductor Temp.

Conductor Current Thermal Rating of kV Line carrying capacity 1200 (Amp) – Ambient (MVA) Temp. 45 deg C 75 deg C

85 deg C

75 deg C

85 deg C

1

Octa Moose

614

787

10209

13086

2

Octa Bersimis

710

917

11806

15248

Thermal Rating of 1200 kV Line : More than 10000 MVA Surge Impedance Loading of 1200 kV Line : Around 6000 MW

1200 KV TRANSMISSION LINE DESIGN TECHNICAL PARTICULARS OF 1200 kV AC LINE ELECTRICAL SYSTEM DATA Nominal System Voltage

1200 kV

Maximum Voltage

1250 kV

Switching Impulse Withstand Voltage (Wet)

2100 kV

Lightning Impulse Withstand Voltage

> 3000 kVp

CONDUCTOR-BUNDLE Conductor-bundle

Octagonal ACSR Bersimis / Moose 457-600 mm spacing

ELECTRICAL CLEARANCES Power Frequency live-metal clearance

2.3 m (55 deg swing)

Switching surge clearance (1.75 pu)

10 m (Stationary/10 deg swing)

Phase to Phase Spacing Ground Clearance

27.5-30 m 23 m (10 kV/m elect field limit)

INSULATOR STRINGS For Suspension Towers (I – V – I)

I- Double Suspension, 300/320 kN (2x55), V – Single V, 420 kN (2x50)

For Tension Towers

Quad Tension, 320 kN (4x55)

1200 KV TRANSMISSION LINE DESIGN ¾ Preliminary Line Design Considerations ƒ Wind Zone – 4 (47 m/sec basic wind speed) ƒ Reliability Level – 2 (150 yr. return period loads) ƒ Ruling Span – 400 m ƒ Maxm. Wind Span – 400 m ; Maxm. Weight Span – 600 m

¾ Estimated Tower Weight ƒ Standard Suspension Tower : I-V-I Octa Bersimis : 53 MT Octa Moose : 50 MT ( Comparative 765 kV Suspension Tower Wt. : 23 MT)

¾ Estimated Transmission Line Cost : Rs. 30 – 33 million/km

1200 KV TRANSMISSION LINE DESIGN 1200 kV vis-à-vis 765 kV 1200 kV Tower Size : Approx. 30% more than 765 kV

1200 KV TRANSMISSION LINE DESIGN 1200 kV vis-à-vis 765 kV 1200 kV vis-à-vis 765 kV Power Flow Capacity - Thermal Rating

Thermal Rating (MVA)

14000

POWER FLOW CAPACITY

12000

12000 10000 8000

765 kV Line

6000

1200 kV Line

4000

3800

Thermal Rating : 3 Times

2000 0 1

SIL (MW)

1200 kV vis-à-vis 765 kV Power Flow - Surge Impedance Loading 7000 6000 5000 4000 3000 2000 1000 0

6000 765 kV Line 1200 kV Line

2000

1

SIL : 3 Times

1200 KV TRANSMISSION LINE DESIGN 1200 kV vis-à-vis 765 kV 1200 kV vis-à-vis 765 kV Right of Way Requirement 120

RIGHT OF WAY

100

ROW (m)

100 80

64

765 kV Line

60

1200 kV Line

40 20

Right of Way Requirement : Approx. 55% more

0 1

ROW Utilization

Power Flow- SIL per unit ROW (MW/m)

1200 kV vis-à-vis 765 kV Right of Way Utilization 80

60

60 40

765 kV Line 30

1200 kV Line

20 0 1

Power Flow per Unit ROW : 2 Times

1200 KV TRANSMISSION LINE DESIGN 1200 kV vis-à-vis 765 kV LINE COST

Estimated Line Cost (Rs million/km)

1200 kV vis-à-vis 765 kV Capital Line Cost 50 40

33

30 20

765 kV Line

Capital Line Cost : 2 – 2.2 Times

1200 kV Line

15

10 0 1

COST EFFECTIVENESS

Line Cost per unit Power Flow - SIL (Rs/km-MW)

1200 kV vis-à-vis 765 kV Cost Effectiveness 9000 8000

7500 765 kV Line

7000 5500

6000 5000 4000 1

1200 kV Line

Line Cost per Unit Power Flow : Approx. 70 %

1200 KV TRANSMISSION LINE DESIGN - Detailed Studies ¾ Detailed Studies to be undertaken in respect of following ƒ Reliability considerations ƒ Air-Gap Optimization ƒ Insulation Co-ordination ƒ Switching Surge Control ƒ Capital cost & line optimization ƒ Right of Way reduction measures ƒ Alternate insulation systems ƒ Low noise conductor ƒ Asymmetrical conductor-bundle ƒ Expandable (variable) conductor-bundle

THANK YOU

EVOLUTION OF INDIAN TRANSMISSION GRID

TRANSMISSION GRID AT THE TIME OF INDEPENDENCE DELHI

KOLKATA

• Installed Capacity : 1349 MW • Local Grid Feeding to Local Load

MUMBAI

• No State/ Regional Grid CHENNAI

TRANSMISSION GRID DEVELOPMENT OVER THE YEARS • 1960s - State Grids • 1970s - Regional Grids • 2000 - Limited Inter- Regional Capacity

TRANSMISSION LINE DEVELOPMENTS • Late 1970s - First 400 kV Lines • 1980s onward – Standardized 400 kV Lines (twin bundle) • Late 1980s-1990 – First 500 kV HVDC Line • Late 1990s-2000 – First 765 kV Lines • Triple Bundle 400 kV Lines

400 kV Twin Bundle Transmission Lines

+/- 500 kV HVDC Transmission Line

400 kV Triple Bundle Transmission Line

765 kV S/C Transmission Line (Horizontal Configuration)

POWER MAP OF INDIA

NATIONAL GRID BY 2007 • Peak Demand : 1,00,000 MW • Installed Capacity : 1,40,000MW • Inter Regional Capacity : 18,400MW • Power Mainly Flows on 400kV Network • 765 kV UHVAC Line in operation

TRANSMISSION LINE DEVELOPMENTS • 765 kV Delta Configuration Lines • 400 kV Quad Bundle Lines • 400 kV Multi-circuit Lines • 400 kV Pole Structures

400 kV D/C Pole Structure 765 kV S/C Transmission Line (Delta Configuration)

400 kV Multi-circuit Transmission Line

INDIAN TRANSMISSION GRID – FUTURE DEVELOPMENTS

POWER MAP OF INDIA

NATIONAL GRID BY 2012 • Peak Demand : 1,57,000 MW (1.5 times of 2007) • Installed Capacity : 2,12,000MW (1.5 times of 2007) • Power from ER/NER to NR/WR/SR : 20,000-25,000 MW (4 times of 2007) • Inter Regional Capacity : More than 40,000MW (2.5 times of 2012) • Strong 765kV EHVAC Network with backup 400kV Network

TRANSMISSION LINE DEVELOPMENTS • +/- 800 kV 6000 MW HVDC

+/- 800 KV HVDC TRANSMISSION LINE TOWER

1200 KV TRANSMISSION LINE DESIGN - Calculations ¾ Power Frequency Clearance ƒ Minm. Air-gap , L = Sqrt(2/3)*1200*1.1/(500*0.95) = 2.3 m Basis : 500 kV/m – Discharge gradient of air gap 1.1 – factor for decrease in strength of total v/s single gap 0.95 – air density correction factor (assumed)

¾ Switching Surge Clearance ƒ CFO = 1.32*1.75*sqrt(2/3)*1200 = 2263 kV Basis : Switching surge S2 = 1.75pu, σs = 10% , σ = 5% Switching surge flashover rate : 1 per 1000 R = CFO/S2 = 1.32 (From EPRI)

ƒ Air-gap , D = 10 m Basis : EPRI Formula CFO = 1.2 * 3400 / (1 + 8/D)

1200 KV TRANSMISSION LINE DESIGN - Calculations ¾ Minimum Ground Clearance as per IE Rules ƒ Ground Clearance = 5.2 + 0.3 * (1200 – 33)/33 = 16 m

¾ Minimum Horizontal Clearance as per IE Rules ƒ Ground Clearance = 2.0 + 0.3 * (1200 – 33)/33 = 13 m

¾ Corona On-set Gradients ƒ Ec = 21 * m *б * (1 + 0.3 /sqrt(б* r)) kV/cm Basis : б = Air density = 0.95 r = conductor radius in cm m = surface roughness factor =0.85 for fair weather = 0.6 for foul weather

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES CONDUCTOR PARAMETERS Parameters

ACSR Moose

ACSR Bersimis

ACSR Lapwing

Stranding

54/3.53mm Al +7/3.53mm St

42/4.57mm Al +7/2.54mm St

45/4.77mm Al +7/3.18mm St

Conductor Dia (mm)

31.77

35.05

38.16

Weight (kg/m)

2.004

2.181

2.667

161

154

188

0.05552

0.0418

0.036

UTS (kN) Rdc @ 20 deg C (ohm/km)

TRANSMISSION LINE DEVELOPMENTS TECHNICAL PARTICULARS OF +/- 800 kV HVDC LINE ELECTRICAL SYSTEM DATA System Voltage

+/- 800 kV DC

Maximum Voltage

820 kV

Switching Impulse Withstand Voltage (Wet)

1850 kV

Lightning Impulse Withstand Voltage

2250 kVpeak

Minm. Corona Extinction Voltage (Dry)

880 kV

RIV at 1 MHz for 22 kV/cm conductor surface gradient (under dry condition)

1000 uV

CONDUCTOR-BUNDLE Conductor-bundle

Hexa ACSR Lapwing 457 mm spacing ELECTRICAL CLEARANCES

Live-metal clearance

6.5 m

Pole to Pole Spacing

25-28 m

Ground Clearance

18-20 m (15 kV/m charge free elect field limit)

INSULATOR STRINGS For Suspension Towers (V – V)

Single V Suspension, 400/420 kN (2x61)

For Tension Towers

Quad Tension, 300/320 kN (4x61)

TRANSMISSION LINE DEVELOPMENTS TECHNICAL PARTICULARS OF 765 KV S/C LINE ELECTRICAL SYSTEM DATA Nominal Voltage

765 kV

Maximum System Voltage

800 kV

Power Frequency Withstand Voltage (Wet)

830 kVrms

Switching Impulse Withstand Voltage (Wet)

1550 kVrms

Lightning Impulse Withstand Voltage

2400 kVpeak

Minm. Corona Extinction Voltage (Dry) RIV at 1 MHz for 510 kVrms phase to earth

510 kVrms 1000 uV

CONDUCTOR-BUNDLE Conductor-bundle

Quad ACSR Bersimis 457 mm spacing

TRANSMISSION LINE DEVELOPMENTS TECHNICAL PARTICULARS OF 765 KV S/C LINE ELECTRICAL CLEARANCES Power Frequency live-metal clearance

1.3 m (55 deg swing)

Switching surge clearance (1.75 pu)

4.4 m (25 deg swing)

Air-gap/stationary live-metal clearance Phase to Phase Spacing

5.1 / 5.6 m 15 m 15 m (10 kV/m elect field limit)

Ground Clearance INSULATOR STRINGS For Suspension Towers (I – V – I)

I- Double Suspension, 120 kN (2x40) V – Single V, 210 kN (2x35)

For Tension Towers

Quad Tension, 210 kN (4x35)

TRANSMISSION LINE DEVELOPMENTS TECHNICAL PARTICULARS OF +/- 500 kV HVDC LINES ELECTRICAL SYSTEM DATA System Voltage

+/- 500 kV DC

Maximum Voltage

525 kV

Power Frequency Withstand Voltage (Wet)

700 kV

Switching Impulse Withstand Voltage (Wet)

1000 kV

Lightning Impulse Withstand Voltage

1800 kVpeak

Minm. Corona Extinction Voltage (Dry)

550 kV

RIV at 1 MHz for 22 kV/cm conductor surface gradient (under dry condition)

1000 uV

CONDUCTOR-BUNDLE Conductor-bundle

Quad ACSR Bersimis Quad ACSR Lapwing 457 mm spacing

TRANSMISSION LINE DEVELOPMENTS TECHNICAL PARTICULARS OF +/- 500 KV HVDC LINES ELECTRICAL CLEARANCES Live-metal clearance

3.75 m

Pole to Pole Spacing

12.5 – 13.5 m 12.5 m (10 kV/m charge free elect field limit)

Ground Clearance

INSULATOR STRINGS For Suspension Towers (V – V)

Single V Suspension, 160/210 kN (2x38/41)

For Tension Towers

Quad Tension, 160/210 kN (4x38/41)

1200 KV TRANSMISSION LINE DESIGN - Variations in TL Parameters w.r.t. Sub-conductor Spacing

Inductive/Capacitive Reactance

1200 kV Transmission Line Parameters - Variation w.r.t. Sub-conductor Spacing 0.3 0.28 0.26 0.24 0.22 0.2 0.18

XL (Ohms/km) XC (Ohms-km)

300

450

600

750

900

Sub-conductor Spacing (m m )

300

8000

275

7000

250

6000

225

5000

200

4000 300

450

600

750

900

Sub-conductor Spacing (mm)

Surge Impedance Loading (MW)

Surge Impedance (Ohms)

1200 kV Transmission Line Parameters - Variations w.r.t. Sub-conductor Spacing

SI SIL

1200 KV TRANSMISSION LINE DESIGN - CONDUCTOR-BUNDLE STUDIES CONDUCTOR – BUNDLES ADOPTED IN OTHER COUNTRIES FOR 1000 - 1200 KV LINES System Voltage

Conductor-Bundle Adopted

ITALY

1000 kV

Octagonal 31.5 mm ACSR

JAPAN

1000 kV

Octagonal 36.4 / 34.2 mm ACSR

USA (BPA)

1200 kV

Octagonal 42.4 mm

USSR

1200 kV

Octagonal 24.1 mm

Country

TRANSMISSION LINE DEVELOPMENTS Comparative Line Cost Cost as per FR

Quad ACSR Bersimis

Octa ACSR Bersimis

765 kV S/C line

per km cost (765 kV)

per km costestimated

per km costestimated

(Rs lacs)

(Rs lacs/km)

(Rs lacs/km)

(Rs lacs/km)

Factor

Octa ACSR Moose

Factor

325 kms Tower Steel

15833

48.72

112.26

2.30

106.88

2.19

Conductor

15007

46.18

92.35

2.00

84.70

1.83

Earthwire

194

0.60

0.60

1.00

0.60

1.00

Insulator

2390

7.35

23.11

3.14

23.11

3.14

Hardware Fittings

1270

3.91

7.82

2.00

7.82

2.00

Conductor & E/W Acc

500

1.54

3.08

2.00

3.08

2.00

Sub-total Supply

35194

108.29

239.21

226.18

F&I & Taxes

4526

13.93

30.76

29.09

TRANSMISSION LINE DEVELOPMENTS Comparative Line Cost Cost as per FR

Quad ACSR Bersimis

Octa ACSR Bersimis

765 kV S/C line

per km cost (765 kV)

per km costestimated

per km costestimated

(Rs lacs)

(Rs lacs/km)

(Rs lacs/km)

(Rs lacs/km)

Factor

Octa ACSR Moose

Factor

325 kms Erection

1564

4.81

11.09

2.30

10.56

2.19

Stringing

1071

3.30

6.59

2.00

6.59

2.00

Civil works

5321

16.37

37.73

2.30

35.92

2.19

River X-ing

473

1.46

3.35

2.30

3.19

2.19

Total Cost

48149

148.15

328.74

2.22

311.53

2.10

1200 KV TRANSMISSION LINE DESIGN 1200 KV VIS-A-VIS 765 KV 1200 KV S/C LINE

765 KV S/C LINE COMPARISON

POWER FLOW CAPACITY – THERMAL RATING Approx. 12000 MVA

Approx. 3800 MVA

Approx. 3 times

POWER FLOW – SURGE IMPEDANCE LOADING Approx. 6000 MVA

Approx. 2000 MVA

Approx. 3 times

RIGHT OF WAY (ROW) REQUIREMENT 100 m

64 m

Approx. 55 % more

CAPITAL LINE COST Approx. Rs. 30-33 million per km

Approx. Rs. 15 million per km

Approx. 2 – 2.2 times

1200 KV TRANSMISSION LINE DESIGN 1200 KV VIS-A-VIS 765 KV 1200 KV S/C LINE

765 KV S/C LINE

COMPARISON

RIGHT OF WAY UTILIZATION Normal Power Flow per Unit ROW Approx. 60 MVA Approx. 30 MVA Approx. 2 times per m per m COST EFFECTIVENESS Line Cost per Unit Power Flow Approx. Rs. 50005500 per km per MVA

Approx. Rs. 7500 per km per MVA

Approx. 70 %

GROWTH OF POWERGRID 60,000

Circuit Kms & Transformation Capacity

50,000

44836

46245

4000

55100 54400

46461 47757

3000

40289

40,000

MVA

CKMs

30,000

27244 22228

35119

Turnover Net Profit

Turnover & Profit

3500

49459 50745

2805

Rs. in Crore

2000

28820

22748

2831

2533

2500

34288

3554

1770

1500

20,000

983

1000

12,201

10,000

643

748

786

1998-99 2002-03

2003-04

2004-05

634

500

444

275

236

1009

0

0 1992-93

1995-96

1998-99

2001-02

2002-03

2003-04

2004-05

1992-93

2005-06

1995-96

2005-06

Growth achieved through Internal resources & Borrowings

Growth in last 13 years ¾Transformation Capacity ¾Circuit Kilometer ¾Asset Growth POWERGRID ¾Turnover ¾Profit ¾Manpower

19876

21930

24888

13877

15000 8851

10000 3521

5492

No. of Employees ----->

Asset Base

Rs. in Crore

20000

5000

345 % 148 % 606 % 460 % 328 % 15 %

7200

30000 25000

-

Manpower

7000

6923 6811

6800

7103 6828

6881

6624

6600 6400 6200

6167

6000 5800

0 1992- 1995- 1998- 2001- 2002- 2004- 200593 96 99 02 03 05 06

5600

Transferred Manpower

1995-96 1998-99 2001-02 2003-04 2004-05 2005-06 Year ---->

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF