104534837 Training Manual TM2500

November 20, 2016 | Author: lunadogger | Category: N/A
Share Embed Donate


Short Description

TM2500+ training manual...

Description

*(3RZHU :DWHU

TM2500 Package Familiarization Ecopetrol

2014

g

All rights reserved by the General Electric Company. No copies permitted without the prior written consent of the General Electric Company. The text and the classroom instruction offered with it are designed to acquaint students with generally accepted good practice for the operation or maintenance of equipment and/or systems. They do not purport to be complete nor are they intended to be specific for the products of any manufacturer, including those of the General Electric Company; and the Company will not accept any liability whatsoever for the work undertaken on the basis of the text or classroom instruction. The manufacturer’s operating and maintenance specifications are the only reliable guide in any specific instance; and where they are not complete, the manufacturer should be consulted. The materials contained in this document are intended for educational purposes only. This document does not establish specifications, operating procedures or maintenance methods for any of the products referenced. Always refer to the official written materials (labeling) provided with the product for specifications, operating procedures and maintenance requirements. Proprietary Training Material Property of GE. Use of these materials is limited to agents and GE employees, or other parties expressly licensed by GE. Unlicensed use is strictly prohibited.

© 2014 General Electric Company

GE Power & Water

TM2500 Package Familiarization Ecopetrol 2014 Tab 1

Introduction

F-000-00-00-000-00

Tab 2

Gas Turbine Basics

F-025-10-10-000-00

Tab 3

Construction and Operation

F-025-10-10-101-00

Tab 4

Turbine Lube Oil System

F-025-10-20-103-00

Tab 5

Variable Geometry System

F-025-10-10-202-00

Tab 6

Hydraulic Start System

F-025-10-20-050-00

Tab 7

Dual Fuel System

F-025-10-20-306-00

Tab 8

Ventilation and Combustion Air System

F-025-10-20-401-00

Tab 9

Water Wash System

F-025-10-20-501-00

Tab 10

Vibration Monitoring System

F-025-10-20-701-00

Tab 11

Fire Protection System

F-025-10-20-801-00

Tab 12

Generator Construction (60 Hz)

F-025-10-30-100-00

Tab 13

Basic Electricity

F-000-00-60-001-00

Tab 14

Generator Lube Oil System (60 Hz)

F-025-10-30-300-00

Tab 15

Control System

F-025-10-40-101-00

Tab 16

Sequences

F-025-10-50-004-00

Tab 17

Appendix & abbreviations

F-000-00-60-002-00

TM2500 Package Familiarization Ecopetrol

1

GE Power & Water Tab 18 Tab A

Tab B

Tab C

Tab D

Reference Drawings Flow and Instrument Drawings Symbols and Abbreviations Hydraulic Start System Ventilation and Combustion Air System Turbine Lube Oil System Generator Lube Oil System (60 Hz) Fuel System Water Wash System Aux Instrumentation Fire Protection System

7245381-751231 7245381-751232 7245381-751239 7245381-751244 7245381-751248 7245381-751260 7245381-751262 7245381-751272 F&ID- MC-1

Electrical Drawings Electrical Symbols and Abbreviations Turbine Control Panel Plan and Elevation One Line Diagram Fuel Control Layout Control system Worksheet Cause and Effect Matrix

7245381-753005 7245381-753014 7245381-753031 752145 7245381-753146 7245381-752149

General Arrangement Drawings Main Unit Plot Plan Auxiliary Skid Fire Protection System

7245381-751200 7245381-751202 7245381-751218 GA-MC-1

LM2500 Airflow LM2500+ Airflow

LM2500

TM2500 Package Familiarization Ecopetrol

2

Tab 1

gGE Energy

F-000-00-00-000-01

GE Aero Package Training Course Introduction

BOC/FAM Course Introduction

Slide 1

gGE Energy

GE Aero Package Training Course Introduction

This document is intended for training use only. It is not intended to cover all possible variations in equipment or to provide for specific problems that may arise. Technical drawings and descriptions herein are intended to illustrate conceptual examples and do not necessarily represent as-supplied system details. System users are advised to refer to drawings of current release when conducting troubleshooting, maintenance procedures, or other activities requiring system information. GE Aero Energy Products advises that all plant personnel read this training manual and the Operation & Maintenance Manual to become familiar with the generator package, auxiliary equipment and operation. This manual is not a replacement for experience and judgment. The final responsibility for proper, safe operation of the generator package lies with the Owners and Operators. Operation and performance of auxiliary equipment and controls not furnished by GE is the sole responsibility of the Owners and Operators. Reproduction of this guide in whole or in part without written permission is prohibited.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 2

gGE Energy

GE Aero Package Training Course Introduction

Course Objectives This training course is designed to provide system operators with : ƒUnderstanding of basic Gas Turbine and Generator operation ƒUnderstanding of how each of the sub systems operates, individually and as part of the total package ƒAbility to initiate and maintain normal system operation ƒAbility to recognize system alarm and fault information and take appropriate action ƒUnderstanding of system documentation ƒKnowledge of serviceable components and maintenance required for normal operation This course should be considered a mandatory prerequisite for more advanced training in package mechanical maintenance or control system maintenance and troubleshooting.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 3

gGE Energy

GE Aero Package Training Course Introduction

OVERVIEW OF GE ENERGY PRODUCTS GE Energy is a leading supplier of diesel and aero-derivative gas turbine packages for industrial and marine applications, with many units operating throughout the world. GE Energy takes single source responsibility for the total equipment package and provides field service for the equipment once it has been installed. All of GE Energy’s skill and field experience is built into each unit. Customers’ needs are met with standardized designs, which have been proven time and time again in tropical heat, desert sand and arctic cold. For a customer with special requirements, GE Energy adds features from a list of pre-engineered options. GE Energy provides job-site supervision and operator training, offers total plant operation and maintenance when desired, and backs up each unit with a multi-million dollar inventory of turbine parts, as well as a service department with trained personnel ready to perform field service anywhere in the world — 24 hours a day, 365 days a year. Meeting customer’s requirements for quality, dependability and outstanding service is the commitment of GE Energy.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 4

gGE Energy

GE Aero Package Training Course Introduction SAFETY CONSIDERATIONS

The following are general safety precautions that are not related to any specific procedures and do not appear elsewhere in this manual. Personnel must understand and apply these precautions during all phases of operation and maintenance. Health Hazards

Use all cleaning solvents, fuels, oil adhesives, epoxies, and catalysts in a well-ventilated area. Avoid frequent and prolonged inhalation of fumes. Concentrations of fumes of many cleaners, adhesives, and esters are toxic and cause serious adverse health effects, and possible death, if inhaled frequently. Wear protective gloves and wash thoroughly with soap and water as soon as possible after exposure to such materials. Take special precautions to prevent materials from entering the eyes. If exposed, rinse the eyes in an eyebath fountain immediately and report to a physician. Avoid spilling solvents on the skid. Review the hazard information on the appropriate Material Safety Data Sheet and follow all applicable personal protection requirements. Environmental Hazards The disposal of many cleaning solvents, fuels, oils, adhesives, epoxies, and catalysts is regulated and, if mismanaged, could cause environmental damage. Review Material Safety Data Sheets, product bulletin information, and applicable local, state and federal disposal requirements for proper waste management practices.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 5

gGE Energy

GE Aero Package Training Course Introduction

Fire Hazards Keep all cleaning solvents, oils, esters and adhesives away from exposed-element electric heaters, sparks or flame. Do not smoke when using flammable materials, in the vicinity of flammable materials, or in areas where flammable materials are stored. Provide adequate ventilation to disperse concentrations of potentially explosive fumes or vapors. Provide approved containers for bulk storage of flammable materials, and approved dispensers in the working areas. Keep all containers tightly closed when not in use. Electrical Hazards Use extreme care when working with electricity. Electricity can cause shock, burns or death. Electrical power must be off before connecting or disconnecting electrical connectors. Lethal output voltages are generated by the ignition exciter. Do not energize the exciter unless the output connection is properly isolated. Be sure all leads are connected and the plug is installed. All personnel should be cleared to at least 5 feet before firing the exciter. Compressed Air Hazards Air pressure used in work areas for cleaning or drying operations shall be regulated to 29 psi or less. Use approved personal protective equipment (goggles or face shield) to prevent injury to the eyes. Do not direct the jet of compressed air at yourself or other personnel so that refuse is blown onto adjacent work stations. If additional air pressure is required to dislodge foreign materials from parts, ensure that approved personal protective equipment is worn, and move to an isolated area. Be sure that the increased air pressure is not detrimental or damaging to the parts before applying high-pressure jets of air.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 6

gGE Energy

GE Aero Package Training Course Introduction

Procedural Hazards Observe all specified and logical safety practices when assembling or disassembling the engine. Wear safety glasses or other appropriate eye protection at all times. Do not allow safety wire or wire clippings to fly from the cutter when removing or installing wire. Do not use fingers as guides when installing parts or checking alignment of holes. Use only correct tools and fixtures. Avoid “shortcuts,” such as using fewer-than-recommended attaching bolts or inferior-grade bolts. Heed all warnings in this manual and in all vendor manuals, to avoid injury to personnel or damage to gas turbine parts.

Tooling Hazards Improperly maintained tools and support equipment can be dangerous to personnel, and can damage gas turbine parts. Observe recommended inspection schedules to avoid unanticipated failures. Use tooling only for its designed purpose and avoid abuse. Be constantly alert for damaged equipment, and initiate appropriate action for approved repair immediately.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 7

gGE Energy

GE Aero Package Training Course Introduction

Gas Turbine Operational Hazards The outside surfaces of the engine are not insulated; therefore, adequate precautions shall be taken to prevent operating personnel from inadvertently coming into contact with these hot surfaces. The gas turbine is a source of considerable noise. It is necessary for personnel working on the gas turbine or in its vicinity to wear proper ear protection equipment when it is operating. The gas turbine is a high-speed machine. In case of component failure, the skid housing would contain compressor and turbine blade failures, but might not contain major compressor or turbine disk failures. Operating personnel shall not be permanently stationed in or near the plane of the rotating parts. Low-pressure, high-velocity airflow created by the compressor can draw objects or personnel into the engine. Although an inlet screen is used, personnel should not stand in front of the inlet while the engine is operating. When entering the gas turbine enclosure, the following requirements must be met: •The gas turbine will be shut down or limited to core idle power. •The fire extinguishing system will be made inactive. •The enclosure door shall be kept open. If the gas turbine is operating, an observer shall be stationed at the enclosure door, and confined space entry procedures will be followed. •Avoid contact with hot parts, and wear thermally insulated gloves, as necessary. •Hearing protection (double) will be worn if the gas turbine is operating. •Do not remain in the plane of rotation of the starter when motoring the gas turbine. When performing maintenance on electrical components, turn off electrical power to those components, except when power is required to take voltage measurements. Lock out all controls and switches, if possible; otherwise, tag electrical switches “Out of Service” to prevent inadvertent activation. Tag the engine operating controls “Do Not Operate” to prevent the unit from being started during a shutdown condition. F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 8

gGE Energy

GE Aero Package Training Course Introduction

Cleanliness and FOD/DOD FOD/DOD (foreign object damage/domestic object damage) is the single major cause of premature gas turbine failure. Prevention is the only practical means of protecting against FOD, and adherence to the following guidelines cannot be over-emphasized. •Empty pockets of all lose objects.

•Keep maintenance area clean and organized. •Keep FOD containers in the work area to receive bits of safety wire, used gaskets, Orings and other similar types of debris. USE THEM. •Do not use the gas turbine as a shelf to hold parts and tools during maintenance. •Install protective covers and caps on all exposed openings during maintenance. •Remove protective caps and covers only when required to install a part or make a connection. •After protective caps and covers are removed, inspect all openings and cavities for foreign objects and cleanliness. •After maintenance, thoroughly clean and inspect work area. Account for all tools, parts, and materials used during maintenance.

F-000-00-00-000-01

BOC/FAM Course Introduction

Slide 9

Tab 2

gGE Energy

TM2500+ Gen VI Package Familiarization

GAS TURBINE BASICS

F-000-10-10-000-00

Turbine Basics

Slide 1

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 2

gGE Energy

TM2500+ Gen VI Package Familiarization

OVERVIEW The major components of the engine are a compressor section, combustion section, and a turbine. The turbine is mechanically coupled and drives the compressor by a drive shaft. The compressor, combustor, and turbine are called the core of the engine, since all gas turbines have these components. The core is also referred to as the gas generator (GG) since the output of the core is hot exhaust gas. The gas is passed through an exhaust duct to atmosphere. On some types of applications, the exhaust gas is used to drive an additional turbine called the power turbine which is connected to a piece of driven equipment (i.e. generators, pumps, process compressors, etc). Because of their high power output and high thermal efficiency, gas turbine engines are also used in a wide variety of applications not related to the aircraft industry. Connecting the main shaft (or power turbine) of the engine to an electromagnet rotor will generate electrical power. Gas turbines can also be used to power ships, trucks and military tanks. In these applications, the main shaft is connected to a gear box.

F-000-10-10-000-00

Turbine Basics

Slide 3

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 4

gGE Energy

TM2500+ Gen VI Package Familiarization

TURBINE BASICS The balloon drawings above illustrate the basic principles upon which gas turbine engines operate. Compressed inside a balloon, as in (A) above, exerts force upon the confines of the balloon. Air, which has weight and occupies space, by definition, has mass. The mass of the air is proportional to its density, and density is proportional to temperature and pressure. The air mass confined inside the balloon, accelerates from the balloon, creating a force as it is released (B). This force increases as mass and acceleration increase, as stated in Newton’s second law; force equals mass times acceleration (F = MA).

The force created by the acceleration of the air mass inside the balloon results in an equal and opposite force that causes the balloon to be propelled in the opposite direction, as stated in Newton’s third law (for every action, there is an equal and opposite reaction). Replacing the air inside the balloon, as in (C) sustains the force and, although impractical, allows a load to be driven by the force of the air mass accelerating across and driving a turbine, as in (D). In (E) a more practical means of sustaining the force of an accelerating air mass used to drive a load is illustrated. A housing contains a fixed volume of air, which is compressed by a motor driven compressor. Acceleration of the compressed air from the housing drives a turbine that is connected to the load. In (F) fuel is injected between the compressor and the turbine to further accelerate the air mass, thus multiplying the force used to drive the load. In (G) the motor is removed and the compressor is powered by a portion of the combustion gas, thus making the engine self-sufficient as long as fuel is provided. In (H) a typical gas turbine-engine operation is represented. Intake air is compressed, mixed with fuel and ignited. The hot gas is expanded across a turbine to provide mechanical power and exhausted to atmosphere.

F-000-10-10-000-00

Turbine Basics

Slide 5

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Turbine Operation Vs.Reciprocating Engine Operation F-000-10-10-000-00

Turbine Basics

Slide 6

gGE Energy

TM2500+ Gen VI Package Familiarization

COMPRESSION – COMBUSTION – EXPANSION – EXHAUST Four processes occur in gas turbine engines, as illustrated above. These processes, first described by George Brayton and called the Brayton cycle, occur in all internal combustion engines. The Brayton steps are as follows: Compression occurs between the intake and the outlet of the compressor (Line A-B). During this process, pressure and temperature of the air increases. Combustion occurs in the combustion chamber where fuel and air are mixed to explosive proportions and ignited. The addition of heat causes a sharp increase in volume (Line BC). Expansion occurs as hot gas accelerates from the combustion chamber. The gases at constant pressure and increased volume enter the turbine and expand through it. The sharp decrease in pressure and temperature (Line C-D). Exhaust occurs at the engine exhaust stack with a large drop in volume and at a constant pressure (Line D-A). The number of stages of compression and the arrangement of turbines that convert the energy of accelerating hot gas into mechanical energy are design variables. However, the basic operation of all gas turbines is the same.

F-000-10-10-000-00

Turbine Basics

Slide 7

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 8

gGE Energy

TM2500+ Gen VI Package Familiarization

CONVERGENT AND DIVERGENT DUCTS Compressors in gas turbine engines use convergent and divergent ducts to generate the high pressures necessary to (a) provide a “wall of pressure,” preventing expanding hot gas from exiting through the engine inlet, as well as, through the exhaust; and (b) provide the proper ratio of air-to-fuel for efficient combustion and cooling of the combustion chamber. Pressure decreases through convergent ducts and increases through divergent ducts, a phenomenon which is demonstrated in paint spray equipment. Compressed air, forced through a convergent duct, generates a lower pressure through the narrow section to draw in paint. Expansion through a divergent section then increases pressure and air volume, dispersing the paint in an atomized mist.

F-000-10-10-000-00

Turbine Basics

Slide 9

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 10

gGE Energy

TM2500+ Gen VI Package Familiarization

INLET GUIDE VANES Inlet guide vanes direct, or align, airflow into the first rotating blade section where velocity is increased by the addition of energy. The following stator vane section is divergent, providing an increase in static pressure and a decrease in air velocity. Airflow then enters the second stage at a higher initial velocity and pressure than at the inlet to the preceding stage. Each subsequent stage provides an incremental increase in velocity and static pressure until the desired level of pressure and velocity is reached.

Some compressor stator vanes are designed to move, changing their divergence, allowing regulation of compressor outlet pressure and velocity to achieve the proper ratio of air for fuel combustion and cooling versus engine speed and power output.

F-000-10-10-000-00

Turbine Basics

Slide 11

gGE Energy

TM2500+ Gen VI Package Familiarization

Axial Flow Compressor

F-000-10-10-000-00

Centrifugal Flow Compressor

Turbine Basics

Slide 12

gGE Energy

TM2500+ Gen VI Package Familiarization

COMPRESSORS Compressors in gas turbine engines use convergent and divergent ducts to generate the high pressures necessary to (a) provide a “wall of pressure,” preventing expanding hot gas from exiting through the engine inlet as well as through the exhaust; and (b) provide the proper ratio of air-to-fuel for efficient combustion and cooling of the combustion chamber. Pressure decreases through convergent ducts and increases through divergent ducts, a phenomenon which is demonstrated in paint spray equipment. Compressed air, forced through a convergent duct, generates a lower pressure through the narrow section to draw in paint. Expansion through a divergent section then increases pressure and air volume, dispersing the paint in an atomized mist. All turbine engines have a compressor to increase the pressure of the incoming air before it enters the combustor. Compressor performance has a large influence on total engine performance. There are two main types of compressors: axial and centrifugal. In the illustration, the example on the left is called an axial compressor because the flow through the compressor travels parallel to the axis of rotation. An apparent contradiction in the operation of the axial-flow compressor is that high pressure is generated, although the overall divergent shape would appear to cause a lower output pressure. Output pressure is increased by divergence in each static inter-stage section. Rotating compressor blades between each static stage increases the velocity that is lost by injecting energy. The compressor on the right is called a centrifugal compressor because the flow through this compressor is turned perpendicular to the axis of rotation. Centrifugal compressors, which were used in the first jet engines, are still used on small turbojets and turbo-shaft engines. Modern large turbojet, turbofan, and turbo-shaft engines usually use axial compressors.

F-000-10-10-000-00

Turbine Basics

Slide 13

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 14

gGE Energy

TM2500+ Gen VI Package Familiarization

COMPRESSOR STALL A stall can happen within the compressor if the air moves from its general direction of motion (also known as the angle of attack). At this point, the low pressure on the upper surface disappears on the stator blade. This phenomenon is known as a stall. As pressure is lost on the upper surface, turbulence created on the backside of the stator blade forms a wall that will lead into the stall. Stall can be provoked if the surface of the compressor blade is not completely even or smooth. A dent in the blade, or a small piece of material on it, can be enough to start the turbulence on the backside of the blade, even if the angle of attack is fairly small. Each stage of compression should develop the same pressure ratio as all other stages. When a stall occurs, the front stages supply too much air for the rear stages to handle, and the rear stage will choke. High Angle of Attack If the angle of attack is too high, the compressor will stall. The airflow over the upper airfoil surface will become turbulent and destroy the pressure zone. This will decrease the compression airflow. Any action that decreases airflow relative to engine speed will increase the angle of attack and increases the tendency to stall. Low Angle of Attack If there is a decrease in the engine speed, the compression ratio will decrease with the lower rotor velocities. With a decrease in compression, the volume of air in the rear of the compressor will be greater. This excess volume of air causes a choking action in the rear of the compressor with a decrease in airflow. This in turn decreases the air velocity in the front of the compressor and increases the tendency to stall.

F-000-10-10-000-00

Turbine Basics

Slide 15

gGE Energy

TM2500+ Gen VI Package Familiarization

Can Type Combustor

F-000-10-10-000-00

Annular Type Combustor

Turbine Basics

Slide 16

gGE Energy

TM2500+ Gen VI Package Familiarization

COMBUSTORS All turbine engines have a combustor, in which the fuel is combined with high pressure air and burned. The resulting high temperature exhaust gas is used to turn the turbine and produce thrust when passed through a nozzle. The combustor is located between the compressor and the turbine. The combustor is arranged like an annulus, or a doughnut, as shown by illustrations above. The central shaft that connects the turbine and compressor passes through the center hole. Combustors are made from materials that can withstand the high temperatures of combustion. The liner is often perforated to enhance mixing of the fuel and air.

There are three main types of combustors, and all three designs are found in gas turbines: • The combustor at the right is an annular combustor with the liner sitting inside the outer casing which has been peeled open in the drawing. Many modern combustors have an annular design. • The combustor on the left is an older can or tubular design. Each can has both a liner and a casing, and the cans are arranged around the central shaft. • A compromise design (not shown) is a can-annular design, in which the casing is annular and the liner is can-shaped. The advantage to the can-annular design is that the individual cans are more easily designed, tested, and serviced. Turbine blades exist in a much more hostile environment than compressor blades. Located just downstream of the combustor, turbine blades experience flow temperatures of more than a thousand degrees Fahrenheit. Turbine blades must be made of special materials that can withstand the heat, or they must be actively cooled. In active cooling, the nozzles and blades are hollow and cooled by air which is bled off the compressor. The cooling air flows through the blade and out through the small holes on the surface to keep the surface cool.

F-000-10-10-000-00

Turbine Basics

Slide 17

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 18

gGE Energy

TM2500+ Gen VI Package Familiarization

FLAME-STABILIZING AND GENERAL-FLOW PATTERNS The flame stabilizing and general-flow patterns are illustrated above for a typical “can-type” combustion chamber. Although modern engines use one continuous annular combustion chamber, the can-type simplifies illustration of the cooling and combustion techniques used in all combustion chambers. The temperature of the flame illustrated in the center of the combustor is approximately 3200°F at its tip when the engine is operating at full load. Metals used in combustion chamber construction are not capable of withstanding temperatures in this range; therefore, the design provides airflow passages between the inner and the outer walls of the chamber for cooling and flame shaping. Air flowing into the inner chamber is directed through small holes to shape the flame centering it within the chamber, to prevent its contact with the chamber walls. Approximately 82% of the airflow into combustion chambers is used for cooling and flame shaping; only 18% is used for fuel combustion. Regulation of fuel flow determines engine speed. Stator vane control in the compressor controls pressure and velocity into the combustion chamber as a function of compressor speed.

F-000-10-10-000-00

Turbine Basics

Slide 19

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 20

gGE Energy

TM2500+ Gen VI Package Familiarization

TURBINE All gas turbine engines have a turbine located downstream of the combustor to extract energy from the hot flow and turn the compressor. Work is done on the turbine by the hot exhaust flow from the combustor. Since the turbine extracts energy from the flow, the pressure decreases across the turbine. The pressure gradient helps keep the boundary layer flow attached to the surface of the turbine blades. Since the boundary layer is less likely to separate on a turbine blade than on a compressor blade, the pressure drop across a single turbine stage can be much greater than the pressure increase across a corresponding compressor stage. A single turbine stage can be used to drive multiple compressor stages. Because of the high pressure change across the turbine, the flow tends to leak around the tips of the blades. The tips of turbine blades are often connected by a thin metal band to keep the flow from leaking. Turbine blades exist in a much more hostile environment than compressor blades. Sitting just downstream of the combustor, the blades experience flow temperatures of more than a thousand degrees Fahrenheit. Turbine blades must be made of special materials that can withstand the heat, or they must be actively cooled. In active cooling, the nozzles and blades are hollow and cooled by air which is bled off the compressor. The cooling air flows through the blade and out through the small holes on the surface to keep the surface cool.

F-000-10-10-000-00

Turbine Basics

Slide 21

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 22

gGE Energy

TM2500+ Gen VI Package Familiarization

TURBINE (Continued) The compressor drive turbine is an “impulse reaction”-type designed for maximum efficiency in converting hot-gas flow into rotational mechanical energy. A first-stage fixed nozzle directs flow into the first-stage of rotating blades. The impulse of expanding hot gas upon the lower surface of each rotating blade propels motion in the upward direction. Hot gas flow above the following blade creates a lower pressure above the blade as above an aircraft wing, causing additional rotational force. Subsequent stages operate identically, multiplying the rotational force. Compressor and loaddriving turbines consist of a varying number of stages, depending upon the load being driven and other design considerations.

F-000-10-10-000-00

Turbine Basics

Slide 23

gGE Energy

TM2500+ Gen VI Package Familiarization

.

Single Shaft

Twin Shaft

Concentric Shaft with Power Turbine

Concentric Shaft

F-000-10-10-000-00

Turbine Basics

Slide 24

gGE Energy

TM2500+ Gen VI Package Familiarization

TURBINE SHAFTS The figure above shows the standard gas turbine shaft arrangements. Single shaft illustration is the traditional single shaft assembly. It consists of the axial flow compressor; Turbine and Power Turbine are all mechanically linked. If we add to this shaft the generator and gearbox, we have a shaft system with a high moment of inertia. This is the favored configuration for electrical generation because this provides additional speed (Frequency) stability of the electrical current during large load fluctuations. This configuration is typical of heavy-duty industrial “frame” turbines, such as the MS7001. The twin shaft illustration shows the standard two shaft arrangement with the compressor and turbine only connected, and an unconnected power turbine and output shaft that will rotate independently. This configuration is favored for variable speeddrive packages, such as pumps and compressors, because the gas generator or gas producer can run at its own optimum speed for a given load. The LM2500 utilizes this configuration and has been applied to both electric power generation and a variety of mechanical drive applications. Aircraft jet engines have for many years been adapted for industrial use as shown in the diagrams above. The concentric shaft illustration, above left, shows a more complicated aero-derivative industrial turbine arrangement. This, too, is still essentially a two shaft configuration but the gas generator core (an original jet-engine) was designed with two spools, a Low Pressure Shaft and a High Pressure Shaft. This engine configuration allows the load to be driven from either the exhaust end or the compressor air intake end. This is the configuration used by the LM6000 The concentric shaft with power turbine illustration is essentially a two shaft arrangement with a gas generator originally designed for propulsion. An independently rotating Power Turbine, manufactured especially to match the flow of the jet engine, is added to the gas path as the power/torque producer. This configuration is found in the LM1600 and the LMS100.

F-000-10-10-000-00

Turbine Basics

Slide 25

gGE Energy

F-000-10-10-000-00

TM2500+ Gen VI Package Familiarization

Turbine Basics

Slide 26

gGE Energy

TM2500+ Gen VI Package Familiarization

NOx CONTROL Oxides of Nitrogen result from the thermal fixation of molecular nitrogen and oxygen in the combustion air. Its rate of formation is extremely sensitive to local flame temperature and, to a lesser extent, to local oxygen concentrations. Virtually all thermal NOx is formed in the region of the flame at the highest temperature. Maximum thermal NOx production occurs at a slightly lean fuel-to-air ratio due to the excess availability of oxygen for reaction within the hot flame zone. Control of local flame fuel-to-air ratio is critical in achieving reductions in thermal NOx. Combustion Controls Reduction of Nox emissions are accomplished by: • Injection of water or steam at the fuel nozzle in order to reduce combustion temperature • Specially designed Dry Low Emissions (DLE) combustors and fuel systems The injection of water or steam into the flame area of a turbine combustor provides a heat sink, which lowers the flame temperature and thereby reduces thermal NOx formation. Water or steam injection, also referred to as "wet controls," have been applied effectively to both aeroderivative and heavy duty gas turbines, and to all configurations. Reduction efficiencies of 70 to 85+ percent can be achieved with properly controlled water or steam injection, with NOx emissions generally higher for oil-fired turbines than for natural gas-fired units. The most important factor affecting reduction efficiency is the water-to-fuel ratio. In general, NOx reduction increases as the water-to-fuel ratio increases; however, increasing the ratio increases carbon monoxide and, to a lesser extent, hydrocarbon emissions at water-to-fuel ratios less than one. Further, energy efficiency of the turbine decreases with increasing water-to-fuel ratio. Post-Combustion Controls The major type of post-combustion control used in gas turbines is Selective Catalytic Reduction (SCR). Applications use SCR to supplement reductions from steam or water injection, or combustion modifications. Carefully designed SCR systems can achieve NOx reduction efficiencies as high as 90 percent. The Selective Catalytic Reduction (SCR) process reduces NOx emissions by using ammonia in the presence of a catalyst. Vaporized ammonia is injected into the flue gas at the appropriate temperature. The ammonia functions, in the presence of the NOx removal catalyst, as a reducing agent to decompose nitrous oxides NOx in the flue gas into nitrogen gas and water vapor. F-000-10-10-000-00

Turbine Basics

Slide 27

Tab 3

gGE Energy

TM2500+ Gen VI Package Familiarization

Engine Overview

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Genealogy

Derived from Proven Technology F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Turbine Modules

Mature rating is approximately 42,000 SHP G4 (4th Generation) is approximately 46,000 SHP F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Comparison

=13.8” longer

Maximizes Design Commonality with Technology Advancements F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

All references to location or position on the LM2500+ are based on the assumption that the individual is standing behind the engine and looking forward. This is true in all cases unless stated otherwise. All GE engines rotate CW aft looking forward, (ALF)

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Following terminology. T2 (Compressor Inlet Temperature or CIT) P2 (Compressor Inlet Total Pressure or CDP) Ps3 (Compressor Discharge Static Pressure of CDP) T3 Compressor Discharge Temperature T4.8 (Power Turbine Inlet Temperature) P4.8 (Power Turbine Inlet Pressure) PTB (Pressure Thrust Balance) F-025-10-10-101-00

LM2500+ Engine Construction

4.8

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Turbine Assembly The LM2500+ gas turbine is a simple cycle, two-shaft, internal combustion engine consisting of the following: 1. 2. 3. 4. 5.

Inlet Components Gas Generator. Power Turbine Exhaust Components High Speed Coupling Shaft

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

MAIN GAS PATH F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Frames The LM2500+ has 4 frames: 1. Compressor Front Frame (CFF) 2. Compressor Rear Frame (CRF) 3. Turbine Mid Frame (TMF) 4. Turbine Rear Frame (TRF) • Frames are rigid, nonmoving, engine structural elements. The primary purpose of a frame is to provide support.

F-025-10-10-101-00

Energy Learning Center

TMF TMF

9/25/2006

GE Proprietary Information

LM2500+ Engine Construction

6

gGE Energy

TM2500+ Gen VI Package Familiarization

Compressor Front Frame (CFF) F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

BEARINGS AND SUMPS Bearings are classified into two broad categories; friction and anti-friction. The gas turbine utilizes anti-friction type bearings, whereas the generator has friction type bearings. Seven anti-friction roller and ball type bearings support the rotating components and the aerodynamic loads on the LM2500+. The bearings are held together with a cage and race assembly and, by design, the bearings do not generate significant heat from friction. They do, however, absorb heat transmitted from the engine’s hot-gas path and because of this, lube oil is supplied to the bearings for cooling purposes. The roller bearings support radial loads and axial thrust loads are supported by ball bearings. These bearings are located in the sumps A, B, C, D areas.

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

ROLLER BEARING

BALL BEARING

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Generator

Power turbine

33R

BEARING AND SUMP LOCATIONS F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Synthetic lube oil is supplied to the bearings and scavenged out of the sumps by a seven (7) element pump assembly which is mounted on the accessory gearbox. A single supply element provides lubricating oil to all the bearings and gearboxes. The remaining six elements are utilized to scavenge oil away from the bearing sumps, gearboxes, and the air/oil separator. The sump-A scavenge oil drains to the transfer gearbox (TGB) through the 6:00 o’clock compressor front frame (CFF) strut that houses the radial driveshaft, and then oil is scavenged through the transfer gearbox. The No. 4R/4B and No. 5R/6R bearing zones of sump-B and sump-C are individually scavenged, as is the No. 7R bearing zone of sump-D. All sumps emit oil mist-carrying air that is vented to an air-oil separator which is mounted on the front side of the AGB. The oil is then scavenged from the separator and the air is vented to the exhaust diffuser.

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Dry Sump Construction (Simplified)

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Inlet Duct The inlet duct is constructed of aluminum (AMS4026) and shaped like a bellmouth. The inlet duct is painted white, and must be maintained in the painted condition. Centerbody The centerbody is a flow divider bolted to the front of the gas generator. The centerbody is sometimes known as the bulletnose, and is made of a graphite reinforced fiberglass composite.

F-025-10-10-101-00

LM2500+ Engine Construction

unpainted

gGE Energy

TM2500+ Gen VI Package Familiarization

Inlet Duct

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Rubber Gasket

P=P0 vs. P1 1”H20=Alarm 2”H20=S/D

Keep Clean Room Clean!

Inlet has minimum of 200 lbs/sec airflow

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

FOD Screen F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

F-025-10-10-101-00

TM2500+ Gen VI Package Familiarization

LM2500+ Engine Construction

gGE Energy

F-025-10-10-101-00

TM2500+ Gen VI Package Familiarization

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Stage 0 Blisk Blade disk combination comes as one unit. The blades are not removable.

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

F-025-10-10-101-00

TM2500+ Gen VI Package Familiarization

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Variable Vanes • The Inlet Guide Vanes (IGV’s) and next 7 stages of vanes are called Variable Stator Vanes, or VSV’s. These vanes are all mechanically ganged together, and will change their angular pitch in response to a change in compressor inlet temperature or a change in gas generator speed. The purpose of this is to provide stall-free operation of the compressor through-out a wide range of speed and inlet temperatures. F-025-10-10-101-00

• Due to their long length the IGV’s and stages 0, 1and 2 are shrouded. The shrouds are aluminum extrusions split into a matched set of forward and aft halves.

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Variable Stator Vanes (VSV’s) F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

VSV Actuator F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization “Fire eyes” UV Flame Detectors (2 ea) With air cooled sapphire lenses

Compressor Rear Frame

SAC Same as base except 2nd T3 port has been added Made of Inconel 718

B

B (6 ea)

CDP discharge

SAC CRF F-025-10-10-101-00

LM2500+ Engine Construction

DLE CRF

gGE Energy

TM2500+ Gen VI Package Familiarization

DLE vs. Standard Combustor With dry low emissions combustor 2 PX36 combustor dynamic pressure 0-10 psi 2 flame detectors 0-1(on or off)

3 zones A= Outer ring B= Pilot ring C= Inner ring 75 premixed areas

With standard combustor F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

STAGE 2 NOZZLE

STAGE 1 NOZZLE

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

F-025-10-10-101-00

TM2500+ Gen VI Package Familiarization

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

High Pressure Turbine Blade Cooling

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

High Pressure Turbine Rotor Cooling •Cooling air enters HPT rotor forward shaft, provides a cooling flow to the rotor cavity and disks, then is discharged through the rotor blades. •Stage 1 blades are cooled by a combination of internal convection, leading edge internal impingement, and external film cooling.

F-025-10-10-101-00

• Stage 2 cooling is accomplished entirely by convection. • Cooling channels within the blades are serpentine to ensure a uniform temperature distribution across blade surface.

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Stage 1 High Pressure Nozzle Cooling

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

HPTN1 Cooling • Impingement, convection and film cooling circuits within each individual HPTN1 vane are supplied with high pressure cooling air directly from the compressor discharge chamber. • To distribute the cooling flows, inserts are installed into forward and aft cooling chambers machined into the vanes. • High pressure air from the compressor discharge chamber enters the forward insert through the underside of the HPTN1 forward inner seal. F-025-10-10-101-00

• Holes in the insert impinge the high pressure air directly against the inner walls of the forward chamber, displacing hot air, and providing a continuous supply of cool air to absorb heat directly from the metal structure of the vane. • Hot air displaced by the impingement flow is carried out of the vanes through nose holes by convection. • Gill holes in side of the vane maintains a thin layer of film cooling air between the metal structure of the vane and the hot combustor discharge gases.

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Stage 2 High Pressure Nozzle Cooling F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Stage 2 Nozzles (HPTN2) The stage 2 nozzle is also made of a pair of vanes. The nozzle vane is cooled by convection from 13th stage bleed air that enters through the cooling air tubes and cools the center area and leading edge. Some of the air is discharged through holes in the trailing edge, while the remainder is used for cooling the inter-stage seals and the HPTR blade shanks.

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Turbine Mid Frame The turbine mid frame (TMF) supports the aft end of the HPTR, and the forward end of the power turbine rotor. The TMF is bolted between the CRF and the power turbine stator case and provides a smooth diffuser flow passage for the HPT exhaust gas into the power turbine. The 1st stage power turbine nozzles are attached to the rear of the TMF.

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization 13th Stage thrust balance for PT 13th Stage Cooling HPTN2

Turbine Mid Frame (TMF)

9th Stage cooling TMF struts

HP Recoup

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Power Turbine The power turbine is composed of: 1. Low Pressure Turbine Rotor 2. Low Pressure Turbine Stator 3. Turbine Rear Frame (TRF) The power turbine is aerodynamically coupled to the gas generator and is driven by the gas generator exhaust gas. F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

PT thrust balance from 13th stage

6 Stage Power Turbine

Exhaust Diffuser

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Exhaust Components The exhaust duct consists of an inner and outer duct forming the diffusing passage from the turbine rear frame. The inner diffuser duct can be moved aft to gain access to the high speed coupling shaft. The exhaust duct is mounted separately from the gas turbine, and piston-ring type expansion joints are used to accommodate the thermal growth. Note: The exhaust duct is supplied by the packager.

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Six Stage Power Turbine “ 6 Pack “

7B

F-025-10-10-101-00

7R

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Goes up in case of failure, so IGB can be removed

Accessory Gearbox

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

F-025-10-10-101-00

TM2500+ Gen VI Package Familiarization

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

BLEED AIR SYSTEM F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

COMPRESSOR DISCHARGE AIR CDP air is used for combustion (18%) and to cool the combustor. It is also used to cool the 1st stage turbine nozzles and Stage 1 & 2 turbine blades. In DLE applications, CDP air is bled for control of flame temperature. STAGE 9 BLEED AIR Stage 9 bleed air is extracted though holes bored in the stator casing aft of the stage 9 vane dovetails. This air is used for sump pressurization and cooling the TMF struts. Some 9th stage air is also used to pressurize the clutch seal and actuate the exhaust drain valve. STAGE 13 BLEED AIR Stage 13 air is bled from the compressor through holes in the casing into a manifold and is used to cool the 2nd stage turbine nozzles and for thrust balance of the power turbine rotor. F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Venturi to mix package air with 9th stage air for Sump Pressurization

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

High Pressure Recoup

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

HIGH PRESSURE RECOUP SYSTEM The CRF B-sump pressurization system is isolated from the HPC by the CDP and vent labyrinth seals. These seals serve to form HP recoup chamber. The HP recoup airflow results from compressor discharge air leaking across the CDP seal. – During engine operation, the compressor exerts a forward thrust load on the #4B bearing. – High Pressure air in the thrust balance chamber exerts an aft directed force on the HPT rotor to counteract the forward directed thrust load. – HP Recoup air is routed to the forward side of the CRF through series of tubes, combined with high pressure seal leakage air on the aft end of the compressor rotor, and ported out of CRF

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Bottom View F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

F-025-10-10-101-00

TM2500+ Gen VI Package Familiarization

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

HP Recoup Orifice Plate

HP Recoup Pressure Sensing line

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

LM2500+ G4 Operating Parameters

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization Pt2/T2

Duplex RTD’s

T2 operates from –65 to 130 deg F Pt2 operates from 0 to 16 psia

INLET SENSORS F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

T2/P2 Sensor F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Dual element platinum RTD’s Read from –40 to 400 deg F -40 to 204 deg C

Lube Oil System Temperature Sensor F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Lube Oil System RTD

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

2 each Reluctance type Reads 100-12,000 rpm

Magnet creates frequency off ferrous gear

Make sure the two sensors are set at the same distance to avoid a signal mismatch alarm.

Gas Generator Speed sensor F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

NGG A & B F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Operates from –40 to 2000 deg F -40 to 1093 deg C

Piezoelectric 1 on GG @ CRF 0-4 ips velocity 1 on PT @TRF (6 pk) 0-2 ips velocity @ Bearing support on 2 stage

Dual element thermocouple Alumel/Chromel

Bypassed with GG Speed less than 5500 rpm

T3 Sensor F-025-10-10-101-00

Accelerometer LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

T3 Sensor

F-025-10-10-101-00

ACCELEROMETER

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Ps3 F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Dual ignition kit # 682L510G02 Consists of ignition unit, lead, and Igniter

Ignition System F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

IGNITORS

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

ULTRAVIOLET FLAME SENSOR F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

ULTRAVIOLET COMBUSTOR FLAME SENSOR

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

H

A

Reads between -40 to2000 deg F

B G

C

F

E

D

T4.8 Thermocouple Harness (ALF) F-025-10-10-101-00

T4.8 Thermocouple

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

T48 Sensors

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Reads 0- 125 psia

Gas Generator Discharge Pressure P4.8 Sensor F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

P48 Sensor

F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

Reads 0-10,000 rpm

Power Turbine Speed Pickup F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

NPT F-025-10-10-101-00

LM2500+ Engine Construction

gGE Energy

TM2500+ Gen VI Package Familiarization

PTB F-025-10-10-101-00

LM2500+ Engine Construction

Tab 4

g GE Energy

TM2500+ Gen VI Package Familiarization

LM2500+ TURBINE LUBE OIL SYSTEM

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 1

g GE Energy

TM2500+ Gen VI Package Familiarization SYNTHETIC LUBE OIL SYSTEM

General The LM2500+ turbine is lubricated by an internal pump and lubrication system described in GE publication GEK-105054. GE AE provides an external lube oil system to filter, cool, and de-aerate the lube oil discharged from the internal system. The external system is fed by a scavenge pump, which is driven by the turbine accessory gearbox whenever the turbine gas generator is rotating. Purpose The synthetic lube oil (SLO) system functions to prevent damage to the high-pressure (HP) and low-pressure (LP) rotor bearings and sumps as well as the inlet transfer gearbox (TGB) and accessory gearbox (AGB). The SLO system also provides oil for operating the actuators for the variable stator vanes (VSVs) and lubrication to protect the over-running clutch for the hydraulic starter motor.

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 2

g GE Energy

TM2500+ Gen VI Package Familiarization

Lube System for LM2500+ w/6 Stage PT F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 3

g GE Energy

TM2500+ Gen VI Package Familiarization

Synthetic Lube Oil Reservoir

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 4

g GE Energy

TM2500+ Gen VI Package Familiarization

Lube Oil and Scavenge Pump Assembly The turbine lube oil and scavenge pump assembly is mounted on the aft side of the Accessory Gearbox and is a seven element, positive displacement, vane type pump. One element is used for the lube oil supply and six elements are used for the lube scavenging. Within the pump are inlet screens, one for each element, and a lube supply pressure-limiting valve. Each scavenge return line is equipped with electrical / magnetic remote-reading chip detectors. Each chip detector indicates chip collection when resistance across the detector drops.

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 5

g GE Energy

TM2500+ Gen VI Package Familiarization

Magnetic Chip Detectors

Sump Scavenge Screen

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 6

g GE Energy

TM2500+ Gen VI Package Familiarization

Scavenge Line RTD’s

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 7

g GE Energy

TM2500+ Gen VI Package Familiarization

Air/Oil Separator To prevent excessive oil losses from venting oil vapor overboard, all sumps and gearboxes are vented to the Air/Oil Separator, located on the turbine lube oil tank. The sump vent air is discharged after passing through the separator. F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 8

g GE Energy

TM2500+ Gen VI Package Familiarization

Fin – Fan Cooler The Fin – Fan cooler is located off base and is equipped with two fans and two tube bundles to cool oil for both the synthetic and mineral lube oil systems. Synthetic lube oil may bypass the cooler module if thermostatic control valve TCV-1001 determines the temperature to be  60° C (140 qF).

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 9

g GE Energy

TM2500+ Gen VI Package Familiarization

Scavenge Filter F-025-10-20-103-00

Supply filter LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 10

g GE Energy

TM2500+ Gen VI Package Familiarization

IGB

AGB F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 11

g GE Energy

TM2500+ Gen VI Package Familiarization

“Over-running” Clutch F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 12

g GE Energy

TM2500+ Gen VI Package Familiarization

Typical Sump F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 13

g GE Energy

F-025-10-20-103-00

TM2500+ Gen VI Package Familiarization

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 14

g GE Energy

TM2500+ Gen VI Package Familiarization

Instruments and Controls Lube oil pressures and temperatures at critical points are transmitted and displayed on the desktop HMI. Gauges and pressure transmitters in the system have been installed with a needle valve in the instrument sensing line to permit replacement and calibration without disturbing the lube oil flow. The system piping has been provided with manually operated ball valves to isolate components for repairs and maintenance.

System Operation Refer to Flow & Instrument Diagram (F&ID) XXXXX-751244, Turbine Lube Oil System. System operation for the GTG set is as follows:

The internal turbine lube oil pump draws lube oil from the 150-gallon reservoir through the check valve and inlet port L1. Oil passes from discharge port L2 2 to the lube oil supply filter assembly in the external system. Differential pressure on the supply line filter is monitored by transmitter PDT-1006, which sends a 4-20 mA signal the electronic-turbine control system. Pressure differential indicator PDI-1006 displays the filter differential pressure at the operator screen as well as locally at the turbine gauge panel. When differential pressure across the filter reaches 20 psid (138 kPaD) increasing, the control system activates high alarm PDAH-1006. Manual shut-off valves upstream and downstream of the filter allow for maintenance. F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 15

g GE Energy

TM2500+ Gen VI Package Familiarization

System Operation (cont.) Oil from the filter passes through the oil header port L4 4 into the internal lube oil system of the turbine for distribution to the accessory gearbox and the turbine shaft bearings. Internal sensor TE-1028 (drawing sheet 2) activates an alarm if the temperature of the incoming oil reaches 200 °F (93 °C) increasing. Other internal sensors, TE-1023, TE-1024, TE-1025, TE-1026, and TE-1027, monitor the lube oil temperature in the turbine-bearing sumps. These sensors activate an alarm if the lube oil temperature in any sump reaches 300 °F (149 °C) increasing, and initiate a SML shutdown if the oil temperature reaches 340 °F (171 °C) increasing. Electromagnetic chip detectors, MCD-1060 through MCD-1064 monitor lube oil for metal chips, and initiate an alarm if accumulated chips lower the detectors’ resistance to 100 ohms decreasing. Gauges and electrical devices monitor oil pressure at the header port L5 (drawing sheet 1). Transmitter PT-1021 provides the internal lube oil pressure reading to the electronic-turbine control system. Header pressure is displayed remotely by pressure indicator PI-1021. PT-1021 activates an alarm for the following conditions: · if pressure < 8 psig and if 4500 < ngg < 8000 · if pressure < 25 psig and ngg ≥ 8000 rpm PT-1021 activates an FSLO shutdown for the following conditions: · if pressure < 6 psig and if 4500 < ngg < 8000 · if pressure < 15 psig and ngg ≥ 8000 rpm F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 16

g GE Energy

TM2500+ Gen VI Package Familiarization

System Operation (cont.) Oil drawn from the bearing sumps by the scavenge stage of the turbine pump passes through scavenge oil discharge port L3 to the scavenge filter. System pressure is monitored remotely by PI-1022 upstream of the scavenge filter. Transmitter PT-1022 forwards pressure signals to the electronic-control system which activates alarm PAH-1022 if the scavenge oil pressure rises to 110 psig (758 kPaG) increasing. Pressure differential transmitter PDT-1007 monitors differential pressure across the scavenge filter and forwards signals to the electronic-control system. The control system activates alarm PDAH-1007 when the pressure differential reaches 20 psid (138kPaD) increasing. . Relief valve PSV-1003, located near the scavenge oil filter inlet, prevents the scavenge system pressure from exceeding 140 psig (965 kPaG) by returning excess oil to the reservoir. Otherwise, oil from port L3 is routed through the scavenge lube oil filter assembly, on its way to the fin fan heat exchanger Cooled oil from the heat exchanger is returned to the lube oil reservoir for recirculation. The portion of oil actually routed through the selected cooler is determined by 3-way, thermostatic control valve TCV1001. This valve apportions oil flow through the cooler, as required, to maintain the outlet temperature at < 140 °F (60 °C). When lube oil temperature is low, such as at the start of turbine operation, the thermostatic valve bypasses the oil flow around the heat exchanger to the reservoir. As the lube oil temperature increases during turbine operation, the valve progressively directs more oil through the heat exchanger until, at 140 °F (60 °C), nearly all the oil flows through the heat exchanger. The filtered and cooled scavenged oil returns to the lube oil reservoir, where air and other gases are vented to the atmosphere through the reservoir demister/flame arrestor. F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 17

g GE Energy

TM2500+ Gen VI Package Familiarization

System Operation (cont.) Reservoir oil temperature is maintained at 90 °F (±8 °F) by an integral thermostatic switch TC-1004 and immersion heater HE-1004. A level gauge LG-1000 permits direct (local) observation of the reservoir oil level, while level transmitter LT-1002 forwards signals to the control system for remote monitoring. The control system activates low alarm LAL-1002 when the oil level drops to 9 1/2" (241) or below (as measured from the bottom of reservoir). The control system also activates high alarm LAH-1002 when the oil level rises 18" (457) or above. Temperature element TE-1013 monitors the temperature of the lube oil in the reservoir and forwards signals to the control system. The control system activates alarm TAL-1013 if the oil temperature falls to 70 °F (21 °C) or below.

F-025-10-20-103-00

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 18

g GE Energy

F-025-10-20-103-00

TM2500+ Gen VI Package Familiarization

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 19

g GE Energy

F-025-10-20-103-00

TM2500+ Gen VI Package Familiarization

LM2500+ Turbine Lube Oil System with 6-stage PT

Slide 20

Tab 5

g

GE Energy

TM2500+ Gen VI Package Familiarization

VARIABLE GEOMETRY SYSTEM

F-025-10-10-202-00

Variable Geometry System

Slide 1

g

GE Energy

TM2500+ Gen VI Package Familiarization

VARIABLE GEOMETRY OVERVIEW The LM2500+ variable geometry (VG) system is designed to allow precise control of air flow through the turbine under all operating conditions, in order to achieve a high degree of efficiency, stall-free safety and operational flexibility. Variable stator vanes (VSV) help control air flow during various turbine speeds. While stator vanes are designed for peak aerodynamic efficiency at full speed, they must also be able to function efficiently at part load and reduced speed. At lower speeds the final stages of the compressor can’t ingest the volume of air compressed by the earlier stages, and the variable stators can be positioned to limit the amount of air handled by the first stages of the compressor. As speed increases, the variable stator vanes gradually open until they are fully open at full turbine speed.

The high pressure compressor (HPC) is comprised of 17 stages (numbered 0 through 16). The inlet guide vanes and the next seven stages (Stages 0 – 6) comprise the components referred to as the variable stator vanes. These vanes are mechanically ganged together and their pitch can be changed as needed during turbine operation. Pitch of the blades is changed in response to changes in compressor inlet temperature (T2) or gas generator speed (NGG).

F-025-10-10-202-00

Variable Geometry System

Slide 2

g

TM2500+ Gen VI Package Familiarization

GE Energy

SEVENTEEN STAGES 0 - 16

VARIABLE STAGES 0-6

F-025-10-10-202-00

Variable Geometry System

Slide 3

g

GE Energy

TM2500+ Gen VI Package Familiarization

The VSV system is an integral part of the high pressure compressor stator (HPCS) consisting of IGVs, two VSV actuators and torque shaft, actuation rings, and nonadjustable linkages for each VSV stage.

F-025-10-10-202-00

Variable Geometry System

Slide 4

g

GE Energy

F-025-10-10-202-00

TM2500+ Gen VI Package Familiarization

Variable Geometry System

Slide 5

g

GE Energy

F-025-10-10-202-00

TM2500+ Gen VI Package Familiarization

Variable Geometry System

Slide 6

g

TM2500+ Gen VI Package Familiarization

GE Energy IGV’s

Stages 0 - 6

Non-adjustable Linkages

Torque Shaft

Actuator

Actuation Rings

F-025-10-10-202-00

Variable Geometry System

Slide 7

g

GE Energy

TM2500+ Gen VI Package Familiarization

ACTUATORS The variable vanes are connected to two actuators (3:00 & 9:00) via a pair of torque shafts. When operated by the individual actuators, the torque shafts operate the variable guide vanes through actuation rings and linkages. The integral linear variable differential transformers (LVDT’s) are the feedback type in which the movement of the actuators is used to provide a feedback signal to the VSV control.

F-025-10-10-202-00

Variable Geometry System

Slide 8

g

GE Energy

TM2500+ Gen VI Package Familiarization

PUMP Oil from the turbine oil system is delivered to the VG pump located on the accessory gearbox. The VG hydraulic pump is a fixed-displacement design which supplies pressurized lube oil to the servo-valve assembly for delivery to the actuators. The hydraulic pump/servo-valve houses a motor-positioned hydraulic servo for porting fluid at regulated pressures. All return flow is bypassed back to the high pressure side of the gas turbine lube oil pump, and the VSV servo-valve will close the VSVs in the event of a failure of the hydraulic pump.

F-025-10-10-202-00

Variable Geometry System

Slide 9

g

GE Energy

TM2500+ Gen VI Package Familiarization

Variable Geometry Pump F-025-10-10-202-00

Variable Geometry System

Slide 10

g

TM2500+ Gen VI Package Familiarization

GE Energy

VSV CONTROL The VG control system consists of the VG hydraulic pump and an electrohydraulic VSV servovalve assembly. The hydraulic pump/VSV servovalve houses a torque motor-positioned hydraulic servo for porting fluid at regulated pressures, and two VSV actuators with integral linear-variable differential transformers (LVDT’s) to provide feedback position signals to the off engine control unit. The VG pump provides hydraulic flow to the head- and rod-ends of the VSV actuators. The actuators are positioned in response to compressor inlet temperature (T2) and gas generator speed (NGG). For any one temperature and any one speed, the VSVs take one position and remain in that position until the NGG or T2 changes. Positioning of the inlet guide vanes (IGV) and VSV’s is scheduled by packager-supplied control system electrical input to the servovalve, mounted on the VG hydraulic pump. Position feed back to the control is provided by LVDT’s from the VSV actuators.

VG PUMP/SERVO MOTOR CONTROL (NGG & T2)

PISTON/LVDT

F-025-10-10-202-00

Variable Geometry System

Slide 11

g

GE Energy

F-025-10-10-202-00

TM2500+ Gen VI Package Familiarization

Variable Geometry System

Slide 12

g

GE Energy

F-025-10-10-202-00

TM2500+ Gen VI Package Familiarization

Variable Geometry System

Slide 13

Tab 6

g

GE Energy

TM2500+ Gen VI Package Familiarization

LM2500+ HYDRAULIC START SYSTEM

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 1

g

GE Energy

TM2500+ Gen VI Package Familiarization

HYDRAULIC START SYSTEM The hydraulic start system turns the engine and is capable of starting it, fuel purging, water washing, cool down, and conducting maintenance. The hydraulic start unit is located on the auxiliary skid and consists of a reservoir, filters, heat exchanger, charge pump and motor, junction box, and a hydraulic starter motor mounted on the starter drive pad of the turbine auxiliary gearbox. This hydraulic starter motor turns the engine. Two operating speeds are provided: a low speed for water washing and maintenance, and a high speed for turbine starting and fuel purging. Engine speed can be controlled automatically from the DCS. Transmitters located on the auxiliary skid allow for monitoring of the hydraulic charge pump and main system pressures, temperatures, and fluid levels on the DCS monitor. Local gauges PI-6009 and PI-6012 are also provided on the auxiliary skid for troubleshooting purposes. Additional details on the hydraulic start system can be found in engineering drawings. This section provides an overview of the hydraulic start system.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 2

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Start System Operation (Refer to F&ID xxxxxxx-751232 Hydraulic Start System) Hydraulic fluid is drawn from the reservoir by the charge pump. The charge pump replenishes the main, closed-loop start system with hydraulic fluid at 350 psi (2413 kPaG). The main pump increases the hydraulic fluid pressure to 5200 psig (35853 kPaG) and delivers the pressurized fluid to the hydraulic starter motor at approximately 56 gpm (212 L/min).

Discharge from the hydraulic starter motor is routed back to the hydraulic reservoir through filter and cooler assemblies. Filters remove particles ³ 10 μ. The cooler removes heat generated during starter motor operation.

Power from the MCC lighting-and-distribution panel is applied to the power supply for the hydraulic start unit.

The hydraulic start system is automatically controlled. The solenoid operated valve SOV-6019 for the pump-control piston and the MCC unit starter are controlled by electronic systems at the TCP.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 3

g

GE Energy

F-025-10-20-050-00

TM2500+ Gen VI Package Familiarization

LM2500+ Hydraulic Start System

Slide 4

g

GE Energy

TM2500+ Gen VI Package Familiarization

Reservoir Hydraulic fluid is stored in a 40-gal (182 L) stainless steel tank equipped with sight level gauge LG-6020, temperature element TE-6003, fluid-level transmitter LT-6001, thermostatically controlled immersion heaters HE-6010 and TC-60101 and a 200-mesh, hydraulic pump suction strainer with an integrated bypass valve. During turbine engine operation, hydraulic fluid is drawn from the reservoir through the strainer and the supply shutoff valve, and flows into the charge pump. Should the hydraulic pump strainer become obstructed with differential pressures ³ 3 psid, (20.7 kPaD) hydraulic fluid will bypass the filter element to prevent damage to the filter assembly. The supply line is monitored by pressure indicator PI-6000 located between the supply shutoff valve and the charge pump.

NOTICE

CHANGE FILTER ELEMENTS ON A REGULAR BASIS. REPLACE THEM AT LEAST ONCE A YEAR, REGARDLESS OF INDICATOR READINGS, AND SOONER IF CONDITIONS WARRANT.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 5

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Starter Reservoir F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 6

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Oil Charge/Main Pump Assembly Hydraulic Oil Charge Pump The charge pump is one of two pumps in the hydraulic pump assembly. The charge pump takes suction from the hydraulic oil reservoir and discharges the hydraulic oil at 350 psig (2413 kPag) at a flow rate of 12 gpm (45 lpm) to the charge pump filter. The charge pump also replenishes lost fluids in the hydraulic pump case and in the main pump, closed-loop hydraulic system. Excess hydraulic pump case supply oil is routed to the hydraulic reservoir through an inline relief valve, set to open at 25 psid (172 kPaD). From the charge pump, hydraulic fluid flows through the charge pump filter assembly and into the main pump, where the hydraulic fluid is pressurized for the starter motor loop. Charge Pump Filter The charge pump filter is a “spin on” type single stage filter. The filter has no visual indicator to show filter condition. The filter housing has a bypass valve that will open, bypassing oil around the filter if differential pressure across the filter reaches 50 psid (344.6 kPaD).

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 7

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Oil Charge/Main Pump assembly w/charge pump filter

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 8

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Oil Charge/Main Pump Assembly Main Hydraulic Oil Pump The main hydraulic starter pump, located on the auxiliary module, is driven by a three-phase, constantspeed, 200 horsepower, AC electric motor. The hydraulic starter pump has a variable swash plate, whose angle is controlled by software logic signals from the turbine control panel (TCP). The signals are applied to a solenoid operated valve (SOV) on the hydraulic starter pump assembly. The hydraulic starter pump supplies hydraulic fluid under high pressure to the turbine starter motor. As the hydraulic starter pump’s swash plate angle is increased or decreased, more or less hydraulic fluid under pressure is applied to the pistons in the turbine starter motor, thereby increasing or decreasing the revolutions per minute (rpm) of the starter and the turbine engine. Fluid pressure from the hydraulic starter pump is applied to pistons in the turbine starter motor causing the motor to rotate.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 9

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Oil Charge/Main Pump Assembly

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 10

g

GE Energy

F-025-10-20-050-00

TM2500+ Gen VI Package Familiarization

LM2500+ Hydraulic Start System

Slide 11

g

GE Energy

F-025-10-20-050-00

TM2500+ Gen VI Package Familiarization

LM2500+ Hydraulic Start System

Slide 12

g

GE Energy

TM2500+ Gen VI Package Familiarization

LOW PRESSURE RETURN and COOLER LP RETURN FILTER Hydraulic oil returning from the starter to the suction side of the auxiliary skid pump is routed through a low-pressure return filter. The filter is a 10 micron, “spin-on” type double element filter with a 25 psi bypass circuit and differential pressure indicator. After leaving the LP return filter, hydraulic oil flows back to the suction side of the auxiliary skid hydraulic pump. CASE DRAIN FILTER Hydraulic oil returning from the starter’s case drain is routed through a case-drain return filter. The filter is a 10 micron, single element filter with a 25 psi bypass circuit and differential pressure indicator. After leaving the case drain filter, hydraulic oil flows through a heat exchanger and then returns to the auxiliary skid hydraulic oil tank. HEAT EXCHANGER The heat exchanger is an air/fan cooled unit that enables extended cranking capability for cool-down cycles without exceeding temperature limits. An electric motor-driven fan cools hydraulic oil returning from the starter and the discharge from the heat exchanger is routed directly to the hydraulic reservoir. The 3 HP motor is dual rated at 380/460 VAC. The temperature of the hydraulic fluid is monitored by high-temperature element TE-6002. If the temperature is ³ 180 °F (82 °C), the control system will activate an alarm.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 13

g

GE Energy

TM2500+ Gen VI Package Familiarization

LP Return Filter F-025-10-20-050-00

Case Drain Filter LM2500+ Hydraulic Start System

Slide 14

g

GE Energy

TM2500+ Gen VI Package Familiarization

Differential Press Indicator

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 15

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Oil Cooler F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 16

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Starter Motor The hydraulic starter motor, located on the auxiliary gearbox, is driven by hydraulic fluid under high pressure from the main hydraulic oil pump. The hydraulic starter motor has a manually variable angle swash plate with movable pistons. The high-pressure fluid forces the pistons to move within the cylinder, causing the motor to rotate.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 17

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Starter Motor F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 18

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Pump

F-025-10-20-050-00

Hydraulic Starter

LM2500+ Hydraulic Start System

Slide 19

g

GE Energy

TM2500+ Gen VI Package Familiarization

Hydraulic Starter Clutch F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 20

g

GE Energy

TM2500+ Gen VI Package Familiarization

Centrifugal Starting Clutch In the starting motor output shaft a centrifugal clutch allows engagement of the starting motor to the gas turbine generator at the beginning of the start-up sequence, and disengagement as soon as the HP runs faster than the starting motor. At 4500 rpm’s XN 2.5 speed the control system will signal a shutdown of the hydraulic start motor. For proper clutch operation, the oil flow to the clutch should be continuously controlled to a minimum of .5 qt/minute (.47 L/min) and to a maximum of 1.25 qt/minute (1.18 L/min). An orifice plate controls this oil flow. This clutch is also referred to as an overriding or overrunning clutch. At standstill of the gas turbine generator and the starting motor, the pawls of the centrifugal clutch engage in the gear on the starting motor output shaft. Weak plate springs push the pawls in the gear teeth. As soon as the starting motor begins to run, it will drive the HP shaft. The pawls tend to move outwards due to centrifugal force, but as long as the starting motor supplies torque to the HP rotor, the claws will stay engaged by friction. At approximately 4500 rpm the control system will shut down the starting motor. This will cause the torque to reverse and, immediately, the claws will disengage. When during the shutdown sequence the gas generator runs down to standstill, the centrifugal force on the pawls will gradually diminish, allowing the weak springs to bring the claws to the starting motor gear. As soon as the HP shaft speed is below 1000 rpm, the gas turbine may be started again. The spring force in the clutch then overrides the centrifugal force of the claws, allowing full engagement of the claws.

F-025-10-20-050-00

LM2500+ Hydraulic Start System

Slide 21

Tab 7

gGE Energy

TM2500+ Gen VI Package Familiarization

LM2500+ DUAL FUEL SYSTEM

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 1

gGE Energy

TM2500+ Gen VI Package Familiarization

LIQUID FUEL SYSTEM The liquid fuel is delivered to the auxiliary trailer at the following conditions: •40 gpm (151 LPM) •30 psig (207 kPag) •Filtered to 5 micron

On the auxiliary trailer, the liquid fuel passes through the following: •A 100-mesh strainer •A positive displacement gear type pump •A set of duplex filters

The liquid fuel is delivered to the main trailer at the following conditions: •45 gpm (170 LPM) •140°F (60°C) Max.

•1100 psig (7584kPaG) •Filtered to 10 micron

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 2

gGE Energy

TM2500+ Gen VI Package Familiarization

LIQUID FUEL SYSTEM On the main trailer, the liquid fuel then passes through: •An orifice plate •A flow divider •The secondary liquid fuel manifold, a low-flow circuit •The secondary port of the fuel nozzles

As load on the engine increases, additional liquid fuel flows through •The upstream solenoid shut off valve •The liquid fuel control valve, which is controlled by the TCP. •The downstream shutoff valve

The liquid fuel then flows to: •The primary liquid fuel manifold, a high-flow circuit •The primary port of the fuel nozzles •The secondary liquid fuel manifold, a low-flow circuit •The secondary port of the fuel nozzles

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 3

gGE Energy

TM2500+ Gen VI Package Familiarization

Liquid Fuel Boost Pump

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 4

gGE Energy

TM2500+ Gen VI Package Familiarization

Duplex Liquid Fuel Filters

Liquid Fuel Boost Pump

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 5

gGE Energy

TM2500+ Gen VI Package Familiarization

Liquid Fuel Flow Control Valve

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 6

gGE Energy

TM2500+ Gen VI Package Familiarization

Liquid Fuel Manifolds

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 7

gGE Energy

TM2500+ Gen VI Package Familiarization

Secondary Fuel/Water Injection Manifold

Primary Fuel Manifold

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 8

gGE Energy

TM2500+ Gen VI Package Familiarization

Liquid Fuel/Water

Gas Fuel

Combustion Air

Mounting Flange Gas Fuel

Liquid Fuel Water Injection

Dual Fuel Nozzle

F-025-10-20-306-00

Fuel Nozzle Tip

TM2500+ Dual Fuel System

Slide 9

gGE Energy

F-025-10-20-306-00

TM2500+ Gen VI Package Familiarization

TM2500+ Dual Fuel System

Slide 10

gGE Energy

TM2500+ Gen VI Package Familiarization

FUEL GAS SYSTEM The fuel gas is delivered to the auxiliary trailer at the following conditions: •250 MMBtu/hr Max. •180°F (121°C) Max. •505 ± 20 Psig (3482 ± 138 kPag) •Filtered to 3 micron

On the auxiliary trailer, the gas fuel passes through the following: •A manual shut off valve •A set of duplex filters

•A flow meter

The gas fuel is then delivered to the main trailer where it passes through the following: •The upstream fuel gas shut off valve •The fuel gas control valve •The downstream fuel gas shut off valve •The fuel gas manifold •The 30 fuel nozzles F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 11

gGE Energy

TM2500+ Gen VI Package Familiarization

Duplex Gas Fuel Filter

Gas Fuel Flow Meter

Manual Shut Off Valve F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 12

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Fuel Shut Off Valves

Gas Fuel Flow Control Valve

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 13

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Fuel Manifold

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 14

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Fuel Inlet

Duel Fuel Nozzle

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 15

gGE Energy

F-025-10-20-306-00

TM2500+ Gen VI Package Familiarization

TM2500+ Dual Fuel System

Slide 16

gGE Energy

TM2500+ Gen VI Package Familiarization

WATER INJECTION SYSTEM To control the amount of oxides of nitrogen (NOX) emitted by the gas turbine engine during normal operation, demineralized water is injected into the combustor section of the gas turbine through the fuel nozzles. The demin water is delivered to the auxiliary trailer at the following conditions: •28 gpm (106 LPM) •15 psig (103 kPag) •Filtered to 10 micron

On the auxiliary trailer, the demin water passes through the following: •A 10 micron basket strainer •A positive displacement gear type pump •A 10 micron y-strainer

The demin water is delivered to the main trailer at the following conditions: •33 gpm (125 LPM) •140°F (60°C) Max.

•800 psig (7584kPaG) F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 17

gGE Energy

TM2500+ Gen VI Package Familiarization

WATER INJECTION SYSTEM On the main trailer, the demin water then passes through: •A flow control valve •Two shut off valves •A flow transmitter •The secondary liquid fuel manifold •The secondary port of the fuel nozzles

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 18

gGE Energy

TM2500+ Gen VI Package Familiarization

Water Injection Pump

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 19

gGE Energy

TM2500+ Gen VI Package Familiarization

Water Injection Pump

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 20

gGE Energy

TM2500+ Gen VI Package Familiarization

Water Injection Flow Control Valve

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 21

gGE Energy

F-025-10-20-306-00

TM2500+ Gen VI Package Familiarization

TM2500+ Dual Fuel System

Slide 22

gGE Energy

TM2500+ Gen VI Package Familiarization

Gas Purge When running on natural gas, fuel gas is used to purge the primary and secondary liquid fuel manifolds and nozzles. Gas is bled from the fuel system downstream of shut-off valve FSV-2004 through a 3/4” line where it passes through a check valve and enters the feed lines to either the primary or secondary liquid fuel manifold. SOV-2013 can stop purge gas from entering the secondary manifold if water injection is to be used for NOX abatement.

***NOTE*** - During operation, fuel supply can be transferred from gas to LQ or LQ to gas at full load if the permissives are met. The process takes approx. 20 seconds for full transfer. Exhaust Collector Drain Significant amounts of flammable liquids and water wash solution may accumulate in the turbine exhaust collector. The exhaust collector drain system eliminates these accumulations to ensure safe starts. During operation, air pressure to close FCV-2005 comes from the 9th-stage bleed-air manifold and, as turbine speed increases, positive pressure developed in the exhaust collector forces the condensate accumulations out through FCV-2005, a check valve, and the fuel drain valve to customer connection [7]. As the turbine speed continues to increase, 9th-stage bleed air increases. When the pressure rises to 50 psig, FCV-2005 closes. The collector drain remains closed during normal operation.

F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 23

gGE Energy

TM2500+ Gen VI Package Familiarization

Exhaust Drain Valve F-025-10-20-306-00

TM2500+ Dual Fuel System

Slide 24

gGE Energy

F-025-10-20-306-00

TM2500+ Gen VI Package Familiarization

TM2500+ Dual Fuel System

Slide 25

gGE Energy

F-025-10-20-306-00

TM2500+ Gen VI Package Familiarization

TM2500+ Dual Fuel System

Slide 26

gGE Energy

F-025-10-20-306-00

TM2500+ Gen VI Package Familiarization

TM2500+ Dual Fuel System

Slide 27

Tab 8

gGE Energy

TM2500+ Gen VI Package Familiarization

TM2500+ VENTILATION and COMBUSTION AIR SYSTEM

F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 1

gGE Energy

TM2500+ Gen VI Package Familiarization

COMBUSTION AND VENTILATION AIR SYSTEM (Refer to F&ID xxxxxxx-751239 Ventilation and Combustion Air System) The combustion and ventilation air system of the MGTG (mobile gas turbine generator) set supplies filtered combustion air for turbine engine operation, filtered ventilation air for the turbine enclosure, and filtered ventilation air for the generator. The air filter module supplies clean combustion air to the gas turbine and clean ventilation air to the turbine enclosure, and the generator is equipped with a separate ventilation system that includes inlet filters, exhaust silencer, and pressure and temperature sensors.

Turbine Enclosure and Combustion Airflow Gas turbine engine suction draws clean, filtered air through the air filter for turbine combustion, while ventilation fans force clean, filtered air through the turbine enclosure. Airflow is in two separate streams:

Combustion air flows through a plenum and an FOD screen to the gas turbine engine. Combustion airflow, at a nominal rate of 150,000 scfm (4248 scmm), enters the turbine engine where it is mixed with fuel and burned in the combustor. Ventilation airflow drawn by the ventilation fans at a nominal rate of 17,500 scfm (496 scmm), enters the turbine compartment where it circulates around and cools mechanical components. Two ventilation fans are provided, one active and one on standby. Ventilation air, having exchanged heat with the mechanical components, is drawn out through the enclosure wall and expelled through the exhaust assembly. The control system activates differential pressure alarm PDAL-4007 when pressure differential reaches 0.1” (2.5 mm) Wg increasing/decreasing (determines eductor or fan mode).

F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 2

gGE Energy

F-025-10-20-401-00

TM2500+ Gen VI Package Familiarization

TM2500+ Ventilation and Combustion Air System

Slide 3

gGE Energy

TM2500+ Gen VI Package Familiarization

Combustion Air

Ventilation Air

F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 4

gGE Energy

TM2500+ Gen VI Package Familiarization

Filtration The guard filter is an disposable filter utilized to catch a majority of the airborne contaminates which will prolong the life of the more expensive barrier filters. When differential pressure increases to an alarm state, the filter assembly will be replaced and the old filter disposed. Barrier filters (high efficiency filter) consist of a minipleat element. All units will have barrier filters as these are the primary filter for the unit. F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 5

gGE Energy

TM2500+ Gen VI Package Familiarization

FOD Screen This screen is the “last chance” filtration of the combustion air before it enters the engine and it is designed to catch any small foreign objects. The screen is supported by a stainless steel mesh across the inlet bell mouth and is rated at 1200 micron. F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 6

gGE Energy

TM2500+ Gen VI Package Familiarization

Fire Dampers The ventilation fans have CO2 activated dampers that close in the event of fire. Should a fire occur these dampers automatically seal the turbine enclosure, thereby eliminating the oxygen required for combustion. Sensors ZSC-4266A and ZSC-4266B monitor ventilation damper position, and initiate an alarm in the closed position. A bypass damper is provided to increase flow area so that an eductor can pull more air when the ventilation fans are turned off. Both the bypass dampers and the filter dampers are used while operating in eductor mode F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 7

gGE Energy

TM2500+ Gen VI Package Familiarization

Ventilation Air F-025-10-20-401-00

Combustion Air TM2500+ Ventilation and Combustion Air System

Slide 8

gGE Energy

F-025-10-20-401-00

TM2500+ Gen VI Package Familiarization

TM2500+ Ventilation and Combustion Air System

Slide 9

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Ventilation Airflow The generator rotor is equipped with fan blades to produce a flow of cooling air through the interior of the generator. The blades draw cool, filtered ambient air into the generator and circulate it around internal parts before expelling the now heated air through the top-mounted silencer and generator hood. Space heaters are provided in the base of the generator and the exciter. These heaters are turned on when ever the machine is un-excited so that any condensation on the windings and exciter parts can be prevented. F-025-10-20-401-00

TM2500+ Ventilation and Combustion Air System

Slide 10

gGE Energy

F-025-10-20-401-00

TM2500+ Gen VI Package Familiarization

TM2500+ Ventilation and Combustion Air System

Slide 11

gGE Energy

F-025-10-20-401-00

TM2500+ Gen VI Package Familiarization

TM2500+ Ventilation and Combustion Air System

Slide 12

Tab 9

g

GE Energy

TM2500+ Gen VI Package Familiarization

TM2500+ WATER WASH SYSTEM

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 1

g

GE Energy

TM2500+ Gen VI Package Familiarization

THEORY OF OPERATION The water wash system provides a mechanism for cleaning engine compressor blades to increase compressor efficiency and improve engine power output versus fuel burned. There are many types of compressor fouling. The type and rate of fouling depend on the environment in which the gas turbine operates and the type of inlet filtration. Among the most common types of contaminants are: Ø

Dirt or soil

Ø

Sand

Ø

Coal dust

Ø

Insects

Ø

Salt (Corrosion)

Ø

Oil

Ø

Turbine exhaust gas

Salt, aside from being a contaminant by itself, also causes corrosion of blading and ductwork and subsequent ingestion of rust and scale. Oil increases the ability of contaminants to cling to compressor passages and airfoils. The type of material that is deposited on the compressor blading influences the method of its removal. In other words, some material will respond to one cleaning media, others to another. Keeping the compressor internals clean can alleviate a number of problems before they ever become apparent. Besides the obvious benefits of enhanced efficiency (increased power output, lower T-3 temperatures, etc.), keeping the HPC clean will help blades survive longer. If the compressor is dirty, additional weight is added to the airfoil and this increases the cyclic stress. Performing thorough water washes with high quality ingredients on a regular basis with help combat these conditions.

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 2

g

GE Energy

TM2500+ Gen VI Package Familiarization

Methods of Detection

•Visual •Performance Monitoring

VISUAL INSPECTION The best method for detecting a fouled compressor is visual inspection. This involves shutting the unit down, removing the inlet plenum inspection hatch, and visually inspecting the compressor inlet, bellmouth, inlet guide vanes, and early stage blading. If there are any deposits, including dust or oily deposits that can be wiped or scraped off these areas, the compressor is fouled sufficiently to affect performance. The initial inspection reveals whether the deposits are oily or dry. For oily deposits, a water-detergent wash is required, followed by clean water rinses. The source of the oil should be located and corrected before cleaning to prevent recurrence of the fouling.

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 3

g

GE Energy

TM2500+ Gen VI Package Familiarization

PERFORMANCE MONITORING A second method for detecting a fouled compressor is performance monitoring. Performance monitoring involves obtaining gas turbine data on a routine basis, which in turn is compared to baseline data to monitor trends in the performance of the gas turbine.

The performance data is obtained by running the unit at a steady base load and recording output, exhaust temperatures, inlet air temperatures, barometric pressure, compressor discharge pressure and temperature, and fuel consumption. The data should be taken carefully with the unit warmed up. If performance analysis indicates compressor fouling, it should be verified by a visual inspection.

Washing and rinsing solutions are mixed in a holding reservoir and pumped into nozzle rings in the engine air inlet under controlled pressure and flow rates for optimum cleaning. Operators are responsible for charging the reservoir and initiating the washing and rinsing cycles. Software logic then operates the valve controls and a local Start switch will operate the pump, based upon operator mode selections and engine safety permissives.

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 4

g

GE Energy

TM2500+ Gen VI Package Familiarization

Water Wash System Components Water wash system components on the main trailer consist of a filter, manifold, and spray nozzles. Water wash system components on the auxiliary trailer consist of a tank, pump, instruments and controls. The water wash tank has a 55 gal (208 L) capacity and receives water and chemical concentrate through customer inlet. The tank is made of polyethylene and designed to withstand temperatures of -20 to180 ºF (82 ºC). The pump is driven by a dual rated 400/460 VAC, 50/60 HZ motor. Pressure on the discharge side of the pump is monitored by pressure indicator PI-5038. During offline water wash, water is delivered to the turbine at 15 GPM (57 LPM) and 75 PSIG (517 kPaG).

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 5

g

GE Energy

TM2500+ Gen VI Package Familiarization

Water Wash Tank

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 6

g

GE Energy

TM2500+ Gen VI Package Familiarization

Water Wash Pump

Water Wash Local Start Button

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 7

g

GE Energy

TM2500+ Gen VI Package Familiarization

Off – Line Water Wash Supply

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 8

g

GE Energy

TM2500+ Gen VI Package Familiarization

OFF-LINE WASH Uses de-min water/detergent solution * T48 average must be < 200 qF (93 qC) Remove the following sensor lines on the engine as close to the sensing point as possible. Tape off, with non-residue tape, the sensor side of the line. Ø P2 High Pressure Compressor Inlet Pressure

Ø Ps3 High Pressure Compressor Discharge Pressure Ø P4.8 Low Pressure Turbine Inlet Pressure Ø PTB Power Turbine Thrust Balance Pressure Ø HP Recoup

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 9

g

GE Energy

TM2500+ Gen VI Package Familiarization

P2/T2

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 10

g

GE Energy

TM2500+ Gen VI Package Familiarization

Ps3 F-025-10-20-501-00

TM2500+ Water Wash System

Slide 11

g

GE Energy

TM2500+ Gen VI Package Familiarization

HP Recoup – There are two HP Recoup lines on the engine, but only one sensor line

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 12

g

GE Energy

TM2500+ Gen VI Package Familiarization

P4.8

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 13

g

GE Energy

TM2500+ Gen VI Package Familiarization

PTB

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 14

g

GE Energy

TM2500+ Gen VI Package Familiarization

NOTICE THE BALL VALVE ON THE TANK DRAIN LINE IS NORMALLY CLOSED DURING NON-WASH CYCLES. SOLENOID-ACTIVATED VALVE SOV-5032 ADMITS OFF-LINE WASH SOLUTION TO TURBINE INLET PORT S1. OFF-LINE WATER WASH MAY NOT BE INITIATED UNTIL GAS TURBINE SURFACE TEMPERATURES ARE LESS THAN 200 qF (93.3 °C).

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 15

g

GE Energy

TM2500+ Gen VI Package Familiarization

Description of Water Wash Operation The customer supplies the recommended amount of chemical concentrate (solvent) through the soap and water fill funnel and the recommended amount of water through the water inlet on the auxiliary trailer. The normal recommended chemical to water mixture is 1:4 (1 part chemical and 4 parts water), but this can change with different soap vendors. After start-permissives have been satisfied (tank level and turbine temperature), the water wash system is started at the local control box on the auxiliary trailer. Fluid from the solvent and rinse tank passes through a 100-mesh strainer before entering the intake of the motordriven pump. Pump discharge is regulated by a flow-regulating valve, then passed through flow and pressure indicator gauges and solenoid valve SOV-5032 before its routed to the turbine inlet port S1. Tank level transmitter LT-5042 monitors liquid level in the tank and forwards a 4-2- mA signal to the turbine control system. LT-5042 also provides a water wash pump start permissive. The control system initiates a pump shutdown if the level lowers to within 2" (51 mm) of the bottom of the tank. Solenoid-activated valve SOV-5032 admits wash solution to turbine inlet port S1 at a regulated 15 GPM (57 LPM) through a 40 micron filter. Wash cycles last approximately 10 minutes and, during rinsing, rinse water temperature should range between 150 °F (66 °C) and 180 °F (82 °C). After rinsing, drain and clear the tank prior to the next water washing. ***NOTE***: If the outside air temperature is < 50 °F (10 °C), the customer must add antifreeze for engine protection during cold-weather washing. F-025-10-20-501-00

TM2500+ Water Wash System

Slide 16

g

GE Energy

TM2500+ Gen VI Package Familiarization

The off-line water wash (referred to as a crank-soak wash) consists of the following cycles: ·

Wash

- When the local start button is depressed, the hydraulic starter is energized and NGG is taken up to 1200 rpm where the starter will then de-energize until NGG coasts to below 200 rpm. The starter is then re-engaged, and NGG is taken back up to 1200 rpm where the starter is deenergized again, and this cycle continues until the wash tank is empty. The sequencing is all automatic and the water wash pump will engage when the hydraulic starter first engages. To stop the sequence, press the local start button a second time. ·

Soak - Allow the engine to soak for a minimum of 10 minutes.

·

Rinse - This is the same as the wash sequence, only without detergent. Typically, a wash would take 2 rinses, but this can vary with detergent vendors. Rinsing is complete when there are no bubbles coming from the exhaust drain at customer connection [7] .

·

Purge - Run the pump dry for several minutes to purge the water wash piping/manifold.

·

Dry - Within 30 minutes of completing the wash/rinse cycle, start the engine and run at idle for 5 minutes. If engine operation is prohibited during this period, motor engine for minimum 5 minutes.

F-025-10-20-501-00

TM2500+ Water Wash System

Slide 17

g

GE Energy

F-025-10-20-501-00

TM2500+ Gen VI Package Familiarization

TM2500+ Water Wash System

Slide 18

Tab 10

gGE Energy

TM2500+ Gen VI Package Familiarization

LM2500+ VIBRATION MONITORING SYSTEM

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 1

gGE Energy

TM2500+ Gen VI Package Familiarization

2

3

4

5

6

7

8

9

GEN.

10

12

13

GAS & FIRE

11

GEN. OPTICALS

TURBINE OPTICALS

AGENT RELEASE

AGENT RELEASE

BLOCK VALVE

ALARM MODULE

INPUT MODULE

INPUT MODULE

RELEASE MODULE

MANUAL PULL

FAULT MODULE

TURBINE

GAS MODULE

GAS MODULE

NT420 % LFL

NT420 % LFL

GAS MODULE NT420 % LFL

SET RESET

STEP

SET RESET

STEP

SET RESET

HIHI ALARM HI ALARM

HIHI ALARM HI ALARM

HIHI ALARM HI ALARM

LO ALARM

LO ALARM

LO ALARM

FAIL

FAIL

FAIL

FIRE 1

FIRE 1

HORN

FIRE 2

FIRE 2

STROBE

FIRE 3

FIRE 3

FAULT 2

FAULT 1 FAULT 2

FAULT 1 FAULT 2

FAULT 3

FAULT 3

FAULT 3

R E S E

I N H I B I T

R E S E T

T

GAS ALARMS

FIRE

SYSTEM ALARMS

HEAT DETS

I N H I B I T

HIHI ALARM HI ALARM

R

LO ALARM

E

FAIL

S E

FAULT 2

FAULT

SET RESET

STEP

4

S I L E N C E

17

AUX =

NT420 % LFL

BELL

FAULT 1 STEP

15 16

14

FAULT 3 FAULT 3

I N H I B I T

8

R

R

E

E

S

S

E

E

T

T

T

TURBINE PRESSURE MANUAL VOTING SWITCH PULL

SYSTEM FAULTS

TERMINATION CUBICLE

1 18

NGG & NPT

19

20

21

22 23 24 25 26

27 28

29

30

31

32

33

34

35

3500

3500

G-29-03

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 2

gGE Energy

TM2500+ Gen VI Package Familiarization

VIBRATION MONITORING The vibration monitoring system for the turbine engine generator consists of sensing elements for monitoring the turbine and generator vibration during operation. These sensing elements transmit vibration signals to the TCP. For General Electric transducer-mounting arrangement, refer to GE publication GEK-97310, Operation and Maintenance Manual for General Electric LM2500 60Hz Series Gas Generators and Gas Turbines. The sensors for the vibration system consist of accelerometers that monitor turbine-casing vibration and proximitors monitoring generator-bearing vibration. Sensors also monitor the high and low rotor speeds. Accelerometers on the CRF and on the TRF monitor turbine vibration. An accelerometer interface module for each accelerometer conditions the accelerometer output signals for application to the monitor unit in the TCP. Proximitors, with shaft proximity probes, monitor shaft vibration at the generator’s drive and exciter ends.

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 3

gGE Energy

TM2500+ Gen VI Package Familiarization

ACCELEROMETER

ACCELEROMETER OPERATION F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 4

gGE Energy

TM2500+ Gen VI Package Familiarization

Accelerometer Theory of Operation In the study of physical systems, it is often desirable to observe the motion of a system and, in particular, its acceleration. An accelerometer can be described as a combination of the two transducers – the primary transducer, typically a single degree of freedom vibrating mass, or seismic mass, which converts the acceleration into displacement, and a secondary transducer which converts the displacement of the seismic mass into an electric signal. As the accelerometer reacts to motion, it places the piezoelectric crystal into compression or tension, which causes a surface charge to develop on the crystal. The charge is proportional to the displacement of the crystal. As the large body moves, the mass of the accelerometer will move with an inertial response. The piezoelectric crystal acts as the spring to provide a resisting force and damping. As the seismic mass moves, it places a piezoelectric crystal into compression or tension, which causes a surface charge to develop on the crystal, which is proportional to the motion.

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 5

gGE Energy

TM2500+ Gen VI Package Familiarization

CRF ACCELEROMETER

F-025-10-20-701-00

TRF ACCELEROMETER

LM2500+ Vibration Monitoring System

Slide 6

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Bearing Proximitors F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 7

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Bearing Proximitors Proximitors are installed on the drive and non-drive ends of the generator drive shaft bearing housings, to measure displacement between the bearing housings and the generator shaft. Two proximitors are mounted on each bearing housing perpendicular to the shaft axis and displaced 90q radially. The proximitors are referred to as x and y and mounted on both drive and non-drive ends of the generator. Displacement measurements from the four proximitors are displayed on modules installed in rack slots 7 and 8 as follows: •Drive end x

•Drive end y •Non-drive end x •Non-drive end y

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 8

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Bearing Proximitors (DE)

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 9

gGE Energy

F-025-10-20-701-00

TM2500+ Gen VI Package Familiarization

LM2500+ Vibration Monitoring System

Slide 10

gGE Energy

F-025-10-20-701-00

TM2500+ Gen VI Package Familiarization

LM2500+ Vibration Monitoring System

Slide 11

gGE Energy

TM2500+ Gen VI Package Familiarization

BENTLEY 3500 RACK F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 12

gGE Energy

TM2500+ Gen VI Package Familiarization

VIBRATION MONITORING SYSTEM

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 13

gGE Energy

TM2500+ Gen VI Package Familiarization

VIBRATION MONITORING SYSTEM 1.

Low Voltage DC Power Supply / Future Expansion: Operates under fully loaded conditions with a single power supply. When two power supplies are installed in a rack, the supply in the lower slot acts as the primary supply and the supply in the upper slot acts as the backup supply. If the primary supply fails, the backup supply will provide power to the rack without interrupting rack operation.

2.

Rack Interface Module: Primary interface that supports Bently-Nevada proprietary protocol used to configure the rack and retrieve machinery information. The rack interface module provides the connections needed to support current Bently-Nevada Communications Processors and Dynamic Data Interface External.

3.

Communications Gateway Module: Provides serial communications between the 3500 Monitor System and a plant information system such as a distributed control system (DCS) or a programmable logic controller (PLC). Collects data from the modules in the rack over a high-speed internal network and sends this data to the information system upon request. The module is able to establish communications with up to six hosts over Ethernet.

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 14

gGE Energy

TM2500+ Gen VI Package Familiarization

4.

Aero GT Vibration Monitor: 4-channel monitor that accepts input from four Velocity Transducers and uses these inputs to drive alarms. The monitor can be programmed using the 3500 Rack Configuration Software to execute any filter options.

5.

Keyphasor Module: 2-channel module used to provide Keyphasor signals to the monitor modules. The module receives input signals from proximity probes or magnetic pickups and converts the signals to digital Keyphasor signals that indicate when the Keyphasor mark on the shaft is under the Keyphasor Probe. A Keyphasor signal is a digital timing signal that is used by monitor modules and external diagnostic equipment to measure vector parameters like 1x amplitude and phase.

6.

Proximitor Monitor: 4-channel module that accepts input from proximity transducers, linear variable differential transformers (DC & AC LVDTs), and rotary potentiometers and uses this input to drive alarms. It is programmed by using the 3500 Rack Configuration Software to perform any of the following functions: Thrust Position, Differential Expansion, Ramp Differential Expansion, Complementary Input Differential Expansion, Case Expansion, and Valve Position.

F-025-10-20-701-00

LM2500+ Vibration Monitoring System

Slide 15

gGE Energy

TM2500+ Gen VI Package Familiarization

7.

Future Expansion

8.

4 Channel Relay Module: Contains four relay outputs. Each relay output is fully programmable using AND and OR voting. The Alarm Drive Logic for each relay channel can use alarming inputs (alerts and dangers) from any monitor channel in the rack. The Alarm Drive Logic is programmed using the Rack Configuration Software.

9.

Dynamic Pressure Monitor: Single slot, 4- channel monitor that accepts input from various high temperature pressure transducers and uses this input to drive alarms. The monitor has one proportional value per channel, bandpass dynamic pressure. The bandpass corner frequencies are configured using the 3500 Rack Configuration Software along with an additional notch filter.

10.

- 16.

F-025-10-20-701-00

Future Expansion

LM2500+ Vibration Monitoring System

Slide 16

Tab 11

g

GE Energy

TM2500+ Gen VI Package Familiarization

FIRE and GAS DETECTION SYSTEM

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 1

g

GE Energy

TM2500+ Gen VI Package Familiarization

FIRE PROTECTION SYSTEM THEORY OF OPERATION The Fire and Gas Detection System is an independently powered, stand-alone system. A controller at the turbine control panel (TCP) provides audible and visual alarm signals. The panel referred to as the Fire Protection Panel (FPP), interfaces with the turbine-control system to initiate operator alarms and cause turbine-engine shutdowns when conditions warrant. Ventilation fan controls are also directed through the turbine-control system interface when fire or fire-causing conditions are detected. Because of its importance to the system while running, and in Standby or Static state, the Allestec Fire Protection system performs a routine “system check” every 36 hours. At time of initial power-up, the FPP sets an internal watchdog timer that initiates a status check at 36hour intervals. During this period the system looks at each circuit run to the manual switches, heat sensors, gas detectors, pressure switches and battery charger system to verify proper operating parameters of the external components. If a device is not functioning properly, or if the system detects a loss of circuit continuity, an alarm will be annunciated and displayed on the Operator’s Alarm and Shutdown screen on the HMI.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 2

g

GE Energy

TM2500+ Gen VI Package Familiarization

Fire Protection Panel

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 3

g

GE Energy

TM2500+ Gen VI Package Familiarization

FIRE PROTECTION SYSTEM THEORY OF OPERATION The fire protection system utilizes thermal spot detectors and gas sensors in the turbine enclosure to detect fire, or fire-causing conditions. In the case of a fire, an emergency shutdown is initiated and fuel flow to the turbine engine is terminated. The compartment-ventilating fans de-energize and the solenoidoperated valves open to release the fire-extinguishing agent. Pressure from CO2 in the release lines activates pneumatic actuators, pulling pins that allow weights to fall, thus closing louvers (fire dampers) in the ventilation ducts. These fire dampers reduce the supply of oxygen and confine CO2 within the enclosures for maximum effect. When an alarm input is received, the control panel energizes a timer to start a time-delay sequence that allows the operator to evacuate the main skid area before the extinguishing agent is released. A red emergency push button station has been provided outside the doors to the engine compartment for manually initiating alarms and releasing the fire-extinguishing agent. The fire suppression and gas detection system is interlocked with the turbine vent fans and shuts down these fans to confine the fire within the compartment. Similarly, when the gas accumulation exceeds the pre-set low explosion level (LEL), a series of events takes place. The dampers remain open and the standby fan activates in order to increase compartment ventilation and expel the gas from the compartments to the atmosphere; fuel flow continues. When the sensors detect a high explosion level (HEL) of gas accumulation, fuel flow is stopped, the dampers remain open, and the standby fan activates to expel the gas from the compartment if not already in service.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 4

g

GE Energy

Thermal Spot Detector

TM2500+ Gen VI Package Familiarization

Control Panel

Cylinders of Inert Gas

Manual Discharge Switch

Discharge Nozzles

Gas Detector

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 5

g

GE Energy

TM2500+ Gen VI Package Familiarization

FIRE-EXTINGUISHING AGENT CO2 is used as the extinguishing agent for the main skid. The system’s CO2 is stored in two sets of bottles, main and reserve, outside the engine compartment. The CO2 bottles have been provided with solenoidoperated discharge heads. A check valve on each tank ensures the activation of one tank at a time. There is no level indicator on these bottles! They need to be weighed every six months minimum. Full weight is 300 lbs.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 6

g

GE Energy

F-025-10-20-801-00

TM2500+ Gen VI Package Familiarization

TM2500+ Fire and Gas Detection System

Slide 7

g

GE Energy

TM2500+ Gen VI Package Familiarization

CO2 MANUAL BLOCK VALVES Manual operated valves located on the discharge side of the CO2 bottles. Utilized when accessing the enclosure to ensure no accidentally CO2 release in the module. The valves have an electronic position feedback to the fire protection panel. In the closed position, release of CO2 is inhibited.

***NOTE***

- Except during an actual response to a fire Alarm/Shutdown condition, if the system initiates a 36-hour status check, any condition, such as a manual inhibit mode, will be reset! Operators should utilize the use of the manual shutoff valve ZS-6364 located in the CO2 enclosure when doing a quick internal package inspection. Situation could arise while in an inhibit-only mode to perform an inspection, system could initiate the 36-hour check and reset inhibit status. System does not indicate that the FPP panel is

performing this diagnostic function! F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 8

g

GE Energy

TM2500+ Gen VI Package Familiarization COMBUSTIBLE GAS DETECTORS Inside the turbine enclosure, combustible gas is detected by five dual-element sensors. The dual elements, one of which is exposed to the local atmosphere and one of which is sealed, are balanced to cancel the effects of temperature, aging, and humidity. An unbalance occurs when gas affects the electrical conductivity of the exposed element.

Alarm @ 15% LEL (Increasing) - Both enclosure fans ordered on Shutdown (FSLO) @ 25% LEL (Increasing) - Both enclosure fans stay on

GT ENCLOSURE EXHAUST GAS DETECTORS Combustible gas monitors may also be mounted in each of the GT enclosure fan ventilation exhaust ducts. Alarm @ 5% LEL (Increasing) - Both enclosure fans ordered on

Shutdown (FSLO) @ 10% LEL (Increasing) - Both enclosure fans stay on

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 9

g

GE Energy

TM2500+ Gen VI Package Familiarization

THERMAL SPOT DETECTORS Two thermal spot detectors, located in the turbine enclosure, monitor temperatures and signal the fire control modules when the temperature reaches 450 qF (232qC).

FIRE DAMPERS (2) Each gas turbine ventilation fan has a fire damper on the inlet side of the fan that will isolate the enclosure in case of fire. The dampers are counter weighted to the close position, but are normally locked open by a mechanical actuation pin assembly. When the control system initiates a fire stop, CO2 is released to the enclosures and a portion of this CO2 releases the actuation pin assemblies and the counter weights will close the damper.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 10

g

GE Energy

TM2500+ Gen VI Package Familiarization

ALARM HORNS Alarm horns, inside and outside the enclosure, will sound if fire is detected. CO2 is released 30 seconds after the alarm horns sound. A manual switch is provided as a “Horn Acknowledge” mute switch.

STROBE LIGHTS Strobe lights, inside and outside the enclosure, emit a bright, flashing red light whenever the fire suppression system has been activated.

***NOTE***

- Strobe lights activate with the initialization of the FPP panel. The strobe latch-in relay is armed when a shutdown condition occurs and the fan latched-out relays are armed (CO2 discharged). In the condition where high LEL initiates a shutdown, the strobe latch-in relays are armed. The strobes cannot be turned off until the key-operated CO2 purge switch is activated and fan logic reset.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 11

g

GE Energy

TM2500+ Gen VI Package Familiarization

HORN SILENCE KEY SWITCH Key switch utilized to silence the internal and external horns during fire incidents. Silencing the horn will not de-energize the strobe lights. Usually located beneath an external horn.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 12

g

GE Energy

TM2500+ Gen VI Package Familiarization

CO2 PURGE SWITCH The CO2 Purge Switch is a key-lock switch that is actuated in order to open fire dampers, enable ventilation fan operation and turn off strobe lights after the fire is determined to be out. This is located next to the CO2 skid.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 13

g

GE Energy

TM2500+ Gen VI Package Familiarization

MANUAL CO2 RELEASE STATIONS Manual release stations permit manual activation of the fire suppression system. Once activated, there is no stopping the sequence.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 14

g

GE Energy

TM2500+ Gen VI Package Familiarization

CO2 BOTTLE RELEASE VALVE (CONTROL HEAD)

SOLENOID

One solenoid operated release valve is mounted in each of the banks of bottles (Main and Reserve). CO2 system may be manually actuated with the solenoid valve. Resetting the valve is completed manually with a screw driver.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 15

g

GE Energy

TM2500+ Gen VI Package Familiarization

CO2 RELEASE PRESSURE SWITCHES The pressure switches are located on the discharge of the CO2 bottles, downstream of the manual block valve. One switch is activated upon discharge of the main bank of CO2. If the main bank is released and the switch is not activated, the controller will release the reserve bank. If CO2 is released manually, activation of the switch will result in a FSLO shutdown of the generator set. Set at 150 psig (1035 kPaG) - FSLO shutdown. CO2 is discharged upon the activation of dry-line discharge pressure switch PSHH-3048 typically set to 150 psig (1034 kPaG) increasing. If pressure in the line reaches 150 psig (1034 kPaG), a shutdown will be initiated. CO2 activation produces a signal at the fire protection panel that is relayed to the sequencer. The sequencer then initiates an orderly FSLO.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 16

g

GE Energy

F-025-10-20-801-00

TM2500+ Gen VI Package Familiarization

TM2500+ Fire and Gas Detection System

Slide 17

g

GE Energy

F-025-10-20-801-00

TM2500+ Gen VI Package Familiarization

TM2500+ Fire and Gas Detection System

Slide 18

g

GE Energy

TM2500+ Gen VI Package Familiarization

FIRE PROTECTION PANEL

The Fire Protection Panel illustrated above is comprised of plug-in modules that link to thermal and gas detection sensors inside the turbine enclosure. The FPP also contains Alarm, Release, Manual Pull, and Fault modules that provide activation of CO2 release solenoids and annunciation of operating conditions. The function of the individual modules is as described on the following pages. ***NOTE*** - The fire detection panel has a reset button that enables it to be returned to its standby configuration after being tripped. ***NOTE*** - Unlike most modular control systems, the “slots” within the Fire Protection System cardframe are numbered from right to left. Thus, for reference, the module in slot number 1 is located at the far right hand end of the cardframe, when viewed from the front of the control panel. F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 19

g

GE Energy

TM2500+ Gen VI Package Familiarization

FAULT MODULE The Fault module assists operators in identifying fault categories and provides a mechanism for resetting the audible fault horn. The Power LED indicates low battery supply voltage. The AUX LED is not used in the system as presently configured. Faults are also displayed locally on each plug-in module type. 1. System – Amber indicator illuminates when a fault in any module in the system is present. 2. Battery Voltage – Green indicator illuminates should the battery power rise to approximately 30V or fall to approximately 18V. 3. Aux – (Not Used) Amber indicator illuminates when normally closed circuit is open. . 4. Power LED – Green indicator illuminates when power is applied to the module. 5. Reset Switch – Toggle switch used to reset module and alarm conditions.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 20

g

GE Energy

TM2500+ Gen VI Package Familiarization

MANUAL PULL MODULE The Manual Pull module accepts inputs from manual pull switches located strategically around the GTG package and sets a latch, which activates the Alarm and Release modules. Operation of any of the manual pull switches also causes the Fire LED on the module front panel to energize. 1. Fire – Upon activation of a manual pull station, this LED will illuminate and audio and visual alarms will be activated. The release module will also be activated. 2. Fault – Amber indicator will illuminate when a circuit is open in the manual release input wiring and the alarm will be activated. 3. Power LED – Green indicator illuminates when power is applied to the module. 4. Inhibit/Reset – Toggle switch allows testing of the detectors while disabling the main and reserve banks of the release module.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 21

g

GE Energy

TM2500+ Gen VI Package Familiarization

RELEASE MODULE The release module activates CO2 release solenoids after pre-set time delays. Manual pull switches, high temperature detection, or flame detection will activate a 30-second timer in the Release module. Following the 30-second warning delay, the primary bank of CO2 bottles is released. At the time of release, 10-second and 90-second timers are initiated. If CO2 pressure is not sensed in the release lines when the 10-second timer elapses, the backup bottle bank is released. If flames continue to be detected when the 90-second timer elapses, the backup bottle bank is also released. 1. Main – Red indicator illuminates when CO2 is released from CO2 cylinders. 2. Reserve – Red indicator illuminates when CO2 is released from reserve CO2 cylinders.

3. Main – Amber indicator illuminates when an open conductor in the Main Release circuit is detected. 4. Reserve – Amber indicator illuminates when an open conductor in the Reserve Release circuit is detected. 5. PSW – Amber indicator illuminates when an open conductor in the Pressure Switch (PSW) line is detected.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 22

g

GE Energy

TM2500+ Gen VI Package Familiarization

RELEASE MODULE 6. Abort – Amber indicator will illuminate when an open conductor in the abort line is detected. 7. Power LED – Green indicator illuminates when power is applied to the module. 8. Inhibit/Reset Switch – Inhibit position inhibits release of CO2 while testing Input Module Alarms. Manual Pulls may still be used in normal manner while Inhibit function is selected. Reset position allows user to reset the fault circuit provided the condition causing the fault has been cleared.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 23

g

GE Energy

TM2500+ Gen VI Package Familiarization

INPUT MODULE The input module accepts inputs from two thermal sensor inputs. Two thermal inputs are wired in parallel from the turbine enclosure and, once activated by a sensor, the Input Module will initiate the Alarm Module. When reset with the spring-loaded Reset switch, the LEDs extinguish. Fault LEDs do not blink. To prevent nuisance alarms, adjustable time delays on the input module printed circuit cards determine the length of time sensor contacts must remain closed before being “captured” and presented as a valid signal. 1. Fire 1 – Red indicator illuminates as long as the detector remains in alarm. When the alarm clears, the LED will blink to indicate there has been a relay closure. The module can be reset when all alarms on this module have been cleared. 2. Fire 2 – Red indicator illuminates as long as the detector remains in alarm. When the alarm clears, the LED will blink to indicate there has been a relay closure. The module can be reset when all alarms on this module have been cleared. 3. Fire 3 – Red indicator illuminates as long as the detector remains in alarm. When the alarm clears, the LED will blink to indicate there has been a relay closure. The module can be reset when all alarms on this module have been cleared

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 24

g

GE Energy

TM2500+ Gen VI Package Familiarization

INPUT MODULE 4. Fault 1 – Amber indicator illuminates when there is a sensor contact open in No. 1 Fault Input circuit.

5. Fault 2 – Amber indicator illuminates when there is a sensor contact open in No. 2 Fault Input circuit. 6. Fault 3 – Amber indicator illuminates when there is a sensor contact open in No. 3 Fault Input circuit. 7. Power LED – Green indicator illuminates when power is applied to the module. 8. Reset Switch – Allows resetting the input module.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 25

g

GE Energy

TM2500+ Gen VI Package Familiarization

ALARM MODULE Note: The horn, strobe, and bell circuits are fused. Open fuses or continuity loss to the end devices will activate the associated Fault LEDs on the module front panel. The Input or Manual Pull modules activate the alarm module. When activated the Alarm Module will sound the annunci ation devices and turn on the strobe light 1. Bell – Red indicator illuminates when the Manual Pull via Release Module activates the Bell upon an alarm input from the Input Module. The LED will blink once the alarm has been silenced to indicate that it has been silenced. 2. Horn – Red indicator illuminates when the Manual Pull via Release Module activates the Horn upon an alarm input from the Input Module. The LED will blink once the alarm has been silenced to indicate that it has been silenced. 3. Strobe – Red indicator illuminates when the Manual Pull via Release Module activates the Strobe upon an alarm input from the Input Module. The LED will blink once the alarm has been silenced to indicate that it has been silenced. 4. Fault 1 – Amber indicator illuminates when there is a fault in the Bell circuit, and it flashes when the Silence switch has been operated. 5. Fault 2 – Amber indicator illuminates when there is a fault in the Horn circuit, and it flashes when the Silence switch has been operated.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 26

g

GE Energy

TM2500+ Gen VI Package Familiarization

ALARM MODULE 6. Fault 3 – Amber indicator when there is a fault in the strobe light circuit. 7. Power LED – Green indicator illuminates when power is applied to the module. 8. Silence/Reset Switch – The Silence function will silence the horn after which the Horn LED blinks until Reset is activated. The reset function extinguishes the Horn and Strobe LEDs. The Reset function is only permitted if the event causing the alarm is cleared.

F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 27

g

GE Energy

TM2500+ Gen VI Package Familiarization

GAS MODULE TURBINE ENCLOSURE Gas modules accept 4–20 mA analog signals from gas detectors in the turbine enclosure and display the values calibrated as a percentage of the lower explosion limit (LEL) of the gas-air mixture. To initiate programming, both the Step and Set Reset pushbuttons are pressed simultaneously. In normal operation, gas levels will be well below the Lo Alarm limit. Should the level increase to a value greater than the Lo or Hi Alarm limits, the respective LEDs will illuminate. The HiHi Alarm LED indicates a 100% LEL. 1. Display – Two seven-segment LEDs display the real-time concentration of gas level between 5 and 100% LEL, PPM, or percent of analog current loop. Displays also indicate “or” or “ur” for over or under range sensor inputs and programming information for setting alarm parameters. 2. Step – Switch used to increment program steps, and the selected values are stored in the memory with this switch. 3. Step/Reset – Switch used to enter and store values into the program mode. Also allows the operator to reset fault circuit. 4. Hi-Hi Alarm – Red LED illuminates when pre-set limit is exceeded. 5. Hi Alarm – Red LED illuminates when pre-set limit is exceeded. 6. Lo-Alarm – Amber LED illuminates when pre-set limit is exceeded. 7. Fail – Red LED illuminates when the module detects a sensor failure. F-025-10-20-801-00

TM2500+ Fire and Gas Detection System

Slide 28

Tab 12

gGE Energy

TM2500+ Gen VI Package Familiarization

TM2500+ GENERATOR CONSTRUCTION

TM2500+ Generator Construction F-025-10-30-100-00

Slide 1

gGE Energy

TM2500+ Gen VI Package Familiarization

BRUSH GENERATOR TM2500+ Generator Construction F-025-10-30-100-00

Slide 2

gGE Energy

TM2500+ Gen VI Package Familiarization

GENERATOR OVERVIEW The generator converts rotational shaft horsepower into electrical energy when driven by an LM2500 gas turbine prime mover. The generator is typically installed without an enclosure and there are various methods used to cool the air. The unit is bolted to the gas turbine-generator package main skid, such that the rotor is axially aligned with the power turbine. A flexible coupling through the engine exhaust connects the generator rotor to the power turbine shaft. The generator is characterized as a three-phase, two-pole brushless exciter type, with an open-circuit aircooling system. To avoid degraded performance under high-current loads or ambient temperatures, cooling has been a major consideration in the design of the generator. Bearings at the drive and non-drive ends support the rotor. The gross weight of the assembled generator is approximately 61 tons.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 3

gGE Energy

TM2500+ Gen VI Package Familiarization

1.

Stator Winding

2.

Stator Core

3.

Rotor

4.

Rotor Endcap

5.

Shaft Mounted Fan

6.

Bearing Oil Seal

7.

Exciter Cooling Air Duct

8.

Endframe Bearing

9.

Exciter Stator

10.

Rotating Diodes

11.

Exciter Rotor

12.

PMG

Brushless Generator Major Components TM2500+ Generator Construction F-025-10-30-100-00

Slide 4

gGE Energy

TM2500+ Gen VI Package Familiarization

MAJOR COMPONENTS 1. Stator Winding - High voltage coils are mounted in the generator frame. Rotor’s lines of force cut through these coils and create the generator’s output voltage. 2. Stator Core – Thin laminations of low-loss electrical steel are stacked together to form the generator core. The core concentrates the rotor’s magnetic flux in the stator coils and completes the path of the rotor’s magnetic loops. 3. Rotor – The rotor is a solid forging of nickel-chromium-molybdenum alloy steel. The rotor supports the field windings of solid copper bars. Current in the rotor windings creates magnetic flux around the rotor. This flux cuts the stator coils and produces the generator’s high-voltage output. 4. Rotor Endcaps – The rotor endcaps are non-magnetic steel. The endcaps cover and protect the end portions of the rotor windings. 5. Shaft-Mounted Fan(s) – Two fans (one on each end of the rotor) pull cooling air into the generator through top inlets at each end of the generator frame. The fans force the air over the rotor and core and out through the central top exhaust exit.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 5

gGE Energy

TM2500+ Gen VI Package Familiarization

6.

Pressure Oil Seals – Twin lube oil seals are mounted at the inner and outer edge of each bearing cavity. Air pressure from the shaft fans is inserted between the seals to contain the bearing lube oil.

7.

Exciter Cooling Air Duct – A fan on the exciter shaft pulls cooling air through this duct and forces the air over the exciter components.

8.

Endframe Bearing(s) – White-metal lined, hydrodynamic, cylindrical bearings support the rotor shaft at each end. These bearings require continuous lubrication while the rotor is turning.

9.

Exciter Stator – DC excitation current flows through these fixed stator coils, producing a magnetic field around the coils. The exciter rotor coils cut through this magnetic field, and a voltage is built in the rotating coils. Note: The energy is transferred to the rotating shaft without brushes, slip rings or physical contact.

10. Rotating Diodes – These diodes rectify the AC voltage in the Exciter Rotor Coils and produce DC current to energize the rotor main windings. 11. Exciter Rotor – A voltage is built in the Exciter Rotor coils when they cut through the magnetic flux of the Exciter Stator coils. This voltage is rectified by diodes, providing DC current to energize the main rotor windings. 12. Permanent Magnet Generator (PMG) – The flux from sixteen shaft-mounted permanent magnets cuts through the PMG stator coils and creates the AC utility voltage needed for excitation. TM2500+ Generator Construction F-025-10-30-100-00

Slide 6

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Frame The generator frame is a box-shaped weldment built of carbon steel plates. The frame is stiffened internally by web plates. These plates are aligned by “key bars” running parallel to the axis of the machine. The key bars support the stator core. After fabrication, the generator frame is machined on a large lathe. The lathe cuts an accurate cylinder along the axis and provides machined faces on each end for mounting the generator end pieces. TM2500+ Generator Construction F-025-10-30-100-00

Slide 7

gGE Energy

TM2500+ Gen VI Package Familiarization

Stator Winding Copper Bars

Main Rotor The rotor is machined from a single alloy-steel forging of tested metallurgical properties. Longitudinal slots are machined radially in the body in which the rotor windings are installed. The windings are secured against centrifugal force by steel wedges fitted into dovetail openings machined in the rotor slots. The coils are insulated from the slot walls by molded slot liners. Molded ring insulation is provided at the coil ends to separate and support the coils under thermal and rotational stresses. A centering ring held into place by shrink fit restricts axial movement. A single brush, spring-loaded against the rotor, carries stray ground currents from the rotor to the frame ground. The brush is located near the drive end of the main rotor.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 8

gGE Energy

TM2500+ Gen VI Package Familiarization

STATOR CORE COMPLETES MAGNETIC CIRCUIT AROUND ROTOR

LAMINATED CORE SUPPORTS STATOR COILS

Stator Core The stator core is built into a fabricated steel frame and consists of low-loss silicon, steel-segmented stampings insulated by a layer of varnish on both sides. The stampings are divided into short sections by radial-ventilating ducts extending from the center through to the outer ends. The stator windings are arranged in patterns to minimize circulating currents. Conducting tape between the windings and the machine frame provides Corona protection.

The stator core is a compressed stack of insulated, laminated steel strips. (The laminated construction reduces electrical losses in the core.) The stator core provides the “return path” to complete the rotor’s magnetic circuit. This concentrates the flux and produces more power in the stator coils. TM2500+ Generator Construction F-025-10-30-100-00

Slide 9

gGE Energy

PHASE & TERMINAL NUMBERS

TM2500+ Gen VI Package Familiarization

“WYE” CONNECTED PHASES

CUBICLES CONNECT GENERATOR TO SITE EQUIPMENT

Generator Terminals TM2500+ Generator Construction F-025-10-30-100-00

Slide 10

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Connections The generator has three stator coils, one per phase. Standard phase and terminal numbering is shown in “A” above. Three coil terminals extend through the left side of the generator housing, near the exciter end of the frame (T1,T2,T3), and three terminals extend through the right side of the generator housing (T4,T5,T6), as shown below. The generator connects to the site equipment through Lineside and Neutral Cubicles. These cubicles contain heavy busbars to transmit the generator voltage to the load. The cubicles are mounted on the generator at the site. The Lineside Cubicle can be mounted on either side of the generator to suit the customer’s layout. The Neutral Cubicle mounts on the side opposite from the Lineside Cubicle. In the Neutral Cubicle, three of the generator terminals are connected together by busbar, creating a Wye arrangement, as shown in “B” above. The common, or “Neutral”, point is connected to ground through a grounding transformer, as shown in “C” above.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 11

gGE Energy

TM2500+ Gen VI Package Familiarization

Lineside Cubicle The Lineside cubicle connects to the high-voltage output terminals of the generator. The customer then connects the Lineside cubicle to the generator circuit breaker (52G) with busbar or high voltage cables. Three sets of lightning arrestors and surge capacitors are mounted in the Lineside cubicle. These devices “short-circuit” lightning energy to ground and protect the generator if lightning should strike the grid.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 12

gGE Energy

TM2500+ Gen VI Package Familiarization Neutral Cubicle The Neutral cubicle connects to the side of the generator opposite the Lineside cubicle. Busbars in the Neutral cubicle connect three phases together to form the “neutral point” of the generator Wye connection. The neutral point connects to earth ground through the Neutral Grounding Transformer. The Neutral cubicle also contains three sets of current transformers. These transformers tell the control system how much current is flowing in each of the three phases of the generator. The control system uses these 0-5 Amp signals for metering and relaying.

Neutral Grounding Transformer The Neutral Grounding Transformer connects the neutral point of the generator’s Wye connection to ground. Grounding generators in this fashion provides a “common potential reference” for all the generators connected to a grid. This allows them to work smoothly in parallel. The Neutral Grounding Transformer also limits the maximum current flow from ground back into the generator if a “phase conductor” should accidentally fall to earth or become grounded TM2500+ Generator Construction F-025-10-30-100-00

Slide 13

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Drive-End Bearing TM2500+ Generator Construction F-025-10-30-100-00

Slide 14

gGE Energy

TM2500+ Gen VI Package Familiarization

GENERATOR BEARINGS A pressure-lubricated journal bearing supports the rotor at the drive and non-drive ends. Thrust pads are installed between the drive-end journal and the bearing, to prevent longitudinal loads that may be imposed upon the drive turbine. The bearings are supported in fabricated steel housings, which are bolted directly to the machine ends. The bearing housings are split on the horizontal shaft centerline with the lower half forming the bearing oil sump. The bearings are of plain cylindrical design, white metal lines, and spherically seated within the end frames. Oil under pressure is fed to the bearings and distributed over the bearing surface by internal grooves. On both the 60 Hz and 50HZ generators, there are two Lube Oil Pumps. One is a mechanically driven pump attached to the generator shaft at the exciter end, and there is an auxiliary DC Pump mounted to the generator lube oil tank. Orifices in each bearing supply lines controls the bearing oil flow. Drain oil discharges into the bottom of the bearing housing from where it is returned to the lube oil system.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 15

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Bearing Seal System Pressurized knife-edge oil seals are mounted on the inboard and outboard faces of the bearing housing. The outer chamber is supplied with pressurized air bled from the downstream side of the main generator fan. Pressurization prevents oil and oil vapor from flowing along the shaft and out of the bearing housing. TM2500+ Generator Construction F-025-10-30-100-00

Slide 16

gGE Energy

TM2500+ Gen VI Package Familiarization

Generator Airflow TM2500+ Generator Construction F-025-10-30-100-00

Slide 17

gGE Energy

TM2500+ Gen VI Package Familiarization

GENERATOR TEMPERATURE MONITORING Instrumentation installed within the generator by the generator manufacturer is as follows: Three resistance temperature detectors (RTD's) are embedded in each stator winding—one in each winding is a spare Four RTD's are installed in the air duct flow path—two are operational, two are spares (on water cooled generators they are used to monitor water temperatures)

Two RTD’s are embedded in the bearings, one on the generator drive end and one on the exciter end Two RTD’s are installed in the bearings oil supply drain flow, one on the generator drive end and one on the exciter end

TM2500+ Generator Construction F-025-10-30-100-00

Slide 18

gGE Energy

TM2500+ Gen VI Package Familiarization

Exciter Diode Wheel TM2500+ Generator Construction F-025-10-30-100-00

Slide 19

gGE Energy

TM2500+ Gen VI Package Familiarization

Exciter and Diode Assembly The exciter assembly consists of a permanent magnet generator (PMG), an exciter stator and rotor, and a rotating diode rectifier. These components are installed at the non-drive end of the generator shaft. The PMG stator consists of a single-phase winding in a laminated core. Twelve permanent magnets rotate on the rotor inside the stator. The PMG output AC voltage is rectified and regulated by the modular automatic voltage regulator (MAVR). The exciter stator, which receives the MAVR output DC voltage, is mounted around the exciter rotor. It consists of a stationary ring that supports the stator poles and carries the magnetic flux between adjacent poles. Stator windings are series-wound around laminated poles. The exciter rotor is constructed from punched laminations and contains resin- impregnated, form-wound, and three-phase windings. A rotating diode assembly rectifies the AC voltage induced into the exciter rotor.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 20

gGE Energy

TM2500+ Gen VI Package Familiarization

Exciter Diode Wiring The rectifier is a three-phase, full-wave bridge rectifier with parallel, individually fused diodes. The fuses are mounted on the reverse side of the diode assembly. The redundant diode configuration enables the exciter to carry full generator output with as many as half the diodes out of service. Because diodes have only two failure modes (shorted or open), the fuses provide over current protection and allow continued normal operation, unless two fuses open in any one of the six rectifier legs. A radio transmitter, powered by the rectifier DC voltage output, discontinues transmission, should a rotor ground fault occur. A stationary radio receiver generates an alarm, should the transmitter signal cease. Diode failure detection is accomplished by sensing ripple induced into the exciter field caused by the unbalanced load.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 21

gGE Energy

TM2500+ Gen VI Package Familiarization

Diode Failure Detection Twelve diodes, each with a fuse in series, are mounted in parallel pairs in a three-phase bridge. Six of the diodes has positive bases and are mounted on one heat sink, the remaining six have negative bases and are mounted on the other heat sink.

The risk of diode failure is very remote. However, if a diode does break down a heavy reverse current will flow which is interrupted by the fuse. The adjacent diode and fuse would then be called upon to carry the whole current that was previously divided between two parallel paths. Each path is designed with sufficient surplus capacity to carry the full current continuously. The generator will therefore continue running as if nothing had happen.

TM2500+ Generator Construction F-025-10-30-100-00

Slide 22

Tab 13

g

GE Energy

Basic Electricity and Generation

BASIC ELECTRICITY and GENERATION

F-000-00-60-001-00

Basic Electricity and Generation

Slide 1

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 2

g

GE Energy

Basic Electricity and Generation

INTRODUCTION TO ELECTRICITY All matter is composed of atoms that often arrange themselves into groups called molecules. The atom is composed of smaller particles separated by space. The center of the atom is the nucleus that contains various particles, including protons. These protons are said to have positive charge. The electrons, which complete the atomic structure, are said to orbit the nucleus and have a negative charge. Different atoms have different numbers of electrons, and atoms in their complete state have equal numbers of electrons and protons. In this structure, the positive and negative charges cancel out each other, leaving the atom electrically neutral. Consider the copper atom; notice the outer electron is farthest from the nucleus and subject to a smaller force of attraction than those electrons in the inner orbit. This electron is weakly held in position and often breaks free, moving at random among the other copper atoms. An atom that loses an electron in this way is left with an overall positive charge, since it has a positive proton in excess of those required to balance the effect of the negative electrons. Such an atom is called a positive ion.

Electrons in motion constitute electric current. By the laws of nature, opposites attract. If opposite-charged materials are connected electrically in some way, current will flow to the movement of electrons from negative to positive.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 3

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 4

g

GE Energy

Basic Electricity and Generation

ELECTRIC CURRENT IN A BLOCK

Consider a block of conducting material. Free electrons are moving at random among positive ions. If a battery is connected across the block, free electrons close to the positive plate will be attracted to it and free electrons near the negative plate will be repelled from it. A steady flow of electrons occurs from the negative battery terminal to the positive terminal. For each electron entering the positive terminal, one is ejected from the negative terminal, thus the total number of electrons in the material remains constant. VOLTAGE, CURRENT, AND RESISTANCE To consider the basic DC circuit we must introduce the notion of voltage. Consider our basic circuit, the battery connected across the piece of material. The reason there is current flow is because there is an excess of electrons at the negative terminal and a deficiency of them at the positive one. We say there is a difference in potential between the positive and the negative terminals, and we measure this potential difference in volts. Adopting the physical analogy to electricity, we can say the following: In order for electrons to move, a force must be applied. This force is called electromotive force (EMF) and is measured in volts.

In all conducting materials there is a resistance associated with electron movement. This is the electrical resistance and is measured in ohms.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 5

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 6

g

GE Energy

Basic Electricity and Generation

OHM’S LAW The conditions required to set up and maintain the flow of electric current are as follows: • There must be a source of EMF (battery or generator • There must be a continuous external path (circuit) for the current to flow in Consider the simple circuit shown on the previous page. When the switch is closed, a current will flow. The value of this current depends on the battery EMF (in volts) and the amount of resistance in the circuit. The relationship between EMF, current, and resistance is defined in the statement called Ohm’s law. The current flowing in a circuit is directly proportional to the applied voltage. EMF is inversely proportional to the resistance. We tend to express this relationship mathematically as follows: I=V/R I = Current (A) V = EMF (V) R = Resistance (R) This gives us the “magic triangle” from which is given two of the circuit parameters; we can deduce the remaining one.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 7

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 8

g

GE Energy

Basic Electricity and Generation

POWER To complete the definitions portion of this section, we need to consider power. We define power as the rate of doing work. Whenever a force of any kind causes motion, work is said to be done. A difference in potential between any two points in an electric circuit gives rise to a voltage, which causes electrons to move and current to flow. Thus, force causes motion and work is done. So whenever voltage causes electrons to move, work is done in moving them. The rate at which the work of moving electrons from point to point is done is called electrical power. The unit in which it is measured is the watt (W). It is defined as “the rate at which work is being done in a circuit in which a current of 1 ampere (A) is flowing when the EMF applied is 1 volt (V)”. In real terms, power is the rate at which electrical energy can be converted into useful forms of energy, such as heat or light. Electrical power is expressed in watts (W), kilowatts (kW), or megawatts (MW). One horsepower of mechanical energy is equal to 746 W or about ¾ kW (1000 W = 1 kW). As an example, 13,800 volts × 1500 amperes = 20,700 kW (20.7 MW). This example provides for the instantaneous amount of electrical power being generated. The total energy produced by the generator is expressed in kilowatt-hours. As an example, 20,000 kW × 2 hours of generation = 40,000 kilowatt-hours. The formula for calculating kW (shown in the above illustration) is valid for directcurrent (DC) circuits and for alternating-current (AC) circuits when the AC voltage and current are in phase with each other. The power (P) consumed in a resistor is determined by the voltage measured across it, multiplied by the current flowing through it. The following power formula results: P = V × I Watts = Volts × Amps.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 9

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 10

g

GE Energy

Basic Electricity and Generation

CONDUCTORS AND INSULATORS In the simple model we have been considering, we introduced the notion of conductors. The piece of material, which permitted electron flow, is a conductor. Copper wire is considered a good conductor since it contains many free electrons. Given an electric force (voltage) acting in a particular direction, electrical energy will be transferred through the conductor by the directional movement of free electrons migrating from atom to atom within it. Each electron only moves a very short distance to a neighboring atom, where it forces one of that atom’s electrons from its outer orbit by mutual repulsion of like charges and then takes its place. The displaced electron repeats the process in another nearby atom, until the movement of electrons has been transmitted through the conductor. The more electrons that can be made to move for a given applied electric force, the better the conductor. Popular conductors in use in the power industry today are aluminum and copper, with aluminum preferred, owing to its lower price. Materials possessing very few free electrons are called insulators. In these materials, a lot of energy is required to force electrons out of their orbit about the atoms. Even then only a few can be forced out at any one time. No such thing as a perfect insulator exists and in that sense, they can be thought of as very poor conductors.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 11

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 12

g

GE Energy

Basic Electricity and Generation

MAGNETISM Let us consider a common bar magnet. Magnetism about the magnet is exhibited in the form of lines of force. These invisible lines of force are called flux lines and the shape of the area they occupy is called the flux pattern or magnetic field. The magnetic lines of force always travel out from the North Pole and reenter the magnet through the South Pole. Inside the magnet the lines of force travel from the South Pole to the North Pole. This way, the lines remain continuous and unbroken and the complete path they take is called the magnetic circuit. Flux lines per unit area, or flux density, are greater at the ends of the coil, where flux lines leave the “north” pole and enter the “south” pole. Pushing two similar poles of different magnets together, you experience a force of repulsion between them. By bringing similar poles together, one can feel a strong force of attraction. It is a characteristic of all magnetic lines of force that they always tend to repel one another and never unite or cross. Two magnetic fields, which are brought close together, will deform themselves into considerably distorted flux patterns, but will not cross each other. The type of magnet we have been considering is the natural phenomena of permanent magnetism that is exhibited in some natural materials. It is possible, however, to induce magnetism in a material by means of electricity. This is known as electromagnetism.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 13

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 14

g

GE Energy

Basic Electricity and Generation

CURRENT FLOW IN A CONDUCTOR If a magnet is moved past a piece of wire, electric current is induced in this wire. The current is induced only when the magnet is moving. As the diagrams demonstrate, you can increase the amount of electricity produced by increasing the speed with which the wire is passed back and forth about the magnet, use a stronger magnet, or use more coils of wire. The energy required to produce relative motion is analogous to the energy used in rotating a mechanical pump to produce liquid flow, as illustrated above. The circulating liquid flow is analogous to current flow in the electric circuit. The switch in the electrical circuit is analogous to the valve in the mechanical liquid circuit.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 15

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 16

g

GE Energy

Basic Electricity and Generation

FIELD AROUND A CURRENT-CARRYING CONDUCTOR Current flow through a conductor produces a magnetic field, as illustrated above. The direction of magnetic flux lines is predictable by Ampere’s right-hand rule. A compass near the conductor can be used to verify the presence and direction of the magnetic field.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 17

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 18

g

GE Energy

Basic Electricity and Generation

ELECTROMAGNET AND RIGHT-HAND RULE One of the effects of a conductor carrying a current is to produce a magnetic field. Any conductor carrying a current will, in fact, act as a magnet. If we cause current to flow in a piece of wire, a magnetic field is induced. The converse is also true—if you move a piece of wire so that it cuts through a magnetic field, an electric current will flow in the wire. Forming the conductor in the previous illustration into a coil, as illustrated above can increase magnetic field strength. To make the magnetic field of the loop stronger, form the wire into a coil containing many loops. The individual fields of all the loops reinforce one another and form a single strong magnetic field, extending both inside and outside the loop. The field strength of the coil will then be proportional to current flow and the number of turns in the coil. The magnetism also increases with increasing current. Note that once current ceases to flow in the conductor, magnetism is lost. Flux lines per unit area, or flux density, is greater at the ends of the coil where flux lines leave the North (N) pole and enter the South (S) pole. The direction of the magnetic field about a current-carrying conductor is determined by the direction of current flow. If a current-carrying conductor is grasped in the right hand with the thumb pointing in the direction of current flow, the fingers wrapped around the conductor will point in the direction of the magnetic lines of force. This is known as the “Right-Hand Rule.”

F-000-00-60-001-00

Basic Electricity and Generation

Slide 19

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 20

g

GE Energy

Basic Electricity and Generation

ELEMENTARY GENERATOR In order to understand the ac waveform, it does well to examine how it is produced. To do this, we need to understand the mechanism of ac power generation. An elementary generator consists of a loop of wire placed so that it can be rotated in a uniform magnetic field to produce electricity in the loop. If sliding contacts are used to connect the loop to an external circuit, a current will flow around the external circuit and the loop. The pole pieces are the North and South Poles of the magnet that supply the magnetic field. The loop of wire that rotates through the field is called the armature. The ends of the armature loop are connected to rings called slip rings, which rotate with the armature. Current collectors, called brushes, “brush off” the slip rings to pick up the electricity generated in the armature and carry it to the external circuit. In the description of the generator outlined, visualize the loop rotating through the magnetic field. As the sides of the loop cut through the magnetic field, they generate an emf, which causes a current to flow through the loop, slip rings, brushes, ammeter, and load resistor, all connected in series. The emf, which is generated in the loop and, therefore, the current that flows, depends on the position of the loop in relation to the magnetic field. ALTERNATING-CURRENT FREQUENCY We have seen that as the loop of the elementary generator rotated through 360 degrees, one complete revolution, the generated emf completed one cycle. If the loop rotates at a speed of 60 revolutions per second, the generated emf will complete 60 cycles per second (c/s). It will then be said to have a frequency of 60 cycles per second. The units we use for frequency are hertz (hz = c/s). Frequency is the number of cycles per second. The standard commercial frequency used in the United States is 60 Hz. Other parts of the world use frequencies of 50 Hz. Lower than 50 Hz causes problems; for instance, a visible flicker of lights can be seen using an electrical supply of less than 50 Hz. This is because every time the current changes direction, it falls to zero and momentarily switches off an electric lamp as it does so. At 50 c/s, the lamp switches on and off at 100 times per second (faster than the human eye can detect, and therefore, we have the impression that the lamp is permanently lit). At lower frequencies, it would be possible to discern this switching.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 21

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 22

g

GE Energy

Basic Electricity and Generation

SIMPLE SINGLE-PHASE GENERATOR Illustrated above is a permanent magnet with high permeability rotating near a single-loop conductor. As the N and S poles rotate (to positions) near the loop, the flux density is increased and reversed when the opposite pole approaches. The reversal in flux direction produces a once-per-cycle reversal in current flow, such that an oscillating waveform is produced. The waveform produced is sinusoidal, having a peak-positive value as each N pole passes and a peak-negative value as each S pole passes. By positioning three loops, or coils, around a rotating magnet, as illustrated in (A) above, three voltage waveforms are generated with each revolution. By arranging the coils 120 mechanical degrees apart (industry standard), three-phase power is produced, as illustrated in (B) on the next page.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 23

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 24

g

GE Energy

Basic Electricity and Generation

SIMPLE THREE-PHASE GENERATOR By positioning three loops, or coils, around a rotating magnet as illustrated in (A) above, three voltage waveforms are generated with each revolution. By arranging the coils 120 mechanical degrees apart, industry-standard, 3-phase power is produced, as illustrated in (B) above. The generating system illustrated in (A) above uses a rotating electric magnet rather than a permanent magnet. Current flow through the rotating windings is supplied by a battery and brushes, which contact rotating slip rings. A variable resistor in the external battery current loop regulates current flow through the rotating coil. This Excitation current determines the strength of the rotating magnetic field and, therefore, the voltage and/or power output from the stator windings.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 25

g

F-000-00-60-001-00

GE Energy

Basic Electricity and Generation

Basic Electricity and Generation

Slide 26

g

GE Energy

Basic Electricity and Generation

TWO POLE GENERATOR The excitation scheme, illustrated in (B) above, provides magnetic linking of the stationary and rotating parts of the machine without using brushes. Brushless excitation has become an industry-preferred standard, eliminating the wear and failure problems associated with brush type exciters. In the brushless excitation scheme, the rotating flux lines of the permanent magnet induce an AC voltage in the surrounding stationary windings. This AC voltage is rectified, and the resulting DC is regulated and applied to a set of stationary windings called the Exciter Field. The exciter field windings surround an exciter rotor, which has induced in it an AC voltage. The AC voltage output of the exciter rotor is rectified by diodes, which also rotate. The DC output from the rotating diodes is applied to the main rotor to control the electrical output of the main stator windings. The regulation of exciter field current, therefore, is a mechanism for controlling the 3-phase generator output.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 27

g

GE Energy

Basic Electricity and Generation

GENERATOR BRUSHLESS EXCITATION

F-000-00-60-001-00

Basic Electricity and Generation

Slide 28

g

GE Energy

Basic Electricity and Generation

TWO BIG IDEAS

When magnetic lines of force cut a coil, a VOLTAGE is built in the coil.

When a current is passed through a coil, a MAGNETIC FIELD is built around the coil.

F-000-00-60-001-00

Basic Electricity and Generation

Slide 29

Tab 14

g

GE Energy

TM2500+ Gen VI Package Familiarization

GENERATOR LUBE OIL SYSTEM

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 1

g

GE Energy

TM2500+ Gen VI Package Familiarization

GENERATOR LUBE OIL SYSTEM The generator lube oil system provides pressurized lubrication to the generator bearings. The major components of the lubrication system are as follows: · · · · ·

Lube oil storage reservoir, 150-gal (567 L) Generator-driven lube oil pump Motor-driven auxiliary DC lube oil pump Lube oil filter assembly Heat Exchanger

To prevent damage, the generator bearings must be lubricated whenever the generator rotor shaft rotates. Thus, lubricating oil must be supplied to the bearing assemblies during startups, at operational speeds, and while the rotor shaft coasts to a stop during shutdown. To ensure that these lubrication requirements are met under all conditions, an auxiliary 125 VDC pump remains on standby in the event the main generator-driven pump fails, or turbine shutdown is initiated. The auxiliary pump also supplies lubricating oil to the bearings during startup until the main pump has a chance to reach operating pressure.

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 2

g

GE Energy

TM2500+ Gen VI Package Familiarization

Mineral Lube Oil Reservoir F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 3

g

GE Energy

TM2500+ Gen VI Package Familiarization

Generator-Driven Lube Oil Pump This pump, mounted to the exciter end of the generator housing, is directly driven by the generator rotor shaft and supplies lube oil to the bearings at the normal operational shaft speed. Because its efficiency decreases at lower shaft speeds, the pump must be supplemented by an auxiliary pump to ensure adequate lubricating oil flow during startups and shutdowns.

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 4

g

GE Energy

TM2500+ Gen VI Package Familiarization

Auxiliary Lube Oil Pump The auxiliary pump supplies oil to the generator bearings for the first 5 minutes of startup, during shutdowns, and in case of generator-driven pump failure. This pump is driven by a 2-hp, 125-VDC, motor, and is controlled by the turbine sequencer in the electronic turbine control system. The sequencer monitors the lube oil system pressure and generator shaft speed, and activates the auxiliary pump during generator startups, shutdowns, and any other time that the lube oil pressure drops to 12 psig. An alarm sounds should the auxiliary pump activate with the generator turning at normal operating speed.

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 5

g

GE Energy

TM2500+ Gen VI Package Familiarization

Fin – Fan Cooler The Fin – Fan cooler is located off base and is equipped with two fans and two tube bundles to cool oil for both the synthetic and mineral lube oil systems. Mineral lube oil may bypass the cooler module if thermostatic control valve TCV-0000 determines the temperature to be  60° C (140 qF).

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 6

g

GE Energy

TM2500+ Gen VI Package Familiarization

GLO Simplex Filter

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 7

g

GE Energy

TM2500+ Gen VI Package Familiarization

Temperature Control valve Pressure Control Valve F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 8

g

GE Energy

TM2500+ Gen VI Package Familiarization

Typical Generator Bearing

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 9

g

GE Energy

TM2500+ Gen VI Package Familiarization

System Operation Refer to F&ID Dwg. xxxxxx-751248, Generator Lube Oil System. Lube oil pumps draw oil from the system reservoir through independent suction lines. Both pumps feed a common discharge line. A check valve maintains oil in the generator-driven pump to ensure instantaneous oil flow to the bearing assembly whenever the pump begins operation. Valve PCV-0013 prevents the lube oil pressure in the common discharge line from exceeding 30 psig (207 kPaG) and ports excess oil back to the reservoir. A relief valve PSV-0003 prevents pressure at the output of the auxiliary pump from exceeding 85 psig (586 kPaG).

Heated lube oil from the discharge of either the generator-driven or the auxiliary pump is cooled by a fin-fan heat exchanger, located on the auxiliary trailer, before flowing through the simplex oil filter assembly. The lube oil may bypass the coolers if thermostatic control valve TCV-0000 determines the temperature to be  140 qF (60 °C). As the lube oil temperature increases during generator operation, the valve progressively directs more oil through the heat exchanger until, at 140 °F (60 °C), nearly all the oil flows through the heat exchanger. After the lube oil passes through control valve TCV-0000, temperature indicator TE-0025 measures actual lube oil temperature downstream of the cooler, signaling an indicator and activating an alarm and shutdown. Temperature indicator TI-0025 provides a temperature reading to the electronic-turbine control system. Alarm TAH-0025 activates when temperatures reach 160 qF (71 °C) or higher, and a cool down lock out (CDLO) is activated when temperatures reach 190 qF (88 °C) or higher.

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 10

g

GE Energy

TM2500+ Gen VI Package Familiarization

System Operation (Continued) From the heat exchanger, the cooled oil flows into the simplex oil filter. Differential pressure transmitter PDT-0015 indicates the pressure differential across the filter elements. PDT-0015 activates alarm PDAH-0015 at the electronicturbine control system if the differential pressure reaches 20 psid (138 kPaD). Pressure indicator PI-0015 provides a pressure reading to the electronic-turbine control system.

Pressure at the filter output is controlled by pressure control valve PCV-0013 which prevents the supply line pressure from exceeding 30 psig (206.8 kPaG). This valve protects against overpressure, which can force oil past the seals in the generator-bearing assemblies, by porting excess oil back to the reservoir. Pressure transmitter PT-0026 monitors pressure down stream of the filter, signaling an indicator and activating an alarm and shutdowns. Pressure indicator PI0026 provides a pressure reading to the electronic-turbine control system. Alarm PAL-0026 is activated when pressure drops to 25 psig (1170 kPaG) or less. FSLO shutdown PALL-0026 is activated when pressure drops to 12 psig (83 kPaG) or lower. FSLO shutdown PAHH-0026 is also activated when pressure increases to 60 psig (413 kPaG) or higher. From PT-0026, lubricating oil enters the generator shaft-bearing assemblies through the orifice at the non-drive end and another orifice at the drive end. Sensing elements TE-0021 and TE-0023 monitor bearing temperatures, activating an alarm at 197 °F (92 °C) and initiating a shutdown at 203 °F (95 °C). Sensing elements TE-0035 and TE-0036 monitor the temperature of lube oil leaving the bearings, activating an alarm at 189 °F and initiating a shutdown at 194 °F. Sensing elements TE-0021, TE-0023, TE-0035, and TE-0036 transmit this data in the form of 4–20-mA signals to the electronic control system for display on the DCS monitor.

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 11

g

GE Energy

TM2500+ Gen VI Package Familiarization

System Operation (Continued) Oil from the bearing assemblies is gravity-drained back to the generator lube oil reservoir. Sight glasses in each drain line permit visual verification of oil flow. The air/oil separator on the lube oil reservoir vents any gases entrained in the returning lube oil. Immersion heater HE0005 maintains the reservoir oil temperature at 90 °F. Tank thermometer TE-0020 monitors reservoir oil temperature, and signals temperature indicator TI-0020, which provides a temperature reading to the electronic-turbine control system.TE0020 also activates alarm TAL-0020 if the oil temperature falls to 70 °F (21 °C). Level transmitter LT-0001 activates alarm LAL-0001 if the oil level drops to 63% of full. LT-0001 activates alarm LAH-0001 if the oil level rises to 87% of full. LT-0001 will initiate a shutdown if the oil level falls to 55% of full.

F-025-10-30-300-00

TM2500+ Generator Lube Oil System

Slide 12

g

GE Energy

F-025-10-30-300-00

TM2500+ Gen VI Package Familiarization

TM2500+ Generator Lube Oil System

Slide 13

g

GE Energy

F-025-10-30-300-00

TM2500+ Gen VI Package Familiarization

TM2500+ Generator Lube Oil System

Slide 14

Tab 15

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 1

gGE Energy

TM2500+Turbine Control System (Woodward Control)

Turbine Control Panel • Divided into Control Cubicle and Termination Cubicle • Discrete Operator Interface • Complete legend of components found in Turbine Control Panel Plan and Elevation Drawing (XXX014)

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 2

gGE Energy

TM2500+Turbine Control System (Woodward Control)

Control System Functions • • • • •

Fuel Control Sequencing Protection Generator Excitation Control Human Machine Interface

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 3

gGE Energy

TM2500+Turbine Control System (Woodward Control)

FUEL CONTROL • More than simple speed “governing” • Includes speed control, temperature control, fuel scheduling/limiting, and variable geometry control • Fuel control performed by Woodward MicroNet Plus™

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 4

gGE Energy

TM2500+Turbine Control System (Woodward Control)

Woodward MicroNet Plus™ • Simplex or duplex CPU and power supplies • Located in MTTB • Complete list of I/O points found in Fuel Control Worksheet (XXX143)

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 5

gGE Energy

TM2500+Turbine Control System (Woodward Control)

SEQUENCING • • • •

Startup/shutdown control Sequencing of auxiliary equipment Monitoring of package instrumentation Central point of communication for all control system components • Primary interface to HMI • Performed by GE FANUC RX7i Process Automation Controller with VersaMax I/O

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 6

gGE Energy

TM2500+Turbine Control System (Woodward Control)

GE FANUC RX7i • CPU with ethernet communication • Redundant Genius buss communications to VersaMax I/O • Located in Turbine Control Panel

• Complete list of sequencer I/O found in Sequencer Worksheet (XXX146) F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 7

gGE Energy

TM2500+Turbine Control System (Woodward Control)

VersaMax I/O • Remote I/O modules mounted in TCP, MTTB, and MGTB • Redundant Genius Buss communications • 4-20mA analog, RTD and Discrete input/output module types

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 8

gGE Energy

TM2500+Turbine Control System (Woodward Control)

PROTECTION • Protection functions exist in both fuel control and sequencer • Separate, dedicated equipment is provided for – – – –

Backup Overspeed Vibration Protection Fire and Gas Detection Electrical Faults

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 9

gGE Energy

TM2500+Turbine Control System (Woodward Control)

HMI Displays • HMI (Human Machine Interface) displays allow the operator to view operational trends of the GTG set and its various systems • Screens show critical operating parameters and system setpoints

F-025-10-40-100-00

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 10

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 11

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 12

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 13

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 14

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 15

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 16

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 17

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 18

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 19

gGE Energy

F-025-10-40-100-00

TM2500+Turbine Control System (Woodward Control)

TM2500+ TURBINE CONTROL SYSTEM (Woodward Control)

Slide 20

Tab 16

g

GE Energy

TM2500+ Gen VI Package Familiarization

TM2500+ SEQUENCES

F-025-10-50-004-00

TM2500+ Sequences

Slide 1

g

GE Energy

TM2500+ Gen VI Package Familiarization

PRE-START INSPECTION Before starting the TM2500+ MGTG set, perform the following inspections and initial steps to avoid inadvertent shutdown or possible damage to the equipment. 1. Check the turbine inlet plenum for foreign objects or debris. Remove any debris.

CAUTION

FOREIGN OBJECTS OR DEBRIS LEFT IN THE TURBINE INLET PLENUM COULD RESULT IN SEVERE DAMAGE TO THE TURBINE ENGINE.

2. Check the oil level in the turbine, hydraulic starter, and generator lube oil systems’ reservoirs. Fill as required. Use only the approved lube oils for the turbine, starter, and generator lube oil systems. Check lube oil temperatures. Minimum acceptable lube oil temperature is 70° F (21° C).

F-025-10-50-004-00

TM2500+ Sequences

Slide 2

g

GE Energy

TM2500+ Gen VI Package Familiarization CAUTION DO NOT FILL THE TURBINE LUBE OIL RESERVOIR PAST TWO-THIRDS FULL WHILE THE TURBINE IS RUNNING. OVERFILLING WILL RESULT IN RUNOVER WHEN UNIT IS SHUT DOWN. IF LUBE OIL TEMPERATURE IS LESS THAN 70 °F, ENSURE THAT THE HEATERS IN THE LUBE OIL TANKS ARE TURNED ON. (REFER TO ONE LINE DIAGRAM, MOTOR CONTROL CENTER.)

3. Check the fuel pressure. Fuel inlet pressure must be within specifications. 4. Check fluid level in the reservoir of the hydraulic start unit. Replenish fluid levels as needed. Use approved fluid. 5. Examine all fluid fittings, piping, flanges, and hoses for evidence of leakage. Check hoses for chafing. NOTICE LEAKS AT FUEL LINE FITTINGS ARE OFTEN CAUSED BY LOOSE FITTINGS AND CAN BE ELIMINATED BY SIMPLY TIGHTENING. IF REQUIRED, LOCK-WIRE FITTINGS IN ACCORDANCE WITH THE STANDARD MAINTENANCE PRACTICES OUTLINED IN THE GE LM2500 ON-SITE OPERATION & MAINTENANCE MANUAL.

F-025-10-50-004-00

TM2500+ Sequences

Slide 3

g

GE Energy

TM2500+ Gen VI Package Familiarization

6. Check condition of the fire and gas protection system detectors. . a. Check thermal (heat) spot detectors for clean, undamaged probes. Check maintenance records to verify that the detectors have been properly calibrated and tested in accordance with the maintenance schedule.

b. Check combustible gas detector sensors to ensure that the screens are clean. Check the maintenance records to verify that the sensors have been properly calibrated and tested in accordance with the maintenance schedule.

NOTICE

GAS DETECTOR SENSORS ARE VERY SENSITIVE AND REQUIRE FREQUENT CALIBRATION. IF IN DOUBT, CALIBRATE OR REPLACE THEM WITH NEW SENSORS.

F-025-10-50-004-00

TM2500+ Sequences

Slide 4

g

GE Energy

TM2500+ Gen VI Package Familiarization 7. Check the fire-extinguishing system as follows: a. Inspect fire extinguishant discharge nozzles for obstructions or .corrosion. b. Check the weight and charge pressure of each fireextinguishing bottle. c. Check the batteries and battery chargers that supply power to the fire suppression and gas detection panel. Verify that connections at the battery terminals are tight and free of dirt and corrosion, the batteries are fully charged, and chargers are operating properly. NOTICE DURING THE FIRST 30–90 DAYS OF OPERATION, MONITOR THE EQUIPMENT FREQUENTLY. RECORD PERFORMANCE TRENDS IN ORDER TO PREDICT MAINTENANCE AND INSTRUMENT SET INTERVALS.

8. Check and record all instrument readings at regular intervals while the GTG set is in operation. Ensure that all readings are within normal limits.

F-025-10-50-004-00

TM2500+ Sequences

Slide 5

g

GE Energy

F-025-10-50-004-00

TM2500+ Gen VI Package Familiarization

TM2500+ Sequences

Slide 6

g

GE Energy

TM2500+ Gen VI Package Familiarization

Local Start Sequence with Automatic Synchronizing & Paralleling OPERATOR ACTION

SYSTEM RESPONSE

1.

Set Synchronizing switch to Auto position.

2.

Set Voltage Regulator excitation mode switch to Auto position; and set Voltage Regulator On-Off switch to On position.

On the CRT, AVR In Auto message appears on the Generator Data portion of the display. If manual voltage regulation has been selected, the AVR In Manual message replaces AVR In Auto.

3.

Select Start from the Unit Control screen.

Compartment vent fans toggle, and vent fan airflow is verified. The hydraulic start pump is energized.

COMMENTS This is the preferred mode of operation. The switch settings are required for automatic voltage, frequency, and phase matching. This permits automatic synchronizing and paralleling of the applicable breaker.

The generator auxiliary lube oil pump energizes. Pump discharge pressure is verified. 10 sec later, the starter is engaged, and cranks the gas generator.

F-025-10-50-004-00

TM2500+ Sequences

The GTG set undergoes crank.

Slide 7

g

GE Energy

OPERATOR ACTION 3.

Select Start from the Unit Control screen. (Cont)

TM2500+ Gen VI Package Familiarization

SYSTEM RESPONSE

COMMENTS

The purge ends after 2 min (standard configuration) and approximately 7-8 min (HRSG). The solenoid valve destrokes the starter swash plate to min position, and the gas generator speed decreases to 0%. When gas generator speed drops below 1700 rpm for gas/1200 rpm for liquid, the solenoid valve positions starter swash plate angle to max (100%).

4.

On the CRT system, observe the rpm indicated by GG Speed Reference display.

The starter ramps to 100% and begins to accelerate the gas generator.

If the gas generator speed fails to exceed 1700 rpm within 10 sec, the Fail To Crank shutdown is tripped.

5.

Observe power turbine inlet T48 Temp and GG Speed Reference displays.

Fuel flow and ignition start at 1700 rpm for gas or 1200 rpm for liquid.

Light-off speed.

Light-off occurs. T4.8 should exceed 400°F (204°C).

If T4.8 temperature fails to exceed 400 °F within 10 sec (or 25 sec for liquid fuel) after gas generator speed reaches 1700 rpm, the Fail To Ignite shutdown is tripped..

F-025-10-50-004-00

TM2500+ Sequences

Slide 8

g

GE Energy

OPERATOR ACTION 5.

Observe power turbine inlet T48 Temp and GG Speed Reference displays. (Cont)

TM2500+ Gen VI Package Familiarization

SYSTEM RESPONSE

COMMENTS

The fuel system start ramp begins increasing fuel flow to accelerate the gas generator to idle (starter disconnect) speed.

If gas generator speed fails to exceed 4500 rpm within 60 sec after T48 temperature reaches 400 °F (204°C), the Fail To Accelerate shutdown is tripped Gas turbine has reached its minimum selfsustaining (idle) speed (app. 6800 rpm).

When gas generator speed exceeds 4500 rpm, - starter disengages - igniters shut off - Starting Cycle message terminates - Turbine Running message appears - Fired Starts Counter advances by one increment - Turbine Run Time meter initializes

F-025-10-50-004-00

TM2500+ Sequences

As generator shaft speed reaches 2500 rpm, the electronic control system deenergizes the auxiliary pump and the generator-driven pump assumes lubrication load. If oil pressure is outside pre-set limits, the control system reenergizes the auxiliary pump, activates an alarm, and displays the Aux Pump On Unsched message. The AC pump remains energized until the problem is corrected.

Slide 9

g

GE Energy

OPERATOR ACTION 6.

On the CRT display, observe that gas generator speed stabilizes at approx. 6800 rpm and that power turbine speed increases.

TM2500+ Gen VI Package Familiarization

SYSTEM RESPONSE

COMMENTS

Gas generator speed reaches 6800 rpm, starting 1 min warm-up timer.

If power turbine speed fails to exceed 350 rpm within the 1 min warm-up period, the PT Fail To Accelerate shutdown activates.

After 1 min warm up complete, GG ramps up to accelerate power turbine to 3600 rpm.

Excitation increases as the accelerates to synch idle speed

7.

On the CRT’s Gen Power Data screen, observe Generator Voltage data, Exciter Field Voltage data, and Exciter Field Current ampere data.

After an approximate 60 sec delay for voltage to stabilize, paralleling devices are enabled.

8.

Observe the red and green lamps used to indicate the status of the circuit breaker.

When paralleling devices generator frequency, phase and output voltage with those other bus, the circuit breaker and Ready To Load appears.

F-025-10-50-004-00

TM2500+ Sequences

match angle, on the closes

unit

The MGTG set is ready to assume its proportional share of the load. The red (breaker closed) lamp illuminates and the green (breaker open) lamp extinguishes.

Slide 10

g

GE Energy

OPERATOR ACTION 9.

On CRT’s Gen Power Data screen, check generator ammeter, varmeter, and wattmeter readings.

10.

On the CRT, check T48 Temp, GG Speed, and PT Speed displays.

11.

Use the Governor Raise-Lower switch to increase the loading on the generator.

TM2500+ Gen VI Package Familiarization

SYSTEM RESPONSE

COMMENTS

The unit assumes new load setting by increasing fuel flow. Loading is limited by T48 maximum temperature.

END OF SEQUENCE

F-025-10-50-004-00

TM2500+ Sequences

Slide 11

g

GE Energy

F-025-10-50-004-00

TM2500+ Gen VI Package Familiarization

TM2500+ Sequences

Slide 12

g

GE Energy

TM2500+ Gen VI Package Familiarization

Engine Stopping Modes Shutdown may be initiated by operator selection or caused by engine operational conditions at any time during startup or running operational modes. The LM2500 software code lists more than 200 engine, generator, and subsystem conditions that can cause a shutdown. The five programmed shutdown sequences that can occur once shutdown is initiated are:

1)

Emergency Stop – No motoring (ESN)

2)

Emergency Stop with motoring (ES)

3)

Step To Idle (STI)

4)

Decelerate to Minimum load (DM)

5)

Normal Shut Down (NSD)

F-025-10-50-004-00

TM2500+ Sequences

Slide 13

g

GE Energy

TM2500+ Gen VI Package Familiarization

ESN (FSLO) - Emergency Stop No motoring (Fast Stop Lock-Out) •Immediately shutdown the unit by shutting off fuel, water / steam and trip the breaker. •When NGG (HP shaft) coasts down below 300 RPM and if the T48 temperature is above 1150 degrees F (621 degrees C) then a 4-hour lockout will be initiated after a 10 minute delay. •A 15 minute crank cycle must complete to reset the 10 minute delay timer. •If the crank cycle is interrupted, causing N25 to coast below 300 RPM, and if the high T48 temperature persists, then a 4-hour lockout period is initiated

ES (FSWM) - Emergency Stop (Fast Stop With Motoring) •Immediately shutdown the unit by shutting off fuel, water / steam and trip the breaker. •When N25 (HP shaft) coasts down to 1700 RPM, engage starter and crank for 15 minutes.

F-025-10-50-004-00

TM2500+ Sequences

Slide 14

g

GE Energy

TM2500+ Gen VI Package Familiarization

STI (SDTI) - Step to Idle (Step Decel To Idle) •Immediately step the megawatt load to minimum. The breaker remains closed. •If the SI condition cannot be reset within 10 seconds then an ESN occurs.

DM (SML) - Decelerate to Minimum load (Slow to Minimum Load) •Fast load shed within 20 seconds. If the DM condition cannot be reset within 5 minutes then an NSD occurs.

NSD (CDLO) - Normal ShutDown (CoolDown LockOut) •Shed load and water / steam at the normal stop rate of 0.19 MW/Sec. Open breaker when minimum load is achieved. •Idle at synchronous speed for 5 minutes maximum to cool down unit and then shut off fuel, water / steam. •If the NSD condition can be reset within the shutdown period, then the NSD shutdown is aborted. •Fans & lube oil pumps remain on for a 30 minute cool-down cycle F-025-10-50-004-00

TM2500+ Sequences

Slide 15

Tab 17

g

ABBREVIATIONS AND ACRONYMS

F-000-00-60-002-00

GE Energy 1

g

THIS PAGE INTENTIONALLY LEFT BLANK

2

F-000-00-60-001-00

GE Energy

g TECHNICAL MANUAL ABBREVIATIONS AND ACRONYMS A A Ampere(s) abs Absolute AC Alternating Current acfm Actual Cubic Feet per Minute acmm Actual Cubic Meter per Minute AGB Accessory Gearbox ALF Aft, Looking Forward Assy Assembly ASTM American Society for Testing and Materials atm Atmosphere AUX Auxiliary AVRX Auxiliary Voltage Regulator B β (Beta) Variable Stator Position BEM Brush Electrical Machines bhp Brake Horsepower BOP Balance of Plant Btu British Thermal Unit C C Degree Celsius (Centigrade) cc Cubic Centimeter CCW Counterclockwise CDLO Cooldown Lockout CDP Compressor Discharge Pressure cfm Cubic Feet per Minute CG Center of Gravity cid Cubic Inch Displacement CIT Compressor Inlet Temperature cm Centimeter cm2 Square Centimeter cm3 Cubic Centimeter Cont Continued CRF Compressor Rear Frame CRT Cathode-Ray Tube (Screen) CT Current Transformer CW Clockwise D dB dBA

Decibel Decibel (Absolute)

F-000-00-60-001-00

GE Energy 3

g DC DCS DF dn/dt

Direct Current Digital Control System Diesel Fuel Differential Speed/Differential Time (Rate of Change, Speed vs. Time) dp Differential Pressure dp/dt Differential Pressure/Differential Time -dPs3/dt Negative Rate of Change of HighPressure Compressor Static Pressure DSM Digital Synchronizing Module Dwg. Drawing E EMU Engine Maintenance Unit F F FCV F&ID Fig. FIR FMP FOD FLSO

Degree Fahrenheit Flow Control Valve Flow & Instrument Diagram Figure Full Indicator Reading Fuel Manifold Pressure Foreign-Object Damage Fast Stop Lockout Without Motoring FSWM Fast Stop With Motoring ft Foot (Feet) 2 Square Feet ft ft3 Cubic Feet ft-lb Foot-Pound G GA gal GE GG gpm GT GTG

General Arrangement Gallon(s) General Electric Gas Generator Gallons per Minute Gas Turbine Gas Turbine Generator

H H-O-A HAND-OFF-AUTO (Switch)

4

F-000-00-60-001-00

GE Energy

g hp HP HPC HPCR HPT HPTR h Hz

Horsepower High Pressure High-Pressure Compressor High-Pressure Compressor Rotor High-Pressure Turbine High-Pressure Turbine Rotor Hour(s) Hertz (Cycles per Second)

I ID Inside Diameter IEEE Institute of Electrical and Electronics Engineers IGHP Isentropic Gas Horsepower IGKW Isentropic Gas Kilowatt IGV Inlet Guide Vane in Inch(es) in2 Square Inch in3 Cubic Inch in-Hg Pressure, Inches of Mercury in-lb Inch-Pound in-Wg Pressure, Inches of Water I/O Input/Output IPB Illustrated Parts Breakdown ISA Instrument Society of America K kg cm Kilogram-Centimeter kg m Kilogram-Meter kohm Kilohm kPa KiloPascal kPad KiloPascal Differential kPag KiloPascal Gauge K (CONT) kV Kilovolt kVA Kilovolt Ampere kvar Kilovar kW Kilowatt kWh Kilowatthour kWhm Kilowatthour Meter L L lb

Liter Pound(s)

F-000-00-60-001-00

GE Energy 5

g LEL LFL LP LPC Lpm LPCR LVDT

Lower Explosive Limit Lower Flammable Limit Low Pressure Low-Pressure Compressor Liters Per Minute Low-Pressure Compressor Rotors Linear Variable-Differential Transformer

M m Meter 2 m Square Meter m3 Cubic Meter mA Milliampere Maint. Maintenance MAVR Modular Automatic Voltage Regulator mb Millibar MCC Motor Control Center MGTB Main Generator Terminal Box MHz Megahertz MIL Military MIL-SPEC Military Specification MIL-STD Military Standard min Minute(s) mm Millimeter Mohm Megohm(s) mph Miles Per Hour MTTB Main Turbine Terminal Box Mvar Megavar MW Megawatt N NEMA National Electrical Manufacturers Association Nm Newton Meter NOx Oxides of Nitrogen O OAT Outside Air Temperature OD Outside Diameter O&M Operation and Maintenance P P2

Low-Pressure Compressor Inlet

6

F-000-00-60-001-00

GE Energy

g Total Pressure High-Pressure Compressor Inlet Total Pressure P48 Low-Pressure Turbine Inlet Total Pressure Pamb Ambient Pressure Para. Paragraph P (CONT) PCB Printed Circuit Board PF Power Factor PMG Permanent Magnet Generator ppm Parts Per Million Ps3 High-Pressure Compressor Discharge Static Pressure Ps25 High-Pressure Compressor Inlet Static Pressure Ps55 Low-Pressure Turbine Discharge Static Pressure psia Pounds per Square Inch Absolute psid Pounds per Square Inch Differential psig Pounds per Square Inch Gauge PT Pressure Transmitter PTO Power Takeoff P25

R rms rpm RTD RTV

Root Mean Square Revolutions Per Minute Resistance Temperature Detector Room Temperature Vulcanizing

S scfm Standard Cubic Feet per Minute scmm Standard Cubic Meters per Minute SDTI Step Decelerate to Idle sec Second(s) SG Specific Gravity shp Shaft Horsepower SMEC Spray Mist Evaporator Cooler SML Slow Decelerate to Minimum Load S/O Shutoff SOV Solenoid-operated Valve S&S Stewart & Stevenson Services, Inc. STIG Steam Injection

F-000-00-60-001-00

GE Energy 7

g T T2 T3 T25 T48 Tamb TAN TBD TGB theta 2

TIT TRF

Low-Pressure Compressor Inlet Total Temperature High-Pressure Compressor Discharge Temperature High-Pressure Compressor Inlet Temperature Low-Pressure Turbine Inlet Temperature Ambient Temperature Total Acid Number To Be Determined Transfer Gearbox Ratio of Measure Absolute Gas Generator Inlet Temperature to Standard Day Absolute Temperature Turbine Inlet Temperature Turbine Rear Frame

V V Volt VAC Volts, Alternating Current var Volt-Ampere Reactive VBV Variable Bypass Valve VDC Volts, Direct Current VG Variable Geometry V (CONT) VIGV Variable Inlet Guide Vane VSV Variable Stator Vane W W W2

Watt Low Pressure Compressor Physical Airflow W25 High Pressure Compressor Physical Airflow Wf Flow, Fuel Wg Pressure, Water Gauge Wh Watt-Hour WHRU Waste Heat Recovery Unit X XN2

8

Low-Pressure Rotor Speed Physical

F-000-00-60-001-00

GE Energy

g XN2R Low-Pressure Rotor Speed Corrected XN25 High-Pressure Compressor Speed Physical XN36 Acoustic monitor DLE XN25R High-Pressure Compressor Speed Corrected XNSD Low-Pressure Turbine Speed

F-000-00-60-001-00

GE Energy 9

g

THIS PAGE INTENTIONALLY LEFT BLANK

10

F-000-00-60-001-00

GE Energy

g

GLOSSARY

F-000-00-60-001-00

GE Energy 11

g

This Page Intentionally Left Blank

12

F-000-00-60-001-00

GE Energy

g GLOSSARY A A/D Conversion – Analog-to-Digital Conversion: A con-version that takes an analog input in the form of electrical voltage or current and produces a digital output. ABT – Automatic Bus Transfer: For critical loads, normal and alternate, power sources are provided. The power sources are supplied from separate switchboards through separate cable runs. Upon loss of the normal power supply, the transfer switch automatically disconnects this source and shifts the load to the alternate source. AC – Alternating Current: Alternating current is an electric current that flows first in one direction for a given period of time, and then in the reverse direction for an equal period of time, constantly changing in magnitude. A – Ampere: A unit of electrical current or rate of flow of electrons. One volt across one ohm of resistance causes a current flow of one ampere. Analog Signal: An analog signal is a measurable quantity that is variable throughout a given range and is representative of a physical quantity. Annular: In the form of, or forming, a ring. Anti-Icing: A system for preventing the buildup of ice on the gas turbine intake systems.

APD – Automatic Paralleling Device: Automatically parallels any two gas turbinegenerator sets. B Babbitt: A white alloy of tin, lead, copper, and antimony which is used for lining bearings. BAS – Bleed-Air System: The BAS uses as its source compressed air extracted from the compressor stage of each gas turbine module and gas turbine-generator set. The BAS is used for anti-icing, prairie air, masker air, and low-pressure gas turbine starting for both the gas turbine module and the gas turbine-generator set. Bleed Air: Hot, compressed air bled off the compressor stage of the gas turbine module and gas turbine-generator set. See BAS – Bleed-Air System. Blow-in Doors: The blow-in doors located on the high-hat assembly are designed to open by means of solenoid-operated latch mechanisms if the inlet airflow becomes too restricted for normal engine operation.

F-000-00-60-001-00

GE Energy 13

g Borescope: A small periscope used to visually inspect internal engine components. BTB – Buss Tie Breaker: A BTB is used to connect one main switchboard to another main switchboard. Buffer: To electronically isolate and filter an electrical signal from its source. Bus: The term used to specify an uninsulated power conductor. C CB – Circuit Breaker: An automatic protective device that, under abnormal conditions, will open a current-carrying circuit. CIT – Compressor Inlet Temperature (T2): CIT is the temperature of the air entering the gas turbine compressor as measured at the front frame. CIT is one of the parameters used for calculating engine power output (torque) and scheduling fuel flow and variable stator vane angle. Coalesce: To grow together, unite, or fuse, as uniting small liquid particles into large droplets. This principle is used to remove water from fuel in the filter/separator. Condensate: The product of reducing steam (gas) to a liquid; (water). For example, as used in the distilling process. D D/A Conversion – Digital-to-Analog Conversion: A con-version that produces an analog output in the form of voltage or current from a digital input. DC – Direct Current: Direct current is an electric current that flows in one direction. A pure direct current is one that will continuously flow at a constant rate. Deaerator: A deaerator is a device that removes air from oil as in the LS&C tank (gas turbine module) which separates air from scavenged oil. Delta P – Differential Pressure: The pressure drop across a fixed device. Demisters: A moisture-removal device that separates water from air. Dessicant: A substance having a great affinity for water and used as a drying agent. Diffuser: A device that reduces the velocity and increases the static pressure of a fluid passing through a system. Digital Signal: A signal, in the form of a series of discrete quantities, that has two distinct levels.

14

F-000-00-60-001-00

GE Energy

g E Eductor: The eductor is a mixing tube which is used in the gas turbine module exhaust system. It is physically positioned at the top of the stack so that the gas flow from the gas turbine module exhaust nozzles will draw outside air into the exhaust stream as it enters the mixing tube. EG – Electronic Governor: An electronic governor is a system that uses an electronic control unit, in conjunction with an electrohydraulic governor actuator, to control the position of the liquid fuel valve on the gas turbine-generator set and regulate engine speed. F Fault Alarm: This type of alarm is used in the Fuel Oil Control System and Damage Control Console. It indicates that a sensor circuit has opened. FO System – Fuel Oil System: The FO system provides a continuous supply of clean fuel to the gas turbine module and to the gas turbine-generator set. The gas turbine module and gas turbine-generator set can operate on DFM, ND, and JP-5. FOD – Foreign-Object Damage: Damage as a result of entry of foreign objects into a gas turbine engine. G GB – Generator Breaker: Circuit breaker used to connect a gas turbine-generator set to its main switchboard. GCU – Generator Control Unit: A static GCU is supplied for each gas turbine-generator set consisting of a static exciter/voltage regulator assembly, field rectifier assembly, motordriven rheostat, and a mode select rotary switch. It controls the output voltage of the generator. Governor Droop Mode: Droop mode is normally used only for paralleling with shore power. Because shore power is an infinite bus, droop mode is necessary to control the load carried by the gas turbine-generator set. If a gas turbine-generator set is paralleled with shore power, and one attempts to operate in isochronous mode instead of droop mode, the gas turbine-generator set governor speed reference can never be satisfied because the gas turbinegenerator set frequency is being held constant by the infinite bus. If the gas turbine-generator set governor speed reference is above the shore power frequency, the load carried by the gas turbine-generator set will increase beyond capacity in an effort to raise the shore power frequency. If the speed reference is below the shore power frequency, the load will decrease and reverse in an effort to lower the shore power frequency. The resulting overload or reverse power will trip the gas turbine-generator set circuit breaker.

F-000-00-60-001-00

GE Energy 15

g Governor Isochronous Mode: The isochronous mode is normally used for gas turbinegenerator set operation. This mode provides a constant frequency for all load conditions. When operating two gas turbine-generator sets in parallel isochronous mode, it also provides equal load sharing between the units. GTG Set – Gas Turbine-Generator Set: The GTG set consists of a gas turbine engine; a reduction gearbox; and a three-phase, alternating-current generator rated at 2000 kW and 450 VAC. GTM – Gas Turbine Module: The GTM consists of the main propulsion gas turbine unit, including the gas turbine engine, base, enclosure, shock-mounting system, fire detection and extinguishing system, and the enclosure environmental control components. H Header: This is a piping manifold that connects several sub-lines to a major pipeline. Head Tank: A tank located higher than other system components to provide a positive pressure to a system by gravity. Helix: A tube or solid material wrapped like threads on a screw. High-Hat Assembly: A removable housing over the main engine air intake ducts, which contains the moisture-separating system, inlet louvers, and blow-in doors. Hz – Hertz: A unit of frequency equal to one cycle per second. I I/O – Input/Output: The interfacing of incoming and outgoing signals from the computer to the controlled device. IGV – Inlet Guide Vanes: Vanes ahead of the first stage of compressor blades of a gas turbine engine whose function is to guide the inlet air into the gas turbine compressor at the optimum angle. Immiscible: Incapable of being mixed. Impinge: To strike, hit, or be thrown against, as in the case of condensate impinging against the tubes or baffles. Inlet Plenum: That section of the gas turbine inlet air passage that is contained within the engine enclosure.

16

F-000-00-60-001-00

GE Energy

g ISO – Isochronous: Governing with steady-state speed regulation of essentially zero magnitude. L Labyrinth/Windback Seals: The labyrinth/windback seals combine a rotating element with a smooth-surface stationary element to form an oil seal. This type of seal is used in conjunction with an air seal, with a pressurization air cavity between the two seals. Pressure in the pressurization air cavity is always greater than the sump pressure, therefore, flow across the seal is toward the sump, thus preventing oil leakage from the sump. The windback is a course thread on the rotating element of the oil seal which, by screw action, forces any oil which might leak across the seal back into the sump. Latent: Present, but not visible or apparent. LED – Light-emitting Diode: A solid-state device which, when conducting, emits light. The LEDs are used for the digital displays and card fault indicators in the local control panel and other electronic systems. Liquid Fuel Valve: Meters the required amount of fuel for all engine operating conditions for the GTG set engine. Load Shedding: Generator overpower protection by automatically dropping preselected nonvital loads when generator output reaches 100% for 3 seconds, and additional dropping of preselected semivital loads if the overload condition exists for another 5 seconds. Local Control: Startup and operation of equipment by means of manual controls attached to the machinery, or by the electric panel attached to the machinery or located nearby. LOCOP – Local Control Panel: Electronic enclosure containing operating and monitoring equipment used to control the turbine during operation. The control elements of the system are powered by 28 VDC from the switchboard or batteries. M micron: A unit of measure equal to one-millionth of a meter. mil: A unit of measure equal to one-thousandth of an inch. MRG – Main Reduction Gear: The reduction gear is a single-reduction, single-helical (spiral), gear-type speed reducer. N Nozzle: A small jet (hole) at the end of a pipe.

F-000-00-60-001-00

GE Energy 17

g O Orifice: A restricted opening used primarily in fluid systems. P PCB – Printed Circuit Board: An electronic assembly mounted on a card using etched conductors. Also called Printed Wiring Board (PWB). PF – Power Factor: The ratio of the average (or active) power to the apparent power (rootmean-square voltage × rms current) of an alternating-current circuit. Pinion: A smaller gear designed to mesh with a larger gear. Pitch: A term applied to the distance a propeller will advance during one revolution. PMA – Permanent Magnet Alternator: PMA is mounted on the generator shaft extension of each GTG set and supplies speed sensing and power to the EG. PMA also supplies initial generator excitation. Poppet-Type Check Valve: A valve that moves into and from its seat to prevent oil from draining into the GTG set when the engine is shut down. ppm – Parts Per Million: Unit of measure. pps – Pulses Per Second: Unit of measure. psi – Pounds per Square Inch: Unit of measure (pressure). psia – Pounds per Square Inch Absolute: Unit of measure (pressure). psid – Pounds per Square Inch Differential: Unit of measure (pressure). psig – Pounds per Square Inch Gage: Unit of measure (pressure). PTO – Power Takeoff: PTO is the drive shaft between the GTG set, gas turbine engine, and the reduction gearbox. Transfers power from the gas turbine to the reduction gearbox to drive the generator. Pushbutton Switch Indicators: A panel-mounted device that contains both switch contacts and indicating lights. The contacts are actuated by depressing the device face. The indicator lights are labeled and wired for indicating alarm or status information. R

18

F-000-00-60-001-00

GE Energy

g Rabbet Fit: A groove, depression, or offset in a member into which the end or edge of another member is fitted, generally so that the two surfaces are flush. Also known as register and spigots. Radio-Frequency Interference: An electrical signal capable of being propagated into, and interfering with, the proper operation of electrical or electronic equipment. RTD – Resistance Temperature Detector: Same as RTE. RTE – Resistance Temperature Element: These temperature sensors work on the principle that as temperature increases, the conductive materials exposed increase their electrical resistance. S Scavenge Pump: Used to remove oil from a sump and return it to the oil supply tank. scfm – Standard Cubic Feet per Minute: Unit of measure. Sensor: A device that responds to a physical stimulus and transmits a result impulse for remote monitoring. Serial Data Bus: The bus is time-shared between the LOCOP and the end device. Control and status information are exchanged in the form of serial data words. Stall: An inherent characteristic of all gas turbine compressors to varying degrees and under certain operating conditions. It occurs whenever the relationship between air pressure, velocity, and compressor rotational speed is altered to such extent that the effective angle of attack of the compressor blades becomes excessive, causing the blades to stall in much the same manner as an aircraft wing. Sync – Synchronize: The state where connected alternating-current systems operate at the same frequency and where the phase-angle displacements between voltages in them are constant or vary about a steady and stable average value. SWBD – SWitchBoarD: A large panel assembly which mounts the control switches, circuit breakers, instruments, and fuses essential to the operation and protection of electrical distribution systems. Switch Indicator: See Pushbutton Switch Indicator. T T2 – Compressor Inlet Temperature: Same as CIT. TIT – Turbine Inlet Temperature: TIT is the GTG set’s turbine inlet temperature.

F-000-00-60-001-00

GE Energy 19

g U Ultraviolet Flame Detectors: Ultraviolet flame detectors sense the presence of fire in the GTM and GTG set and generate an electrical signal to the alarm panel. X XDCR – Transducer: The XDCR is a sensor that converts quantities such as pressure, temperature, and flow rate into electrical signals. XFR – Transfer: The theoretical relationship between measure and output values, as determined by inherent principles of operation.

20

F-000-00-60-001-00

GE Energy

g

GAS TURBINE ENGINE THEORY DEFINITIONS

F-000-00-60-001-00

GE Energy 21

g

THIS PAGE INTENTIONALLY LEFT BLANK

22

F-000-00-60-001-00

GE Energy

g GAS TURBINE ENGINE THEORY DEFINITIONS INTRODUCTION This information sheet has been prepared to aid the student in his understanding of the basic principles of physics, the gas laws, thermodynamics, and the Brayton cycle, which are associated with gas turbine engine operation. A thorough knowledge of these principles will greatly aid the student throughout his career in the Gas Turbine field. REFERENCES Aircraft Gas Turbine Engine Technology Sawyer’s Turbomachinery Maintenance Handbook Modern Marine Engineers Manual Handbook of Physics and Chemistry Basic Thermodynamics DEFINITIONS Absolute pressure P The actual pressure applied to a system. Normally found by adding a value of 14.7 to gauge readings. (Normal units are expressed as pounds per square inch, absolute (psia).) Absolute temperature T Temperature that is reckoned form the absolute zero. (Normal units are expressed as either degrees Rankine or degrees Kelvin.) Absolute zero The point at which all molecular activity ceases. Computed to be a temperature of approximately –460 degrees Fahrenheit (−460° F) or –273 degrees Celsius (−273° C). Acceleration a The rate of change of velocity, in either speed or direction. (Normal units are expressed as feet per second squared (ft/sec2).) Adiabatic As applied to thermodynamics, applies to a process or cycle that occurs with no net loss or gain of heat. Ambient pressure Pamb For our uses while studying marine gas turbine engines, the pressure felt directly outside the ship (atmospheric pressure). Ambient temperature Tamb For our uses while studying marine gas turbine engines, the temperature felt directly outside the ship (atmospheric temperature). DEFINITIONS (CONT)

F-000-00-60-001-00

GE Energy 23

g Bernoulli theorem As a fluid flows through a restricted area such as a nozzle, the velocity of the fluid will increase with a corresponding decrease in pressure and a slight decrease in temperature. The inverse is true for fluid flow through a diffuser. Boyle’s law If the absolute temperature of a given quantity of gas is held constant, the absolute pressure of the gas is inversely proportional to the volume the gas is allowed to occupy. Brayton cycle The thermodynamic cycle on which all gas turbine engines operate, considered to be a constant pressure cycle (combustion occurs at a constant pressure). British thermal unit Btu Defined as the quantity of heat required to raise the temperature of a 1-pound mass of water 1 degree Fahrenheit (1° F). (Water is to be pure distilled water, and the temperature change is from 64 degrees Fahrenheit (64° F) to 65 degrees Fahrenheit (65° F).) Cascade effect As related to compressor stall, cascade effect is where turbulence created in the forward stages of the compression section is passed rearward through the compressor, with an increase in the total amount of turbulence with each successive stage. Celsius (centigrade) °C Normally used by scientists, a temperature scale in which the temperature θc in degrees Celsius (°C) is related to the temperature Tk in kelvins by the formula: θc = Tk − 273.15. Charles’ law If the absolute pressure of a given quantity of gas is held constant, the volume the gas is allowed to occupy is directly proportional to the absolute temperature of the gas. Compound blading A blending of both reaction and impulse turbine blading such that the actual blades are impulse at the root and reaction at the tip. It is the most common type of blading used in the turbine and power turbine sections of modern gas turbine engines. Compressor discharge pressure CDP The actual pressure of the air exiting the compressor section, after having passed through all stages of compression and the diffuser, and passing on to the combustion section. Compressor discharge temperature CDT The temperature of the compressed air that has passed through all compression stages and the diffuser, and is being passed to the combustor.

24

F-000-00-60-001-00

GE Energy

g Compressor inlet pressure CIP The pressure of the air at the inlet to the inlet guide vanes of the compressor. Normally slightly less than atmospheric pressure.

Compressor inlet temperature CIT The temperature of the air which actually enters the compressor. Normally measured at the inlet bellmouth. Compressor stall When turbulence across the stages of the compressor becomes severe enough (owing to the cascade effect), the actual airflow through the compressor is disrupted and decreases. During compressor stall, it is not common to see a reduction in the rpm of the compressor section, only a reduction in the actual air- flow through the compressor. Compressor ratio C/R compressor inlet pressure.

A ratio of the compressor discharge pressure divided by the

Compressor ratio per stage CR/STG The pressure rise that each individual stage in the compressor can handle. It has been determined that in an axial-flow compressor, the maximum CR/STG is approximately 1.2-to-1. Conduction A method of heat transfer in which one area of a substance is heated, causing an increase in the molecular vibrations at that point. These increased vibrations are transmitted from atom to atom throughout the length of the substance. Configuration

How something is put together.

Conservation of momentum During an elastic collision with no losses owing to heat or friction, the total momentum of Object 1 must equal the total momentum of Object 2. Convection A method of heat transfer in which one area of a fluid is heated, causing a current to be set up that transfers the heat throughout the fluid. Cycle conditions.

A process that begins with certain conditions and ends at the original

Cycle efficiency The output horsepower of the engine divided by the input energy used. In the case of all gas turbine engines, efficiency is equal to work rate brake divided by heat rate of addition (the units for both must be the same). (Normal units are expressed as percent (%).) Delta δ

Pressure correction factor.

Distance

d

The amount of linear separation between two or more objects or points.

Diameter D The length of a straight line through the center of an object. (Normal units are expressed as feet (ft) or inches (in).)

F-000-00-60-001-00

GE Energy 25

g Dovetail A type of blade attachment normally used to attach the rotating blades in the compressor section of an axial-flow compressor to the disk. Elastic collision In physics, a collision in which there are no losses owing to friction or heat, and no plastic deformation occurs. Energy (ft-lb.).)

E

The capacity to do work. (Normal units are expressed as foot pounds

Exhaust gas temperature EGT The temperature of the gases that are exhausted from the engine. (Normal units are expressed as degrees Fahrenheit (°F).) Exit guide vanes EGV Used in most axial-flow compressors to reduce the total amount of turbulence that is passed from the compressor section to the combustion section of the engine. Fahrenheit °F Degrees Fahrenheit. A temperature scale normally used by engineers (not an absolute temperature scale). First law of thermodynamics Energy is indestructible and interconvertible. Three main points: (1) Energy cannot be created or destroyed; (2) energy can change forms; and (3) energy is conserved for any system, open or closed. A type of blade attachment normally used to hold the rotating blades of an axial-flow turbine to the turbine disk or wheel.

Fir tree

Fluid Any substance which conforms to the shape of its container (may be either liquid or gas). Force F A vector quantity that tends to produce, modify, or retard motion. (Normal units are expressed as pounds (lb).) Fuel flow Wf The amount of fuel an engine is using at any given time. (Normal units are expressed as gallons per hour (gal/hr).) Function

How something is accomplished.

Gas constant R A number derived for any gas by use of the perfect gas equation. This constant for atmospheric air is 53.345. Gas generator G/G The section of a split-shaft engine that is composed of the compressor, combustor, and turbine.

26

F-000-00-60-001-00

GE Energy

g Gas turbine engine GTE A form of internal combustion heat engine that operates on the Brayton cycle, and in which all events occur continuously during normal engine operation. Gauge pressure psig The actual pressure readings taken from gauges that are calibrated to read absolute pressure. General gas law

A combination of both Boyle’s law and Charles’ law.

Gravity g The gravitational attraction of the mass of the earth, the moon, or a planet for bodies at or near its surface. On earth, the acceleration owing to gravity is 32.174 ft/sec2. Heat Q The energy associated with the random motion of atoms, molecules, and smaller structural units of which matter is composed. .

Heat rate of addition Qa The amount of energy (in Btu/min) which is added during the combustion process in the gas turbine engine. DEFINITIONS (CONT) .

Heat rate of rejection Qr A loss for a gas turbine engine. The amount of energy that was added during the gas turbine engine cycle, but was not extracted in the turbine section and was exhausted to the atmosphere. (Normal units are expressed in British thermal units per minute (Btu/min).) Heat transfer substances. Height hgt

The transfer of thermal energy between two or more bodies or

The extent of elevation above a level. (Normal units are expressed as feet (ft).)

Horsepower hp The unit of power in the British engineering system, equal to 550 footpounds per second, approximately 745.7 watts. Impulse blading A type of turbine or power turbine blading which operates principally by the conservation of momentum. Inlet guide vanes IGV A set of vanes located in the forward part of the axial-flow compressor which are used to direct the incoming air at a predetermined angle toward the direction of rotation of the first-stage blades. Kelvin K scale.

A temperature scale which is absolute and is related to the Celsius temperature

Kinetic energy pounds (ft-lb).)

EK

F-000-00-60-001-00

The energy of motion. (Normal units are expressed as foot-

GE Energy 27

g Local sound of speed CS temperature.

Speed of sound is directly related to the ambient or local

Mass m The quantity of fundamental matter of which an object is composed. Mass of an object does not change with location. Matter

Anything having weight and occupying space.

Momentum M A property of a moving body that determines the length of time required to bring it to rest when under the action of a constant force. Newton’s laws physics:

Three laws which encompass a large amount of classical

Every body or substance will continue in its state of rest or uniform motion in a 1st straight line, unless acted upon by some external force. 2nd A force is required to accelerate a body; the magnitude of this force is directly proportional to the mass of the body and to the acceleration produced. Mathematically written as: F = m · a. 3rd

For every action, there is an equal and opposite reaction.

Open cycle A cycle in which the operating medium is drawn in at atmospheric conditions, undergoes some process or processes, and is then returned to atmospheric conditions. Potential energy

Ep

Stored energy.

pi π The ratio of the circumference of any circle to its diameter. A constant with no units; an approximation is 3.1416. Power p

The time rate of doing work. (Normal units are expressed as horsepower (hp).)

Power turbine extracted.

P/T

Pound(s)

A unit of measure used to denote either an amount of weight or force.

lb

Pound mass lbm weight).

The section of split-shaft engines in which work rate brake is

A unit of measure used to denote the mass of an object (the object’s

Pressure The force or thrust exerted over a surface divided by its area. (Normal units are expressed as pounds per square inch (psi).)

28

F-000-00-60-001-00

GE Energy

g Primary air all CDP air.

The CDP air which is actually used for combustion in a GTE; 25% of

Radiation One type of heat transfer in which the thermal energy is transferred from one body or substance which is not in physical contact with a second body or substance by random wave motion. Rankine °R Degrees Rankine. An absolute temperature scale that is directly related to the Fahrenheit temperature scale.

Reaction blading The type of turbine blading which operates mainly on the principle of action and reaction. Revolutions per minute

rpm

A measure of the speed of rotation of a rotating body.

Secondary air The portion of CDP air which is used to cool and center the flame of combustion, 75% of all CDP air. Second law of thermodynamics Heat cannot, on its own accord, be made to flow from a body or substance of lower temperature to a body or substance of higher temperature in a continuous, self-sustaining process. More simply stated, heat transfer is from hot to cold. Single-shaft engine One of the simplest forms of GTE which has only one shaft and three major components: (1) a compressor, (2) a combustor, and (3) a turbine. Specific enthalpy

h

The total energy content of a mass of gas.

Specific heat c The quantity of heat required to raise the temperature of a 1-pound mass of a substance at 1 degree Fahrenheit (1° F). cv

Specific heat at constant volume

cp

Specific heat at constant pressure

Speed N Distance traveled per unit time. (Common units are expressed as feet per second (ft/sec), miles per hour (mph), and revolutions per minute (rpm).) Temperature T A measure of the intensity of heat. (Normal units are expressed as Fahrenheit (°F) or Rankine (°R) (where an absolute unit is required).) Theta Θ

The temperature correction factor.

Thermodynamics or reaction of heat.

F-000-00-60-001-00

The branch of physics which deals with the mechanical action

GE Energy 29

g Time t A measured or measurable period during which an action, process, or condition exists or continues. Tip clang The actual bending of the rotating blades used in an axial-flow compressor when the pressures across the blades become excessive because of the turbulence of stall. When these have enough pressure to cause them to physically bend, they can actually contact the stationary vanes; when this occurs, the condition is known as tip clang. Turbine inlet temperature TIT The temperature of the gases exiting the combustion section of the engine and entering the turbine section. Total energy Et

The algebraic sum of the potential and kinetic energy of a body or substance.

Velocity vel Speed in a given direction; a vector quantity. (Normal units are expressed as feet per second (ft/sec) or revolutions per minute (rpm).) Vector quantity Volume V inches (in3).)

A quantity that has both magnitude and direction. Cubic capacity. (Normal units are expressed as cubic feet (ft3) or cubic

Weight wt A measure of the pull of gravity on a quantity of matter. (Normal units are expressed as pound(s) (lb).) Work W Work is equal to the product of the force applied to an object, multiplied by the distance through which the force acts. Work rate brake

Wb

The actual output horsepower that is produced by an engine.

Work rate of compression Wc compressor sections of a GTE.

The calculated value of power required to drive the

Work rate turbine Wt The amount of work extracted from the hot gases in the turbine section. This work must be utilized to drive both the compressor section and the engine’s load in the single-shaft engine, and the value of work rate turbine is used only to drive the compressor in the splitshaft engines. (Normal units are expressed as horsepower (hp).)

30

F-000-00-60-001-00

GE Energy

g

CONVERSION CHARTS

F-000-00-60-001-00

GE Energy 31

g

32

F-000-00-60-001-00

GE Energy

g

F-000-00-60-001-00

GE Energy 33

g

34

F-000-00-60-001-00

GE Energy

Tab 18

Tab A

Tab B

CONTROL SYSTEM LAYOUT SITE:

GE PACKAGED POWER, L.P.

MASTER - Replace with Customer Name

LOCATION MOBILE GENERATOR

***PRELIMINARY***

TURBINE: TM2500+ MICRONET PLUS / LINKNET

WOODWARD TO SUPPLY MATERIAL AND SPARE PARTS RECOMMENDATIONS FOR: 1 MICRONET FUEL MANAGEMENT AND SEQUENCER SYSTEM.

LOCAL MAIN MICRONET PLUS CHASSIS BASED ON THE FOLLOWING OPERATING CONDITIONS:

X -4 C 50 C -40 C

CONTINUOUS DUTY COGENERATION SERVICE OPERATING TEMPERATURE (MIN) (-20 C) OPERATING TEMPERATURE (MAX) (55 C) STORAGE TEMPERATURE (MIN) (-40 C)

80.0 C 95 X 4

STORAGE TEMPERATURE (MAX) (80 C) % HUMIDITY (NON CONDENSING) NON HAZARDOUS AREA SEISMIC ZONE (UBC)

© Copyright 2010 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary and/or confidential property of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

WOODWARD LOCAL MAIN CHASSIS 1

1 1 1 3 1 1 1 1 0 1

WOODWARD LOCAL CONTROL SYSTEM CONSISTS OF:

14 SLOT MICRONET PLUS CHASIS VME RACK WITH FAN ASSEMBLY ------------------------------------ 5453-759 MICRONET CPU5200 (POWERPC MPC5200, 400MHZ, 64MB FLASH, 128MB RAM, DUAL CAN) ------- 5466-1035 POWER SUPPLY MODULE, 24 VDC INPUT POWER ---------------------------------------------------------------5466-1000 ANALOG I/O MODULE (2 X 12 ISOLATED ANALOG INPUTS - RTDs, OR 4-20mA, OR TYPE K THERMOCOUPLES, AND OUTPUTS 2 X 4 -- 4-20mA PER) ---------------------------------------5466-425 MAGNETIC PICKUP MODULE (4 INPUTS PER) --------------------------------------------------------------------- 5464-658 ACTUATOR DRIVER/FDBK MODULE (2 ACT OUTPUTS PER) -------------------------------------------------- 5501-432 DISCRETE OUTPUT MODULE ( 64 CHANNELS) -------------------------------------------------------------------- 5464-654 ISOLATOR, ETHERNET PORT ------------------------------------------------------------------------------------------- 5453-754 DRIVER BOX ASSM., FOR 3 DLE GAS FUEL VALVES ------------------------------------------------------------ 8301-706 LINKNET CONTROLLER MODULE------------------------------------------------------------------------------------- 5466-031

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

1 1 0 0 0 6 0 0 0 15 28 7

SERIAL INPUT/OUTPUT MODULE ( 4 PORTS) ----------------------------------------------------- 5466-348 DISCRETE I/O MODULE (2X24 INPUTS, 2X12 OUTPUTS PER) -------------------------------- 5466-258 SERIAL PORT ISOLATOR/CONVERTOR (RS-232 TO RS-485) ---------------------------------- 1784-575 REAL TIME SI/O MODULE ------------------------------------------------------------------------------ 5466-328 PRESSURE XDUCER COMM INTERFACE MODULE --------------------------------------------- 5466-326 RACK SLOT COVER PLATES ---------------------------------------------------------------------------3799-301 NOTCH FILTER - 3 kHz ( 1 PER SYSTEM)------------------------------------------------------------ 5437-845 DRIVER BOX ASSM., FOR 4 DLE LIQ FUEL VALVES -------------------------------------------- 8301-714 10 AMP RELAY BOX (16 RELAYS PER BOX) ------------------------------------------------------5464-691 K TYPE THERMOCOUPLE TO 0-5 VOLT------------------------------------------------------------- 1784-653 NON-ISOLATED PASS THRU WITH 200 OHM RES. FOR 4-20ma LOOP-----------------------1784-659 MODULE, RTD, 100 OHM,PT---------------------------------------------------------------------------- 1784-655

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 1 OF 7

GE PACKAGED POWER, L.P.

CONTROL SYSTEM LAYOUT SITE:

MASTER - Replace with Customer Name

***PRELIMINARY***

LOCATION MOBILE GENERATOR TURBINE: TM2500+ MICRONET PLUS / LINKNET

MIicroNet - 14 SLOT VME RACK - Fuel/Airflow Controller RACK - FC1

POWER SUPPLY 1PA1 2 SLOTS

B

SLOT 1

SLOT 2

SLOT 3

SLOT 4

SLOT 5

CPU

COVER PLATE

COVER PLATE

SPEED SENSOR MPU

SERIAL I/O

5200

SLOT 7 DISCRETE OUTPUT

SLOT 8

SLOT 9

ACTUATOR HI-DENS TWO ANALOG CHANNEL IN/OUT

SLOT 10

SLOT 11

SLOT 12

HI-DENS ANALOG IN/OUT

HI-DENS DIST ANALOG I/O IN/OUT NETWORK

SLOT 13

SLOT 14

COVER PLATE

COVER PLATE

COVER PLATE

COVER PLATE

RESERVED FOR POWER SUPPLY

WIDE

4 CH

A1 W101-1

CABLES

SLOT 6 HI-DENS SIMPLEX DISCRETE IN/OUT

B

MODULE CONNECTORS

ENET1 ENET2 RTN1 RTN2 DEBUG COM1 CAN1 CAN2

B

TERMINAL BLOCKCONNECTOR

EISO1 ESWM1

A2

A3

A4 W104

4 CH

A5 W1009-1

UL1.1A4J1 UL1.1A5J1 UL1.1A5J2 UL1.1A5J3 UL1.1A5J4

FTM104

DMMF

2 X 24 IN 2 X 12 OUT

2 X 32 OUT

A6 W106-1 W106-2

A7 W107-1 W107-2

A8 W108

UL1.1A6J1 UL1.1A6J2

UL1.1A7J1 UL1.1A7J2

UL1.1A8J1

FTM106.1 FTM106.2

FTM107.1 FTM107.2

FTM108

24-IN/ 8 OUT

24-IN/ 8 OUT

24-IN/ 8 OUT

A9 W109-1 W109-2

A10 W110-1 W110-2

A11 W111-2

UL1.1A9J1 UL1.1A10J1 UL1.1A11J1 UL1.1A9J2 UL1.1A10J2 UL1.1A11J2

FTM109.1 FTM109.2

FTM110.1 FTM110.2

2 SLOTS

A12 W112-1 W112-2 W112-3

A13

WIDE

A14

NTWK1 NTWK2 NTWK3 NTWK4

FTM111.2

NOTE: W107-2 is a jumper from one Relay Box to the other.

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 2 OF 7

GE PACKAGED POWER, L.P.

CONTROL SYSTEM LAYOUT SITE:

MASTER - Replace with Customer Name

***PRELIMINARY***

LOCATION MOBILE GENERATOR TURBINE: TM2500+ MICRONET PLUS / LINKNET

MicroNet Plus CABLE SCHEDULE

B

FOR LOCAL MicroNet MAIN CHASSIS

OTHER CABLE W101-1 W101-2 W101-3 W101-4 W101-5 W101-6 W101-7 W101-8 W104 W105-1 W105-2 W1009-1 W105-4 W106-1 W106-2 W107-1 W107-2 W108 W109-1 W109-2 W110-1 W110-2 W111-1 W111-2 W112-1 W112-2 W112-3 W112-4 QUANTITY

5417-041 LD DISC 12 FT

5417-040 LD DISC 10 FT

CABLE 5417-045 LD DISC 20 FT

TYPE 5417-029 LD ALG 12 FT

5417-175 HD 14 FT

5417-176 HD 16 FT

5417-177 HD 18 FT

1 0 0 0 0 0 0 0 1 0 0 1 0 1 1 1 1 1 1 1 1 1 0 1 0 0 0 0 2

1

1

1

1

2

3

2

FUNCTION ETHERNET COM #1 ETHERNET COM #2 REAL TIME NETWORK #1 REAL TIME NETWORK #2 RS232 SERVICE PORT RS232 / 422 / 485 PORT CAN1 CAN2 SPEED SENSORS RS232 PORT #1 RS232 PORT #2 RS232 / 422 / 485 PORT #3 RS232 / 422 / 485 PORT #4 HD DISCRETE I/O HD DISCRETE I/O RELAY OUT RELAY OUT ACTUATOR HD ANALOG I/O # 1 HD ANALOG I/O # 2 HD ANALOG I/O # 1 HD ANALOG I/O # 2 HD ANALOG I/O # 1 HD ANALOG I/O # 2 LINKNET COM #1 LINKNET COM #2 LINKNET COM #3 LINKNET COM #4

TERMINAL BLOCK AND CONNECTOR ISOLATOR

FTM104

ANALOG 5437-523

DEVICE DESIGNATION HD ANALOG I/O HD DISC I/O ACT DVR 5441-695 5441-693 5437-672

16 RELAYS OUT

1751-6091

1

DMMF/VIB COMM FTM106.1 FTM106.2 FTM107.1 FTM107.2 FTM108 FTM109.1 FTM109.2 FTM110.1 FTM110.2 FTM111.1 FTM111.2 MTTB - N101 M,GTB - N207 TCP - N340 TERM BLOCK QTY

1 1 1 1 1 1 1 1 1 1

1

5

1

3

2

ISOLATOR = 5453-754

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 3 OF 7

GE PACKAGED POWER, L.P.

CONTROL SYSTEM LAYOUT SITE:

MASTER - Replace with Customer Name

***PRELIMINARY***

LOCATION MOBILE GENERATOR TURBINE: TM2500+ MICRONET PLUS / LINKNET

LINKNET DISTRIBUTIVE I/O BLOCKS DISTRIBUTIVE I/O BLOCKS BASED ON THE FOLLOWING OPERATING CONDITIONS: X -25 C 60.0 C -40 C

CONTINUOUS DUTY COGENERATION SERVICE OPERATING TEMPERATURE (MIN) (-25 C) OPERATING TEMPERATURE (MAX) (60 C) STORAGE TEMPERATURE (MIN) (-40 C)

N101 B

LOOP 1 MTTB

TB

LOOP 2 MGTB

TB

LOOP 3 TCP/MCC

TB

N102 TB

4-20 mA INPUT

B

100 OHM RTD

N108 TB

100 OHM RTD

N209 TB

100 OHM RTD

N110 TB

100 OHM RTD

N206 TB

N340 DISCRETE DIGITAL INPUT

N105 TB

4-20 mA INPUT

N207 B

80.0 C 95 X 4

100 OHM RTD

N119 TB

100 OHM RTD

N212 TB 100 OHM RTD

N103 TB

100 OHM RTD

N217

TB

STORAGE TEMPERATURE (MAX) (80 C) % HUMIDITY (NON CONDENSING) UL RATED FOR CLASS 1 DIV 2 GROUP D AREA CLASSIFICATION SEISMIC ZONE (UBC)

TERMINATOR TB

4-20 mA INPUT

TERMINATOR TB

4-20 mA INPUT

TERMINATOR TB

LOOP 4 AUX SKID NOT USED

WOODWARD DISTRIBUTIVE I/O BLOCKS 4

4-20mA INPUT MODULE (6 POINTS PER MODULE) (NON-ISOLATED) -------------------------------------- 9905-969

0

4-20mA INPUT MODULE (6 POINTS PER MODULE) (ISOLATED) ---------------------------- 9905-968

0 8 0 0

4-20mA OUTPUT MODULE (6 POINTS PER MODULE) ----------------------------------------------------------- 9905-972 100 OHM RTD MODULE (6 INPUTS PER MODULE) --------------------------------------------------------------- 9905-970 200 OHM RTD MODULE (6 INPUTS PER MODULE) --------------------------------------------------------------- 9905-678 TYPE K THERMOCOUPLE INPUT MODULE (6 ISOLATED INPUTS PER MODULE) (FAIL HIGH) ------------------------------------------------------------------------------------------- 9905-966

1 0 3 0

DIGITAL INPUT MODULE (16 POINTS PER MODULE) ------------------------------------------ 9905-971 DIGITAL OUTPUT MODULE (8 POINTS PER MODULE) ----------------------------------------- 9905-973 LOOP TERMINATOR ------------------------------------------------------------------------------------- 9905-760 TYPE K THERMOCOUPLE INPUT MODULE (6 ISOLATED INPUTS PER MODULE) (FAIL LOW) -------------------------------------------------------------------------- 9905-967

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 4 OF 7

CONTROL SYSTEM LAYOUT SITE:

GE PACKAGED POWER, L.P.

MASTER - Replace with Customer Name

***PRELIMINARY***

LOCATION MOBILE GENERATOR TURBINE: TM2500+ MICRONET PLUS / LINKNET

TM2500 TURBINE OPERATING MODES: X X

ISOCHRONOUS ISOCHRONOUS (LOAD SHARING) DROOP DROOP (FREQUENCY COMPENSATED)

3. 4. 5. 6. 7. 8. 9.

N2 MINIMUM SPEED ----------------------------------N2 SPEED SWITCH 1 SET POINT ---------------------N2 SPEED SWITCH 2 SET POINT ---------------------N2 SPEED SWITCH 3 SET POINT ---------------------N2 OVERSPEED SWITCH 4 SET POINT -------------N2 FAILURE SPEED ------------------------------------DROOP CALIBRATION ----------------------------------

GAS FUEL LIQUID FUEL * = TUNABLE RANGE

N1 SPEED CONTROL:

N2 SPEED CONTROL: 1. N2 RPM/MPU FREQUENCY RATIO 1 RPM =------2. N2 ACTUAL SPEED READOUT CALIB 4mA =----20mA =

X X

1.3833 Hz 0 RPM 5000 RPM 60 Hz 1800 3000 3598 3900 3960 500 5

RPM RPM RPM RPM RPM RPM %

50 Hz 1500 2500 2995 3250 3960 500 5

RPM (PT BREAKAWAY) RPM RPM (ENABLE SYNCHRONIZER) RPM (* 3000,3400 PRE O/S ALM) RPM (OVERSPEED SHUTDOWN) RPM %

1. RPM/MPU FREQUENCY RATIO -------------------------- 1 RPM 2. ACTUAL READOUT CALIBRATION ----------------------- 4mA 20mA = 3. a. N1 SPEED SWITCH 1 SET POINT (GAS) ------------------------b. N1 SPEED SWITCH 1 SET POINT (LIQ) ------------------------4. N1 SPEED SWITCH 2 SET POINT ----------------------------------5. N1 SPEED SWITCH 3 SET POINT ----------------------------------6. N1 SPEED SWITCH 4 SET POINT ----------------------------------7. N1 SPEED SWITCH ---------------------------------------------------8. N1 FAILURE SPEED POINT ------------------------------------------

0.783294 0 12000 1700 1200 4500 5000 10100 10200 500

Hz RPM RPM RPM (FUEL & IGN ON "GAS") RPM (FUEL & IGN ON "LIQ") RPM (STARTER CUT-OFF) RPM (IDLE) RPM (OVERSPEED ALARM) RPM (OVERSPEED SHUTDOWN) RPM

N1 SPEED REFERENCE: N2 SPEED REFERENCE: 1. 2. 3. 4. 5. 6. 7. 8.

N2 N2 N2 N2 N2 N2 N2 N2

UPPER LIMIT -----------------------------------------POSITION 1 CONTROL POINT -------------------POSITION 2 CONTROL POINT -------------------LOWER LIMIT ---------------------------------------SLOW RATE ----------------------------------------MEDIUM RATE --------------------------------------FAST RATE -------------------------------------------REFERENCE READOUT CALIB 4mA = -----20mA =

3852 3600 3634 3200 6 8 12 0 5000

RPM RPM RPM RPM RPM/SEC RPM/SEC RPM/SEC RPM RPM

3210 3000 3034 2666 6 8 12

RPM RPM RPM RPM RPM/SEC RPM/SEC RPM/SEC

* SEE NOTE 1 BELOW

1. 2. 3. 4. 5. 6. 9.

N1 UPPER LIMIT ------------------------------------------------------N1 POSITION 2 CONTROL POINT ---------------------------------N1 POSITION 3 CONTROL POINT ---------------------------------N1 LOWER LIMIT -----------------------------------------------------N1 SLOW RATE -------------------------------------------------------N1 MEDIUM RATE ---------------------------------------------------N1 FAST RATE ---------------------------------------------------------

10500 5300 5300 5000 30 60 120

RPM RPM RPM RPM (* 5000,5500) RPM/SEC RPM/SEC RPM/SEC

NOTE: * 1: TUNABLE (60 Hz 3600,3900) (50 Hz 3000,3250)

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 5 OF 7

CONTROL SYSTEM LAYOUT SITE:

GE PACKAGED POWER, L.P.

MASTER - Replace with Customer Name

***PRELIMINARY***

LOCATION MOBILE GENERATOR TURBINE: TM2500+ MICRONET PLUS / LINKNET

TEMPERATURE CONTROL: T48

60 Hz 1. 2. 3. 4. 5. 6. 7. 8. 9.

THERMOCOUPLE TYPE K T48 SWITCH 1 SETPOINT -------------------------T48 SWITCH 2 SETPOINT -------------------------T48 SWITCH 3 SETPOINT -------------------------T48 SWITCH 4 SETPOINT -------------------------T48 FAILURE OVERRIDE SETPOINT ----------T48 FAILURE LEVEL -------------------------------T48 SPREAD CHECK -------------------------------T48 GAS FUEL DRY --------------------------------T48 LIQ FUEL DRY --------------------------------10. T48 GAS FUEL WET TO 42 PPM NOX ---------T48 LIQ FUEL WET TO 42 PPM NOX ----------11. T48 GAS FUEL WET 25/42 PPM NOX ----------T48 LIQ FUEL WET 25/42 PPM NOX ------------12. T48 OVERTEMP DRY -----------------------------T48 OVERTEMP WET TO 42 PPM NOX--------T48 OVERTEMP WET 25/42 PPM NOX----------

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

200 400 1150 1200 400 400 200 1540 1565 1530 1555 1520 1545 1575 1565 1555

50 Hz DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F DEG F

200 400 1150 1200 400 400 200 1525 1550 1515 1540 1505 1530 1575 1565 1555

DEG F (WATER WASH ENABLE) DEG F (FAIL TO FIRE/FLAME OUT) DEG F (START OVERTEMP ALARM) DEG F (START OVERTEMP SHUTDOWN) DEG F DEG F DEG F (SPREAD ALARM) DEG F (* 1480-1540)(* 1480-1525)(RUN PRE-OVERTEMP ALARM) DEG F (* 1480-1565)(* 1480-1550)(RUN PRE-OVERTEMP ALARM) DEG F (* 1480-1530)(* 1480-1515)(RUN PRE-OVERTEMP ALARM) DEG F (* 1480-1555)(* 1480-1540)(RUN PRE-OVERTEMP ALARM) DEG F (* 1480-1520)(* 1480-1505)(RUN PRE-OVERTEMP ALARM) DEG F (* 1480-1545)(* 1480-1530)(RUN PRE-OVERTEMP ALARM) DEG F (RUN OVERTEMP SHUTDOWN) DEG F (RUN OVERTEMP SHUTDOWN) DEG F (RUN OVERTEMP SHUTDOWN)

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 6 OF 7

CONTROL SYSTEM LAYOUT SITE:

GE PACKAGED POWER, L.P.

MASTER - Replace with Customer Name

LOCATION MOBILE GENERATOR

***PRELIMINARY***

TURBINE: TM2500+ MICRONET PLUS / LINKNET

A B B B B B

REVISION INITIAL ISSUE UPDATED CABLES ON SHEET 2 UPDATED MODULE CONNECTORS ON SHEET 2 UPDATED TERMINAL BLOCK CONNECTORS ON SHEET 2 UPDATED CABLE SCHEDULE ON SHEET 3 UPDATED ORDER ON LINKNET DISTRIBUTIVE I/O BLOCKS

DATE 10/10/07 ML 01/25/10 HS 01/25/10 HS 01/25/10 HS 01/25/10 HS 01/25/10 HS

===== END =================

ORIGINATED: 10/10/07 PRINTED: 11/03/2014 03:10 p. m. REV DATE: 01/25/10

CONTROL SYSTEM LAYOUT

DWG NO: 752145 REV B EC-75837 PAGE 7 OF 7

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 1

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V FUNCTION

ITEM

SOURCE/ DESTINATION

CHASSIS

IN/ OUT

CABLE

BOARD

CHANNEL NUMBER

TYPE

GE PACKAGED POWER, L.P.

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

FTM TERMINALS

TERMINAL FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** PACKAGE - LOCAL

ANALOG

INP UTS/OUTP UTS

1111-

1 2 3 4

GAS GENERATOR ROTOR SPEED (NGGA) POWER TURBINE ROTOR SPEED (NPTA) GAS GENERATOR ROTOR SPEED (NGGB) POWER TURBINE ROTOR SPEED (NPTB)

SE-8000A SE-8002A SE-8000B SE-8002B

IN IN IN IN

MAG MAG MAG MAG

1 1 1 1 1

4 4 4 4 4

1 2 3 4

W104 W104 W104 W104 W104

2222222222222222-

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PT INLET TEMP (T48A) PT INLET TEMP (T48B) PT INLET TEMP (T48C) PT INLET TEMP (T48D) (T3A2) GG COMPRESSOR DISCHARGE TEMP (T3B2) GG COMPRESSOR DISCHARGE TEMP TURBINE GAS FUEL SUPPLY FLOW TURBINE LIQ FUEL PUMP SUPPLY TURBINE LUBE OIL TANK TURBINE LIQ FUEL PRIMARY MANIFOLD TURBINE LIQ FUEL SECONDARY MANIFOLD TURBINE NOX WATER INJECTION PUMP SUPPLY TURBINE NOX WATER INJ METERING VALVE POSITION DEMAND TURBINE FUEL GAS METERING VALVE POSITION DEMAND TURBINE HYDRAULIC STARTER PUMP PISTON GENERATOR MEGAWATT (TO CUSTOMER)

TE-8043A TE-8043B TE-8043C TE-8043D TE-8038C TE-8038D FT-2000 PT-2021 TE-1013 PT-2029 PT-2030 PT-2074 ZC-2019 ZC-2001 SOV-6019 MW

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 OUT1 OUT2 OUT3 OUT4

TYPE K TYPE K TYPE K TYPE K TYPE K TYPE K 4-20 4-20 RTD 4-20 4-20 4-20 4-20 4-20 4-20 4-20

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4

W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1 W109-1

FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1FTM109.1-

15/14/16 21/20/22 27/26/28 33/32/34 39/38/40 45/44/46 54/51/52 60/57/58 61/62/63/64 72/69/70 78/75/76 84/81/82 1/2/3 4/5/6 7/8/9 10/11/12 86

+/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +24V/+/SHLD +24V/+/SHLD X/-/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD GROUND

2222222222222222-

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

EXCITER FIELD VOLTS EXCITER FIELD AMPS BUS VOLTAGE (RUNNING) BUS FREQUENCY GENERATOR VOLTAGE (INCOMING) AIR INLET FILTER (COMBUSTION) AIR INLET FILTER (VENTILATION) TURBINE HYDRAULIC STARTER OIL TANK TURBINE HYDRAULIC STARTER OIL TANK POWER TURBINE INLET (P48) TURBINE COMP DISCHARGE (PS3A) HIGH PRESSURE RECOUP (RIGHT) (SPARE) (SPARE) GENERATOR MVAR (TO CUSTOMER) GENERATOR VOLTAGE (INCOMING) (TO CUSTOMER)

EVX EAX BVX BFX GVX PDT-4005 PDT-4004 LT-6001 TE-6003 PT-8060 PT-8004A PT-8064

IN13 IN14 IN15 IN16 IN17 IN18 IN19 IN20 IN21 IN22 IN23 IN24 OUT5 OUT6 OUT7 OUT8

4-20S 4-20S 4-20S 4-20S 4-20S 4-20 4-20 4-20 RTD 4-20 4-20 4-20 4-20 4-20 4-20 4-20

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9 9

13 14 15 16 17 18 19 20 21 22 23 24 5 6 7 8

W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2 W109-2

FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2FTM109.2-

15/14/16 21/20/22 27/26/28 33/32/34 39/38/40 48/45/46 54/51/52 60/57/58 61/62/63/64 72/69/70 78/75/76 84/81/82 1/2/3 4/5/6 7/8/9 10/11/12 86

+/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD X/-/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD GROUND

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

MVAR GVX

FTM104FTM104FTM104FTM104FTM104-

20/21/2 22/23/4 24/25/6 26/27/8 37

PACKAGE - LOCAL ANALOG INPUTS/OUTPUTS

+/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD GROUND

Ratio 1 RPM = 0.783294 Hz Ratio 1 RPM = 1.38333 Hz Ratio 1 RPM = 0.783294 Hz Ratio 1 RPM = 1.38333 Hz

OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+

SIGNAL TO CUSTOMER

SIGNAL TO CUSTOMER SIGNAL TO CUSTOMER

DWG NO: 7245381-753146 REV A EC-10013 SHEET 1 OF 6, PAGE 1 OF 16

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 1

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V FUNCTION

ITEM

SOURCE/ DESTINATION

CHASSIS

IN/ OUT

TYPE

GE PACKAGED POWER, L.P.

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

CABLE

BOARD

CHANNEL NUMBER

FTM TERMINALS

TERMINAL FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** PACKAGE - LOCAL

ANALOG

INP UTS/OUTP UTS

3333333333333333-

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

PT INLET TEMP (T48E) PT INLET TEMP (T48F) PT INLET TEMP (T48G) PT INLET TEMP (T48H) (T3B1) GG COMPRESSOR DISCHARGE TEMP TURBINE LIQ FUEL METERING VALVE POSITION TURBINE LIQ FUEL SUPPLY TURBINE NOX WATER INJECTION SUPPLY TURBINE NOX WATER INJECTION METERING VALVE POSITION TURBINE COMBUSTOR FLAME DETECTOR A TURBINE GAS FUEL METERING VALVE POSITION TURBINE COMBUSTOR FLAME DETECTOR B (RESERVE) (RESERVE) (SPARE) (SPARE)

TE-8043E TE-8043F TE-8043G TE-8043H TE-8038B ZC-2018 FT-2002 FT-2003 ZC-2019 BE-8022A ZS-2001 BE-8022B

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 OUT1 OUT2 OUT3 OUT4

TYPE K TYPE K TYPE K TYPE K TYPE K 4-20S 4-20 4-20 4-20S 4-20 4-20S 4-20 4-20 4-20 4-20 4-20

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4

W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1 W110-1

FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1FTM110.1-

15/14/16 21/20/22 27/26/28 33/32/34 39/38/40 45/44/46 51/50/52 57/56/58 63/62/64 72/69/70 75/74/76 84/81/82 1/2/3 4/5/6 7/8/9 10/11/12 86

+/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +24V/+/SHLD +24V/+/SHLD +/-/SHLD +24V/+/SHLD +/-/SHLD +24V/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD GROUND

OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+

3333333333333333-

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

(T3A1) GG COMPRESSOR DISCHARGE LIQUID FUEL PRIMARY MANIFOLD LIQUID FUEL SECONDARY MANIFOLD TURBINE HYDRAULIC STARTER OIL RETURN TURBINE LIQUID FUEL SUPPLY (SPARE) TURBINE WATER WASH TANK TURBINE LIQUID FUEL SUPPLY FILTER TURBINE GAS FUEL FILTER GENERATOR MEGAWATT TURBINE COMP DISCHARGE (PS3B) TURBINE NOX WATER INJECTION PUMP DISCHARGE (SPARE) TURBINE LIQ FUEL METERING VALVE POSITION DEMAND (SPARE) (SPARE)

TE-8038A TE-2034 TE-2035 TE-6002 TE-2024

IN13 IN14 IN15 IN16 IN17 IN18 IN19 IN20 IN21 IN22 IN23 IN24 OUT5 OUT6 OUT7 OUT8

TYPE K TYPE K TYPE K RTD RTD TYPE K 4-20 4-20 4-20 4-20 4-20 RTD 4-20 4-20 4-20 4-20

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

13 14 15 16 17 18 19 20 21 22 23 24 5 6 7 8

W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2 W110-2

FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2FTM110.2-

15/14/16 21/20/22 27/26/28 31/32/33/34 37/38/39/40 45/44/46 54/51/52 60/57/58 66/63/64 72/69/70 78/75/76 79/80/81/82 1/2/3 4/5/6 7/8/9 10/11/12 86

+/-/SHLD +/-/SHLD +/-/SHLD X/-/+/SHLD X/-/+/SHLD +/-/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD X/-/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD -/+/SHLD GROUND

OPTION - LM2500+/LM2500 BASE ES30A/E30A PLUS / ES30/E30 BASE

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

LT-5042 PDT-2020 PDT-2063 WX PT-8004B TE-2037 ZC-2018

PACKAGE - LOCAL ANALOG INPUTS/OUTPUTS

DWG NO: 7245381-753146 REV A EC-10013 SHEET 1 OF 6, PAGE 2 OF 16

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 1

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V FUNCTION

ITEM

SOURCE/ DESTINATION

CHASSIS

IN/ OUT

CABLE

BOARD

CHANNEL NUMBER

TYPE

GE PACKAGED POWER, L.P.

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

FTM TERMINALS

TERMINAL FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** PACKAGE - LOCAL 4444444444444444-

4444444444444444-

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

ANALOG

INP UTS/OUTP UTS

(SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION) (SPARE FTM POSITION)

LPC INLET TEMPERATURE (T2A) LPC INLET TEMPERATURE (T2B) DELTA 12 DELTA 12 DELTA 12 AIR INLET FILTER AMBIENT HUMIDITY AIR INLET FILTER AMBIENT TEMPERATURE (T0) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (RESERVE) AIR INLET FILTER AMBIENT HUMIDITY AIR INLET FILTER AMBIENT TEMPERATURE (T0) LPC INLET TEMPERATURE (T2)

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 OUT1 OUT2 OUT3 OUT4

TE-8015A TE-8015B TE-8044I TE-8044J TE-8044K MT-4000 TT-4000

MT-4000 TT-4000 TE-8015

IN13 IN14 IN15 IN16 IN17 IN15 IN16 IN20 IN21 IN22 IN23 IN24 OUT5 OUT6 OUT7 OUT8

RTD RTD TYPE K TYPE K TYPE K 4-20 4-20

4-20S 4-20S 4-20S

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11 11

13 14 15 16 17 18 19 20 21 22 23 24 5 6 7 8

W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1 W111-1

FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1FTM111.1-

15/14/16 21/20/22 27/26/28 33/32/34 39/38/40 45/44/46 54/51/52 6057/58 63/62/64 72/69/70 75/74/76 84/81/82 1/2/3 4/5/6 7/8/9 10/11/12 86

W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2 W111-2

FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2FTM111.2-

13/14/15/16 19/20/21/22 27/26/28 33/32/34 39/38/40 45/44/48 54/51/52 6057/58 63/62/64 72/69/70 75/74/76 84/81/82 1/2/3 4/5/6 7/8/9 10/11/12 86

PACKAGE - LOCAL ANALOG INPUTS/OUTPUTS

GROUND X/-/+/SHLD X/-/+/SHLD X/-/+/SHLD X/-/+/SHLD X/-/+/SHLD +24V/+/SHLD +24V/+/SHLD

OPTION - LM2500+/LM2500 BASE 100 OHM PLUS / 200 OHM BASE OPTION - LM2500+/LM2500 BASE 100 OHM PLUS / 200 OHM BASE OPTION - LM2500 BASE OPTION - LM2500 BASE OPTION - LM2500 BASE OPT: WEATHER STATION OPT: WEATHER STATION

+24V/+/SHLD +24V/+/SHLD +24V/+/SHLD GROUND

OPT: WEATHER STATION CUSTOMER OUTPUT OPT: WEATHER STATION CUSTOMER OUTPUT OPT: WEATHER STATION CUSTOMER OUTPUT

DWG NO: 7245381-753146 REV A EC-10013 SHEET 1 OF 6, PAGE 3 OF 16

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 1

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V FUNCTION

ITEM

SOURCE/ DESTINATION

CHASSIS

IN/ OUT

CABLE

BOARD

CHANNEL NUMBER

TYPE

GE PACKAGED POWER, L.P.

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

FTM TERMINALS

TERMINAL FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** PACKAGE - LOCAL

555555555555-

1 2 3 4 5 6 7 8 9 10 11 12

ANALOG

INP UTS/OUTP UTS

VSV ACTUATOR TORQ MOTOR VSV LVDT EXCITATION (LEFT/RIGHT) VSV A LVDT RETURN (LEFT,SEC 1) VSV A LVDT RETURN (LEFT,SEC 2) VSV B LVDT RETURN (RIGHT,SEC 1) VSV B LVDT RETURN (RIGHT,SEC 2) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE)

FCV-8073 ZE-8073A/B ZE-8073A ZE-8073A ZE-8073B ZE-8073B

OUT OUT IN IN IN IN OUT OUT IN IN IN IN

ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG ANALOG

1 1 1 1 1 1 1 1 1 1 1 1 1

8 8 8 8 8 8 8 8 8 8 8 8 8

1 2 3 4 5 6 7 8 9 10 11 12

W108 W108 W108 W108 W108 W108 W108 W108 W108 W108 W108 W108 W108

FTM108FTM108FTM108FTM108FTM108FTM108FTM108FTM108FTM108FTM108FTM108FTM108FTM108-

2/3/1 5/6/4 8/9/7 11/12/10 14/15/13 17/18/16 20/21/22 23/24/25 26/27/28 29/30/31 32/33/34 35/36/38 37

+/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD +/-/SHLD

OPTION - LM2500+ (MIN CURRENT = MIN POSITION) OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE OPTION - LM2500+/LM2500 BASE

GROUND DATE 6/11/13 MR

REVISION LIST A ORIGINAL RELEASE

NOTE: USE "GRAY" CELL COLOR FILL IN REVISION LIST FOR CELLS THAT HAVE FORMULAS CHANGED DURING A REVISION. ===== END ====================

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

PACKAGE - LOCAL ANALOG INPUTS/OUTPUTS

DWG NO: 7245381-753146 REV A EC-10013 SHEET 1 OF 6, PAGE 4 OF 16

ITEM

111111111111111111111111111111111111-

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 2

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V

SOURCE/ DESTINATION

FUNCTION

CHASSIS IN/ OUT

*** PROPRIETARY INFORMATION *** L O C A L D I G I T A L D I S C R E T E I N P U TS / O U T P U T S

REFER TO SHEET 5 FOR NOTES

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

ES3 AVR K100/SS AVR SAS/CUSTOMER SAS/CUSTOMER A17 AVR AVR AVR VIB-SYS VIB-SYS VIB-SYS K67A K1 F&G F&G F&G F&G K230A K229A SSW1/2 ESAS,ESGR,ESTR AVR CRIT PATH CRIT PATH CRIT PATH VIB MON K85 K83 A15 K28 K5/K115 HORN VIB MON K81

LOCAL EMERGENCY STOP GEN AVR SUMMARY ALARM AUTO/MANUAL SYNC GEN MANUAL EXCITATION/AUTO AVR SELECTED RAISE XNSD SPEED (MANUAL) LOWER XNSD SPEED (MANUAL) GEN ZERO SPEED SWITCH GENERATOR EXCITATION LIMITER OPERATION GENERATOR EXCITER DIODE FAILURE GENERATOR AVR FAULT VIBRATION SUMMARY ALARM VIBRATION SUMMARY SHUTDOWN VIBRATION SYSTEM MALFUNCTION ISOC./DROOP CONTROL CRITICAL PATH SHUTDOWN FIRE/GAS MONITOR SHUTDOWN ALARM L.E.L. - TURB ROOM SHUTDOWN L.E.L. - TURB ROOM FIRE/GAS MONITOR FAILURE GEN BREAKER OPEN GEN BREAKER CLOSED TURBINE EXTERNAL OVERSPEED REMOTE EMERGENCY STOP GEN AVR EXCITATION TRIPPED DPS3/DT TRIP T48 OVERTEMP GOVERNOR SHUTDOWN VIBRATION TRIP MULTIPLY CIRCUIT BREAKER CONTROL TURBINE INGITOR CONTROL FUEL SYSTEM INITIALIZE SYNCHRONIZER ENABLE SYSTEM RESET (VIB/ESD BUS) HORN INHIBIT VIBRATION MONITOR TURBINE RUNNING /READY

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 IN16 IN17 IN18 IN19 IN20 IN21 IN22 IN23 IN24 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12

ACTION

ACTIVE SIGNAL

SWITCH WIRED

CONTROL VOLTAGE

FSLO ALARM CONTROL STATUS CONTROL CONTROL INTLK ALARM ALARM ALARM ALARM FSLO ALARM STATUS FSLO FSLO ALARM FSLO ALARM STATUS STATUS FSLO FSLO ALARM FSLO FSLO FSLO CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL STATUS

0 0 1 1/0 1 1 1 0 0 0 0 0 0 1 0 0 0 0 0 1 1 1 0 0 0 0 0 1 0/1 1# 1 1 1 1 1 1

N.O. N.C. * N.O./N.C. N.O. N.O. N.O. N.C. N.C. N.C. N.O. N.O. N.O. N.O. N.O. N.O. N.C. N.C. N.O. N.O. N.O. N.O. N.C. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.C.

+24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC

BOARD CHANNEL

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12

CABLE NUMBER

W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1 W106-1

FTM

TERMINALS

FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1FTM106.1-

1/25 2/26 3/27 4/28 5/29 6/30 7/31 8/32 9/33 10/34 11/35 12/36 13/37 14/38 15/39 16/40 17/41 18/42 19/43 20/44 21/45 22/46 23/47 24/48 K1-51/52/53 K2-54/55/56 K3-57/58/59 K4-60/61/62 K5-63/64/65 K6-66/67/68 K7-69/70/71 K8-72/73/74 K9-75/76/77 K10-78/79/80 K11-81/82/83 K12-84/85/86 TB8-49 TB9-A TB3-87 TB3-88

LOCAL DIGITAL DISCRETE INPUTS/OUTPUTS

TERMINALS FUNCTION

COMMENTS

IN/+24VDC N.O.= SHUTDOWN (PULL) IN/+24VDC IN/+24VDC * AUTO = 1, MANUAL = 0 IN/+24VDC 0 = MANUAL EXCITER; 1 = MVAR IN/+24VDC IN/+24VDC IN/+24VDC 0 RPM = 1; POWER UP CHANGES RELAY IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC 0 = DROOP; 1 = ISOC IN/+24VDC 1 = ENABLE; 0 = SHUTDOWN IN/+24VDC FIRE DET - CHANGES STATE ON POWER UP IN/+24VDC TURN ON ALL FANS IN/+24VDC SHUTDOWN UNIT-LEAVE FANS ON IN/+24VDC FIRE SYS PWR AND OK SWITCH CLOSED IN/+24VDC IN/+24VDC NOTE 6 IN/+24VDC IN/+24VDC N.O.= SHUTDOWN (PUSH) IN/+24VDC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC 0 = TRIP BKR , 1 = BKR CLOSE PERMISSIVE COM/NO/NC FOR BE-8016A & BE-8016B COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC CONTROLS HE-4050/51 +24VDC FIELD CONTACT POWER COMMON +24VDC FIELD CONTACT POWER +24VDC RELAY POWER +24VDC RELAY POWER COMMON

DWG NO: 7245381-753146 REV A EC-10013 SHEET 2 OF 6, PAGE 5 OF 16

ITEM

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 2

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V

SOURCE/ DESTINATION

FUNCTION

*** PROPRIETARY INFORMATION *** L O C A L D I G I T A L D I S C R E T E I N P U TS / O U T P U T S 111111111111111111111111111111111111-

37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66 67 68 69 70 71 72

HAND SWITCH TURBINE WATER WASH CONTROL STATION GEN DC LUBE PUMP CONTROL NOT IN AUTO POS GEN ROTOR GROUND FAULT TURBINE START TURBINE STOP MCC 50/60 Hz SELECTOR SWITCH BATTERY CHARGER FAILURE - DC BATTERY CHARGER FAILURE - AC LO BATTERY VOLTAGE BATTERY CHARGER GROUND FAULT SWGR 50/60 Hz SELECTOR SWITCH GEN 86 LOCAL TRIP START SKID MOTOR STARTER AUX CONTACT RAISE XNSD SPEED (DSM) LOWER XNSD SPEED (DSM) IGPS 52G TRIP IGPS FAULT ALARM IGPS FAILURE IGPS POWER SUPPLY ALARM LOCAL/REMOTE CONTROL SELECTION FIRE SUPPRESSANT AGENT (CO2) DISCHARGE GAS FUEL METERING VALVE DRIVER FAILURE LIQUID FUEL METERING VALVE DRIVER FAILURE NOX WATER METERING VALVE DRIVER FAILURE RAISE VOLTAGE CUSTOMER LOWER VOLTAGE CUSTOMER (RESERVE) (SPARE) VOLTAGE REGULATOR EXCITATION ON VAR SHED CONTROL VOLTAGE REGULATOR RESET SD/RESET GAS FUEL METERING VLV CONTROL SD/RESET NOX WATER METERING VLV CONTROL SD/RESET LIQUID FUEL METERING VLV CONTROL ACTUATOR MOTOR FORWARD - OPEN ACTUATOR MOTOR REVERSE - CLOSED

2222222222222222-

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

(SPARE) TURBINE/GENERATOR LUBE OIL HEAT EXCHANGER FAN A TURBINE/GENERATOR LUBE OIL HEAT EXCHANGER FAN B (SPARE) TURBINE WATER WASH PUMP TURB ENCLOSURE VENT FAN (A) TURB ENCLOSURE VENT FAN (B) (SPARE) (SPARE) (SPARE) TURBINE HYDRAULIC STARTER PUMP TURBINE WATER INJECTION PUMP TURBINE LIQUID FUEL PUMP (SPARE) (SPARE) GEN DC LUBE OIL PUMP

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

CHASSIS IN/ OUT

ACTIVE SIGNAL

SWITCH WIRED

CONTROL VOLTAGE

1 0 0 1 1 * 0 0 0 0 * 0 0 1 1 0 0 0 1 1 0 0 0 0 1 1

N.O. *N.O. N.C. N.O. N.O. N.C. N.O. N.O. N.O. N.C. N.O. N.O. N.C. N.O. N.O. N.C. N.C. N.O. N.C. N.O. N.C. N.O. N.O. N.O. N.O. N.O.

TCP TCP TCP GTG SKID GTG SKID GTG SKID

1/0 1 1 1/0 1/0 1/0 1 1

N.O./N.C. N.O. N.O. N.O. N.O. N.O. N.O. N.O.

+24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC

CONTROL CONTROL

1 1

N.O. N.O.

+125VDC +125VDC

CONTROL CONTROL CONTROL

1 1 1

N.O. N.O. N.O.

+125VDC +125VDC +125VDC

CONTROL CONTROL CONTROL

1# 1 1

N.O. N.O. N.O.

+125VDC +125VDC +125VDC

CONTROL

0

N.C.

+125VDC

ACTION

BOARD CHANNEL

CABLE NUMBER

FTM

TERMINALS

TERMINALS FUNCTION

COMMENTS

REFER TO SHEET 5 FOR NOTES HS-5005 DC STARTER RGF TSS TSS MCC CHG. CHG. CHG. CHG. SWGR SWBD MCC DSM DSM IGPS IGPS IGPS IGPS LRS PSHH-3048 ZC-2001 ZC-2018 ZC-2019 K22 K23

AVR AVR AVR ZC-2001 ZC-2019 ZC-2018 MOT-4276-1 MOT-4276-2

MOT-1076A MOT-1076B MOT-5035 MOT-4017A MOT-4017B

MOT-6015 MOT-2075 MOT-2022

MOT-0034

IN25 IN26 IN27 IN28 IN29 IN30 IN31 IN32 IN33 IN34 IN35 IN36 IN37 IN38 IN39 IN40 IN41 IN42 IN43 IN44 IN45 IN46 IN47 IN48 OUT13 OUT14 OUT15 OUT16 OUT17 OUT18 OUT19 OUT20 OUT21 OUT22 OUT23 OUT24

OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12 OUT13 OUT14 OUT15 OUT16

ALARM ALARM

STATUS ALARM ALARM CDLO ALARM STATUS FSLO CONTROL CONTROL CONTROL ALARM ALARM CDLO ALARM

AVR AVR

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 13 14 15 16 17 18 19 20 21 22 23 24

W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2 W106-2

FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2FTM106.2-

1/25 2/26 3/27 4/28 5/29 6/30 7/31 8/32 9/33 10/34 11/35 12/36 13/37 14/38 15/39 16/40 17/41 18/42 19/43 20/44 21/45 22/46 23/47 24/48 K1-51/52/53 K2-54/55/56 K3-57/58/59 K4-60/61/62 K5-63/64/65 K6-66/67/68 K7-69/70/71 K8-72/73/74 K9-75/76/77 K10-78/79/80 K11-81/82/83 K12-84/85/86 TB8-49 TB9-A TB3-87 TB3-88

IN/+24VDC FIRST SELECT WATER WASH ON KEYPAD TO USE IN/+24VDC * WIRE N.O. CONT. OF "AUTO" POSITION ON CNTRL SWITCH - 1 = AUTO POSITION (MOT-0034) IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC *50 Hz=0; 60 Hz=1 IN/+24VDC D.C. OUTPUT FAILED IN/+24VDC A.C. SUPPLY FAILED IN/+24VDC LOW BATTERY VOLTAGE IN/+24VDC BATTERY SYSTEM GROUNDED IN/+24VDC *50 Hz=0; 60 Hz=1 IN/+24VDC CONTACT OPEN WHEN 86 TRIPPED IN/+24VDC IN/+24VDC ACTIVE DURING AUTOMATIC SYNCH ONLY IN/+24VDC ACTIVE DURING AUTOMATIC SYNCH ONLY IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC 1 = REMOTE; 0 = LOCAL IN/+24VDC MAIN CO2 RELEASE ALARM & SHUT DOWN IN/+24VDC NOTE 5 IN/+24VDC NOTE 5 IN/+24VDC NOTE 5 COM/NO/NC ONLY ACTIVE WHEN IN REMOTE CONTROL (PULSE OUT) COM/NO/NC ONLY ACTIVE WHEN IN REMOTE CONTROL (PULSE OUT) COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC ACTIVATE ON NORMAL STOP COM/NO/NC COM/NO/NC 1=ENABLE; 0=SD GAS; 1-0-1 = RESET - NOTE 5 COM/NO/NC 1=ENABLE; 0=SD NOX; 1-0-1 = RESET - NOTE 5 COM/NO/NC 1=ENABLE; 0=SD LIQUID; 1-0-1 = RESET - NOTE 5 COM/NO/NC COM/NO/NC +24VDC FIELD CONTACT POWER COMMON +24VDC FIELD CONTACT POWER +24VDC RELAY POWER +24VDC RELAY POWER COMMON

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1 W107-1

FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1FTM107.1-

1/2/3 4/5/6 7/8/9 10/11/12 13/14/15 16/17/18 19/20/21 22/23/24 25/26/27 28/29/30 31/32/33 34/35/36 37/38/39 40/41/42 43/44/45 49/50/51 55 56 57 58

OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC + 24 VDC POWER + 24 VDC POWER COMMON + 24 VDC POWER + 24 VDC POWER COMMON

LOCAL DIGITAL DISCRETE INPUTS/OUTPUTS

NOTE 4 NOTE 4

OPT-NPOS-JS WAS K80

DWG NO: 7245381-753146 REV A EC-10013 SHEET 2 OF 6, PAGE 6 OF 16

ITEM

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

333333333333333333333333333333333333-

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V

SOURCE/ DESTINATION

FUNCTION

*** PROPRIETARY INFORMATION *** L O C A L D I G I T A L D I S C R E T E I N P U TS / O U T P U T S 2222222222222222-

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 2

TURBINE GAS FUEL DOWNSTREAM BLOCK VALVE TURBINE GAS FUEL UPSTREAM BLOCK VALVE / VENT VALVE TURBINE LIQUID FUEL UPSTREAM BLOCK VALVE TURBINE LIQUID FUEL DOWNSTREAM BLOCK VALVE TURBINE LIQUID FUEL PRIMARY MANIFOLD DRAIN VALVE TURBINE LIQUID FUEL SECONDARY MANIFOLD DRAIN VALVE DEMIN WATER BLOCK VALVE DOWNSTREAM / UPSTREAM TURB WATER WASH OFF-LINE SUPPLY ENABLE VALVE IGPS POWER SELECT 50 Hz IGPS POWER SELECT 60 Hz MTTB1 CABINET COOLING MGTB1 CABINET COOLING TURBINE HYDRAULIC STARTER OIL TANK HEATER GENERATOR LUBE OIL TANK TURBINE LUBE OIL TANK (SPARE)

SOV-2004 SOV-2006/2008 SOV-2012 SOV-2018 SOV-2009 SOV-2010 SOV-2017/2016 SOV-5032 IGPS1 IGPS2 K347 K365 HE-6010 HE-0005 HE-1004

MCC_GFEP (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE)

AMBIENT ICING CONDITIONS EXIST

CUSTOMER (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE)

ACTION

ACTIVE SIGNAL

SWITCH WIRED

CONTROL VOLTAGE

BOARD CHANNEL

CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL CONTROL

(1#) 1# 1# (1#) 1 1 1# 1# 0 0 1 1 0 0 0 0

N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O. N.O.

+24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +125VDC +125VDC +125VDC +24VDC

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

7 7 7 7 7 7 7 7 7 7 7 7 7 7 7 7

17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

+24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC +24VDC 120 VAC 120 VAC

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13 13

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 1 2 3 4 5 6 7 8 9 10 11 12

CABLE NUMBER

TERMINALS FUNCTION

FTM

TERMINALS

W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2 W107-2

FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2FTM107.2-

1/2/3 4/5/6 7/8/9 10/11/12 13/14/15 16/17/18 19/20/21 22/23/24 25/26/27 28/29/30 31/32/33 34/35/36 37/38/39 40/41/42 43/44/45 49/50/51 55 56 57 58

OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+24VDC OUT/+125VDC OUT/+125VDC OUT/+125VDC OUT/+24VDC + 24 VDC POWER + 24 VDC POWER COMMON + 24 VDC POWER + 24 VDC POWER COMMON

W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1 W113-1

FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1FTM113.1-

1/25 2/26 3/27 4/28 5/29 6/30 7/31 8/32 9/33 10/34 11/35 12/36 13/37 14/38 15/39 16/40 17/41 18/42 19/43 20/44 21/45 22/46 23/47 24/48 K1-51/52/53 K2-54/55/56 K3-57/58/59 K4-60/61/62 K5-63/64/65 K6-66/67/68 K7-69/70/71 K8-72/73/74 K9-75/76/77 K10-78/79/80 K11-81/82/83 K12-84/85/86 49 50 56 57 58

IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC IN/+24VDC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC COM/NO/NC +24VDC FIELD POWER +24VDC FIELD POWER COMMON + 24 VDC POWER COMMON + 24 VDC POWER + 24 VDC POWER COMMON

COMMENTS

REFER TO SHEET 5 FOR NOTES

(SPARE) (SPARE) (SPARE) (SPARE) HEAT TRACING GROUND FAULT

CHASSIS IN/ OUT

OUT17 OUT18 OUT19 OUT20 OUT21 OUT22 OUT23 OUT24 OUT25 OUT26 OUT27 OUT28 OUT29 OUT30 OUT31 OUT32

IN1 IN2 IN3 IN4 IN5 IN6 IN7 IN8 IN9 IN10 IN11 IN12 IN13 IN14 IN15 IN16 IN17 IN18 IN19 IN20 IN21 IN22 IN23 IN24 OUT1 OUT2 OUT3 OUT4 OUT5 OUT6 OUT7 OUT8 OUT9 OUT10 OUT11 OUT12

STATUS

1

N.O.

0

N.O.

ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE TO CLOSE VALVE ENERGIZE IF MCC SELECTOR SWITCH IS ON 50 Hz ENERGIZE IF MCC SELECTOR SWITCH IS ON 60 Hz CONTROLS MOT-4019 CONTROLS MOT-4036 TRIP HEATER POWER WHEN LEVEL TRANSMITTER INDICATES LOW TRIP HEATER POWER WHEN LEVEL TRANSMITTER INDICATES LOW TRIP HEATER POWER WHEN LEVEL TRANSMITTER INDICATES LOW

OPT: WINTERIZATION HEAT TRACING

OPT:POSSIBLE ICING CONDITIONS WHEN INDICATED

( ) IN ACTIVE SIGNAL COL. = POWER GROUND RETURN THRU SAFETY MODULE. % IN THE TRIP POINT COLUMN = TUNABLE TRIP POINT (#1) IN ACTIVE SIGNAL COL.= RETURN WIRED THRU A15 SAFETY CIRCUIT.

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

LOCAL DIGITAL DISCRETE INPUTS/OUTPUTS

DWG NO: 7245381-753146 REV A EC-10013 SHEET 2 OF 6, PAGE 7 OF 16

ITEM

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 2

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option R

SIGNAL

E V

SOURCE/ DESTINATION

FUNCTION

*** PROPRIETARY INFORMATION *** L O C A L D I G I T A L D I S C R E T E I N P U TS / O U T P U T S

A

CHASSIS IN/ OUT

ACTION

ACTIVE SIGNAL

SWITCH WIRED

CONTROL VOLTAGE

BOARD CHANNEL

CABLE NUMBER

FTM

TERMINALS

TERMINALS FUNCTION

COMMENTS

REFER TO SHEET 5 FOR NOTES

REVISION LIST ORIGINAL RELEASE

DATE 6/11/13 MR

NOTE: USE "GRAY" CELL COLOR FILL IN REVISION LIST FOR CELLS THAT HAVE FORMULAS CHANGED DURING A REVISION. ===== END ====================

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

LOCAL DIGITAL DISCRETE INPUTS/OUTPUTS

DWG NO: 7245381-753146 REV A EC-10013 SHEET 2 OF 6, PAGE 8 OF 16

R ITEM

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option

E V

NETWORK FUNCTION

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 3

DEVICE CONTROLLED

IN/ OUT

TYPE

NODE LOCATION

NODE CHANNEL

NODE

TERMINALS

TERMINALS FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** DI S T RI BUT I VE ANALO G I NP UT S 111111-

1 2 3 4 5 6

TURB ROOM PRESSURE TURBINE LUBE OIL SUPPLY PRESS TURBINE SCAVENGE DISCHARGE PRESS DE-MIN WATER SUPPLY PRESS GAS FUEL SUPPLY PRESSURE MGTB1 AC AMBIENT HEAT SINK TEMP

PDT-4007 PT-1021 PT-1022 PT-2098 PT-2027 TE-4036A

IN IN IN IN IN IN

4-20 4-20 4-20 4-20 4-20 4-20

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

1 1 1 1 1 1 1 1

1 2 3 4 5 6

N101N101N101N101N101N101N101N101N101-

4/5/7 8/9/11 12/13/15 16/17/19 20/21/23 25/26/27 2 3 1

+24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

222222-

1 2 3 4 5 6

TURBINE LUBE OIL TANK LEVEL TURBINE LUBE OIL SUPPLY FILTER PRESSURE GAS FUEL MANIFOLD PRESS TURB VG PUMP HYDRAULIC OIL FILTER PRESSURE TURBINE LUBE OIL SCAVENGE FILTER PRESSURE LIQUID FUEL PUMP DISCHARGE PRESSURE

LT-1002 PDT-1006 PT-2028 PDT-1014 PDT-1007 PT-2070

IN IN IN IN IN IN

4-20 4-20 4-20 4-20 4-20 4-20

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

2 2 2 2 2 2 2 2

1 2 3 4 5 6

N102N102N102N102N102N102N102N102N102-

4/5/7 8/9/11 12/13/15 16/17/19 20/21/23 24/25/27 2 3 1

+24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24VDC POWER +24VDC POWER COM GROUND

333333-

1 2 3 4 5 6

MGTB1 AC CABINET HEAT SINK TEMP TURBINE COMPRESSOR INLET PRESSURE (P2) TURBINE THRUST BALANCE PISTON CAVITY PRESSURE MTTB1 AC AMBIENT HEAT SINK TEMP MTTB1 AC CABINET HEAT SINK TEMP (SPARE)

TE-4036B PT-8024 PT-8061 TE-4019A TE-4019B

IN IN IN IN IN IN

4-20 4-20 4-20 4-20 4-20 4-20

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

3 3 3 3 3 3 3 3

1 2 3 4 5 6

N103N103N103N103N103N103N103N103N103-

5/6/7 8/9/11 12/13/15 17/18/19 21/22/23 24/25/27 2 3 1

+/-/SHLD +24V/+/SHLD +24V/+/SHLD +/-/SHLD +/-/SHLD +24V/+/SHLD +24VDC POWER +24VDC POWER COM GROUND

444444-

1 2 3 4 5 6

TURBINE ACC GB SCAVANGE OIL TEMP A TURBINE SUMP A SCAVANGE OIL TEMP A TURBINE SUMP B SCAVANGE OIL TEMP A TURBINE SUMP C SCAVANGE OIL TEMP A TURBINE SUMP D SCAVANGE OIL TEMP A TURBINE SUPPLY TEMP A

TE-1023A TE-1024A TE-1025A TE-1026A TE-1027A TE-1028A

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

5 5 5 5 5 5 5 5

1 2 3 4 5 6

N105N105N105N105N105N105N105N105N105-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

555555-

1 2 3 4 5 6

GENERATOR LUBE OIL SUPPLY TEMP GENERATOR JOURNAL BEARING METAL (DE) TEMP GENERATOR BEARING OIL DRAIN (DE) TEMP GENERATOR JOURNAL BEARING METAL (NDE) TEMP GENERATOR BEARING OIL DRAIN (NDE) TEMP GENERATOR LUBE OIL TANK TEMP

TE-0025 TE-0021A TE-0036 TE-0023A TE-0035 TE-0020

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MGTB MGTB MGTB MGTB MGTB MGTB 24+3 24+3COM

2 2 2 2 2 2 2 2

6 6 6 6 6 6 6 6

1 2 3 4 5 6

N206N206N206N206N206N206N206N206N206-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

DISTRIBUTIVE ANALOG INPUTS

OPTION - LM2500+ 50 DEG C - THERMAL FUSE, MOT-4019 MOT-4019

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 3 OF 6 PAGE 9 OF 16

R ITEM

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option

E V

NETWORK FUNCTION

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 3

DEVICE CONTROLLED

IN/ OUT

TYPE

NODE LOCATION

NODE CHANNEL

NODE

TERMINALS

TERMINALS FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** DI S T RI BUT I VE ANALO G I NP UT S

666666-

1 2 3 4 5 6

GENERATOR STATOR WINDING PHASE T1 (RTD 1A) GENERATOR STATOR WINDING PHASE T2 (RTD 2A) GENERATOR STATOR WINDING PHASE T3 (RTD 3A) GENERATOR STATOR WINDING PHASE T1 (RTD 4A) GENERATOR STATOR WINDING PHASE T2 (RTD 5A) GENERATOR STATOR WINDING PHASE T3 (RTD 6A)

TE-4021A TE-4022A TE-4023A TE-4024A TE-4025A TE-4026A

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MGTB MGTB MGTB MGTB MGTB MGTB 24+3 24+3COM

2 2 2 2 2 2 2 2

7 7 7 7 7 7 7 7

1 2 3 4 5 6

N207N207N207N207N207N207N207N207N207-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

777777-

1 2 3 4 5 6

TURBINE ACC GB SCAVENGE OIL TEMP B TURBINE SUMP A SCAVENGE OIL TEMP B TURBINE SUMP B SCAVENGE OIL TEMP B TURBINE SUMP C SCAVENGE OIL TEMP B TURBINE SUMP D SCAVENGE OIL TEMP B TURBINE SUPPLY TEMP B

TE-1023B TE-1024B TE-1025B TE-1026B TE-1027B TE-1028B

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

8 8 8 8 8 8 8 8

1 2 3 4 5 6

N108N108N108N108N108N108N108N108N108-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

888888-

1 2 3 4 5 6

GENERATOR AIR OUTLET TEMP A GENERATOR EXCITER AIR OUTLET TEMP A GENERATOR BEARING THRUST PAD INBOARD A GENERATOR AIR OUTLET TEMP B GENERATOR EXCITER AIR OUTLET TEMP B GENERATOR BEARING THRUST PAD INBOARD B

TE-4030A TE-4031A TE-0057A TE-4030B TE-4031B TE-0057B

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MGTB MGTB MGTB MGTB MGTB MGTB 24+3 24+3COM

2 2 2 2 2 2 2 2

9 9 9 9 9 9 9 9

1 2 3 4 5 6

N209N209N209N209N209N209N209N209N209-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

999999-

1 2 3 4 5 6

TURBINE ENCLOSURE ROOM TEMP TURBINE ENCLOSURE EXHAUST TEMP TURBINE GAS FUEL SUPPLY TEMP TURBINE HYDRAULIC STARTER CLUTCH OIL A TURBINE HYDRAULIC STARTER CLUTCH OIL B TURBINE AIR FILTER INLET TEMP

TE-4002 TE-4054 TE-2032 TE-6027A TE-6027B TE-4082

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

10 10 10 10 10 10 10 10

1 2 3 4 5 6

N110N110N110N110N110N110N110N110N110-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

101010101010-

1 2 3 4 5 6

GENERATOR STATOR WINDING PHASE T1 (RTD 1B) GENERATOR STATOR WINDING PHASE T2 (RTD 2B) GENERATOR STATOR WINDING PHASE T3 (RTD 3B) GENERATOR STATOR WINDING PHASE T1 (RTD 4B) GENERATOR STATOR WINDING PHASE T2 (RTD 5B) GENERATOR STATOR WINDING PHASE T3 (RTD 6B)

TE-4021B TE-4022B TE-4023B TE-4024B TE-4025B TE-4026B

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MGTB MGTB MGTB MGTB MGTB MGTB 24+3 24+3COM

2 2 2 2 2 2 2 2

12 12 12 12 12 12 12 12

1 2 3 4 5 6

N212N212N212N212N212N212N212N212N212-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

DISTRIBUTIVE ANALOG INPUTS

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 3 OF 6 PAGE 10 OF 16

R ITEM

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option

E V

NETWORK FUNCTION

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 3

DEVICE CONTROLLED

IN/ OUT

TYPE

NODE LOCATION

NODE CHANNEL

NODE

TERMINALS

TERMINALS FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** DI S T RI BUT I VE ANALO G I NP UT S 111111111111-

1 2 3 4 5 6

GENERATOR LUBE OIL TANK LEVEL GENERATOR LUBE OIL SUPPLY PRESSURE GENERATOR LUBE OIL FILTER PRESSURE GENERATOR INLET AIR FILTER (DRIVE END) PRESSURE GENERATOR INLET AIR FILTER (NON-DRIVE END) PRESSURE MGTB1 ENCLOSURE TEMP.

LT-0001 PT-0026 PDT-0015 PDT-4008 PDT-4009 TE-4091

IN IN IN IN IN IN

4-20 4-20 4-20 4-20 4-20 4-20

MGTB MGTB MGTB MGTB MGTB MGTB 24+3 24+3COM

2 2 2 2 2 2 2 2

17 17 17 17 17 17 17 17

1 2 3 4 5 6

N217N217N217N217N217N217N217N217N217-

4/5/7 8/9/11 12/13/15 16/17/19 20/21/23 25/26/27 2 3 1

+24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +24V/+/SHLD +/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

121212121212-

1 2 3 4 5 6

MAGNETIC CHIP DETECTOR SUMP A MAGNETIC CHIP DETECTOR SUMP B MAGNETIC CHIP DETECTOR SUMP C MAGNETIC CHIP DETECTOR SUMP D MAGNETIC CHIP DETECTOR ACCESSORY GEARBOX MTTB1 ENCLOSURE TEMP.

MCD-1061 MCD-1062 MCD-1063 MCD-1064 MCD-1060 TE-4090

IN IN IN IN IN IN

RTD RTD RTD RTD RTD RTD

MTTB MTTB MTTB MTTB MTTB MTTB 24+3 24+3COM

1 1 1 1 1 1 1 1

19 19 19 19 19 19 19 19

1 2 3 4 5 6

N119N119N119N119N119N119N119N119N119-

4/5/6/7 8/9/10/11 12/13/14/15 16/17/18/19 20/21/22/23 24/25/26/27 2 3 1

SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD SENSE/+/-/SHLD +24VDC POWER +24VDC POWER COM GROUND

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

DISTRIBUTIVE ANALOG INPUTS

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 3 OF 6 PAGE 11 OF 16

R ITEM

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option

E V

NETWORK FUNCTION

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 3

DEVICE CONTROLLED

IN/ OUT

TYPE

NODE LOCATION

NODE CHANNEL

NODE

TERMINALS

TERMINALS FUNCTION

COMMENTS

*** PROPRIETARY INFORMATION *** DI S T RI BUT I VE ANALO G I NP UT S

A

REVISION LIST ORIGINAL RELEASE

DATE 6/11/13 MR

NOTE: USE "GRAY" CELL COLOR FILL IN REVISION LIST FOR CELLS THAT HAVE FORMULAS CHANGED DURING A REVISION. ===== END ====================

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

DISTRIBUTIVE ANALOG INPUTS

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 3 OF 6 PAGE 12 OF 16

SH 4 R ITEM

NETWORK

*** PROPRIETARY INFORMATION *** DISTRIBUTIVE DISCRETE INPUTS 1111111111111111-

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

© Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option

E V FUNCTION

VIBRATION SWITCH HIGH-TURB/GEN LUBE OIL HEAT EXCHANGER FAN (MOT-1076A) VIBRATION SWITCH HIGH-TURB/GEN LUBE OIL HEAT EXCHANGER FAN (MOT-1076B) PRESSURE SWITCH HIGH FIRE SUPPRESSANT AGENT DISCHARGE (DOWNSTREAM) POSITION SWITCH TURBINE ENCLOSURE VENTILATION FAN INLET DAMPER A POSITION SWITCH TURBINE ENCLOSURE VENTILATION FAN INLET DAMPER B MCC LOSS OF POWER DEVICE EARTHING SWITCH STATUS INDICATOR LIMIT SWITCH 85 DEGREE BY-PASS DAMPER OPENED (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE) (SPARE)

GE PACKAGED POWER, L.P.

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL

SIGNAL SOURCE

ACTIVE CONTACT NODE SIGNAL USED LOCATION

NODE CHANNEL

NODE TERMINALS

COMMENTS

N340N340N340N340N340N340N340N340N340N340N340N340N340N340N340N340-

NOTE 4 NOTE 4 ALARM INDICATOR ONLY DAMPER STATUS INDICATOR F&C - FOR ALTAIR USE ZSC-4158A DAMPER STATUS INDICATOR F&C - FOR ALTAIR USE ZSC-4158B UNDER VOLTAGE STATUS

REFER TO SHEET 5 FOR NOTES XSH-1076A XSH-1076B PSH-3048A ZSC-4266A ZSC-4266B (27) DEVICE +MESW ZSC-4276 ZSO-4276

1 1 1 1 1 1 1 1 1

N.O. N.O. N.O. N.C. N.C. N.O. N.O. N.O. N.O.

TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP TCP

3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

REVISION LIST A ORIGINAL RELEASE

40 40 40 40 40 40 40 40 40 40 40 40 40 40 40 40

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16

10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25

DAMPER STATUS INDICATOR (ONLY FOR F&C) DAMPER STATUS INDICATOR (ONLY FOR F&C)

DATE 6/11/13 MR

NOTE: USE "GRAY" CELL COLOR FILL IN REVISION LIST FOR CELLS THAT HAVE FORMULAS CHANGED DURING A REVISION. ===== END ====================

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

DISTRIBUTIVE DISCRETE INPUTS

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 4 OF 6 PAGE 13 OF 16

SITE: ECOPETROL SH 5

WORKSHEET, CONTROL SYSTEM

GE PACKAGED POWER, L.P.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option © Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

R E V *** PROPRIETARY INFORMATION *** WORKSHEET NOTES ACTION CODES: FSWM = FAST STOP WITH MOTOR FSLO = FAST STOP LOCKOUT WITHOUT MOTOR F-SD = FAST SHUTDOWN CDLO = COOL DOWN LOCKOUT CDNLO = COOL DOWN NON-LOCKOUT INTLK = INTERLOCK SD/STSY = SHUTDOWN STEAM SYSTEM ONLY SML = SLOW DECEL TO MIN LOAD SDTI = STEP DECEL TO IDLE STATUS = STATUS OF I/O POINT CONTROL = INPUT OR OUTPUT REQUIRED TO CONTROL A DEVICE OR FUNCTION. ALARM = AUDIO AND VISUAL INDICATION OF A FAULT CONDITION. ST/FSLO = STATUS OR FAST STOP LOCKOUT

NOTES: 1. "S" AFTER 4-20 IN TYPE COLUMN INDICATES 4-20 IS SOURCED FROM ANOTHER DEVICE. ALL OTHER INPUTS HAVE LOOP POWERED DEVICES. 2. # IN ACTIVE SIGNAL COLUMN = POWER TO RELAY TO BE REMOVED IF CRITICAL SHUTDOWN PATH TRIPPED. 3. ( ) IN ACTIVE SIGNAL COLUMN = RETURN WIRED THRU A15 SAFETY CIRCUIT. 4. WHEN THE VIBRATION SWITCH IS CLOSED (ie TRUE) = ALARM AND SWITCH OVER TO THE OTHER FAN (MOT-1076A / MOT-1076B) WHILE THE FAN UNDER FAULT CONDITION IS SHUT DOWN. 5. a. FUEL VALVE DRIVER FAILURE WILL RETURN THE FUEL VALVE TO MIN. POSITION. IF ONLY ONE FUEL IS BEING USED WHEN DRIVER FAILURE OCCURS = FSWM b. IF MORE THEN ONE FUEL IS USED AT A TIME, SHUTDOWN THE FUEL SYSTEM WITH THE BAD DRIVER AND ALARM. c. TO RESET FUEL DRIVER, DE-ENERGIZE AND RE-ENERGIZE "SD/RESET" OUTPUT FOR THE PARTICULAR FUEL DRIVER THAT NEEDS RESETTING AFTER THE FUEL SYSTEM FOR THAT DRIVER IS SHUTDOWN. 6. 1 = CONTACT CLOSED WHEN BREAKER CLOSED. - THIS INPUT ALSO USED FOR LOAD SHARE STATUS.

A

REVISION LIST INITIAL RELEASE

DATE 6/11/13 MR

===== END ====================

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

WORKSHEET NOTES

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 5 OF 6 PAGE 14 OF 16

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 6

GE PACKAGED POWER, L.P.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option © Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

R E V *** PROPRIETARY INFORMATION *** &

EFFECT

MATRIX OL LA RM AC ER TI A N M ON N -S UN TA SM C IA RT LTI TU SL ON OW RB AL IN M T EP O -A MI NN ER N M UN LO CI A AT D SH EB UT IT DN ID FA IL UR E

CAUSE

-A AL M

SH UT DO W

N

CAUSE AND EFFECT MATRIX

SP

MALFUNCTION

/C ON TR

VIBRATION

INITIATING DEVICE NOTE

1

2

3500 Rack

Vibration Malfunction Signal Active

1

X

X

3500 Rack

(Vibration Malfunction Signal Active and one or more of the following bits true below)

2

X

3500 Com Port

Removal of the Rack Interface Module from the 3500 rack OR Plugging a module in the rack during self-test OR Hardware failure in the rack OR Configuration file downloaded to rack OR Any module in the 3500 rack which has detected a fault. "Summary Vibration System Malfunction Alarm."

Device

SERVICE DESCRIPTION

3500 Com Port 44 Aero Card

25 Key Phasor Card

40 Prox Card

3500 Com Port 3500 Com Port 3500 Com Port 20 Card 92 Card 44 Card 25 Card 40 Card 32 Card 42 Card

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

Bit Number

Transducer going not OK (with the exception of the on-engine accelerometers) OR OK Circuit Checks to the AIM and Back Summary of 4 channels on 44 Aero Card 44 Channel 1 44 Channel 2 44 Channel 3 44 Channel 4 44 Channels 1 to 4 failed Summary of 2 channels on 25 KP card 25 Channel 1 25 Channel 2 Summary of 4 channels on 40 Card 40 Channel 1 40 Channel 2 40 Channel 3 40 Channel 4 Keyphasor < 1 rpm, Channel 1 or 2 Keyphasor > 99,999 rpm Channel 1 or 2 Config failure OR Slot ID Failure OR Voltage Node Failures 20 Card Config Fail 92 Card Config Fail 44 Aero Card Config Fail 25 KP Card Config Fail 40 Prox Card Config Fail 32 Relay Card Config Fail 42 Seismic Card Config Fail

ACTION

10001 OR 13685

3

4

X

X

X

X X X X X X X

10613 10621 10033 10869 10877 10885 10893 10613 10621

X X X X X X X X X X X X X X X X

10009 10015 10021 10027 10033 10045 10063

X X X X X X X

10021 10357 10365 10373 10381 10357, 365, 373, 381

3

4

VIBRATION MALFUNCTION CAUSE EFFECT MATRIX

X

X X X X X X X X X

X

NOTES 1.

IMMEDIATELY ALARM AND ANNUNCIATE VIBRATION FOR START PERMISSIVE.

2.

WAIT 2 S FOR FOLLOW UP BIT TO BE RECEIVED FROM COMMUNICATION PORT, THEN ANNUNCIATE IDENTIFIED VIBRATION SYSTEM FAILED PARAMETER

3.

IF ALL 4 EACH 44 AERO CHANNELS FAIL (LOGICAL AND), ANNUNCIATE ALARM "TURBINE VIBRATION SYSTEM CHANNELS FAILED, 10 MINUTE WINDOW TO RESET ALARM BEFORE SML INITIATED" IF ALL 4 CHANNELS STAY FAILED AND NOT RESET IN 10 MINUTES, INITIATE SHUTDOWN, tunable * 10 s to 1 h

X X X X X X X

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 6 OF 6 PAGE 15 OF 16

WORKSHEET, CONTROL SYSTEM

SITE: ECOPETROL SH 6

GE PACKAGED POWER, L.P.

TM2500 - MICRONET PLUS CONTROL - System 50 Deg C Option © Copyright 2013 GE Packaged Power, L.P. All rights reserved. This drawing is the proprietary information of GE Packaged Power, L.P. and is loaned in strict confidence with the understanding that it will not be reproduced nor used for any purpose except that for which it is loaned. It shall be immediately returned on demand and is subject to all other terms and conditions of any written agreement or purchase order that incorporates or relates to this drawing.

R E V *** PROPRIETARY INFORMATION *** VIBRATION

A

MALFUNCTION

CAUSE

&

EFFECT

MATRIX

REVISION LIST ORIGINAL RELEASE

DATE 6/11/13 MR

===== END ====================

ORIGINATED: 06/11/13 PRINTED: 6/26/2013 2:32 PM REV DATE: NA

VIBRATION MALFUNCTION CAUSE EFFECT MATRIX

DWG NO: 7245381-753146 REV: A EC-10013 SHEET 6 OF 6 PAGE 16 OF 16

GE PACKAGED POWER, L.P.

CUSTOMER: ECOPETROL

©Copyright, 2013, GE Packaged Power, L.P., All Rights. Reserved.

CAUSE AND EFFECT MATRIX HYDRAULIC STARTER SYSTEM

SITE: COLOMBIA

This Drawing Is The Proprietary Information Of Ge Packaged Power, L.P., And Is Loaned In Strict Confidence With The Understanding That It Will Not Be Reproduced Nor Used For Any Purpose Except That For Which It Is Loaned. It Shall Be Immediately Returned On Demand, and Is Subject To All Other Terms and Conditions Of Any Written Agreement Or Purchase Order Which Incorporates Or Relates To This Drawing.

IMS-2013 - TM029 - TM2500 / TM2500+

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW

RANGE HIGH

LIMIT DECR.

LIMIT INCR.

ENGLISH UNIT

RANGE LOW

RANGE HIGH

LIMIT DECR.

LIMIT INCR.

METRIC UNIT

RANGE MULT.

ACTION

0

100

-2

102

%

0

100

-2

102

%

x10

SF

95

%

95

%

x10

%

x10

LAL

1, 6

%

x10

LALL

2, 3

1

LT-6001

LEVEL TRANSMITTER-TURBINE HYDRAULIC STARTER OIL TANK

2

LT-6001

LEVEL TRANSMITTER-TURBINE HYDRAULIC STARTER OIL TANK

3

LT-6001

LEVEL TRANSMITTER-TURBINE HYDRAULIC STARTER OIL TANK

74

%

74

4

LT-6001

LEVEL TRANSMITTER-TURBINE HYDRAULIC STARTER OIL TANK

40

%

40

NOTE

ALARM

ALARM DELAY (S)

SHUT DOWN

ABORT START

X

LAH

START PERM

CRANK PERM

X

X

MOTORS

HEATERS

HE-6010 OFF

VALVES

COMMENTS

X X

X

X

MOT-6015 PERM

X

X

MOT-6015 OFF

SHUTDOWN OF START SYSTEM

MOT-6015 OFF

SHUTDOWN OF START SYSTEM

5 6

TE-6002

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL RETURN

7

TE-6002

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL RETURN

8

TE-6002

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL RETURN

10

TE-6003

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

11

TE-6003

12 13

-40

400

-48

408 180

40

DEG F

-40

204

-44

DEG F

DEG C

x10

SF

X

DEG C

x10

TAH

X

DEG C

x10

TAL

X

209

DEG C

x10

SF

X

209 82

DEG F

4

9 408

DEG F

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

190

DEG F

88

DEG C

x10

TAHH

2, 3

TE-6003

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

190

DEG F

88

DEG C

x10

TAHH

4

TE-6003

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

180

DEG F

82

DEG C

x10

TAH

14

TE-6003

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

35

DEG C

x10

EVENT

6

15

TE-6003

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

90

DEG F

32

DEG C

x10

EVENT

6

16

TE-6003

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

70

DEG F

21

DEG C

x10

TAL

-40

400

-48

95

-40

204

-44

DEG F

X

X

X

X

X

X

X

X

X HE-6010 OFF HE-6010 ON X

17 18

HE-6010

HEATER ELEMENT-TURBINE HYDRAULIC STARTER OIL TANK

6

MOT-6015

MOTOR-TURBINE HYDRAULIC STARTER PUMP

7

TRIP HEATER POWER WHEN LEVEL TRANSMITTER INDICATES LOW

19 20

MOT-1076A/B ON

21 22

MOT-1076A MOTOR-TURBINE/GENERATOR LUBE OIL HEAT EXCHANGER FAN

23

MOT-1076B MOTOR-TURBINE/GENERATOR LUBE OIL HEAT EXCHANGER FAN

5 5

24 25

XSH-1076A VIBRATION SWITCH HIGH-TURBINE/GENERATOR LUBE OIL HEAT EXCHANGER FAN

XAH

5

X

SHUTDOWN FAN - ACTIVATE ALTERNATE FAN

26

XSH-1076B VIBRATION SWITCH HIGH-TURBINE/GENERATOR LUBE OIL HEAT EXCHANGER FAN

XAH

5

X

SHUTDOWN FAN - ACTIVATE ALTERNATE FAN

27 28

SOV-6019

SOLENOID OPERATED VALVE-TURBINE HYDRAULIC STARTER PUMP PISTON

0

100

-40

400

%

0

100

204

-44

%

x10

29 30

TE-6027A

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

408

DEG F

209

DEG C

x10

SF

31

TE-6027A

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

230

DEG F

110

DEG C

x10

TAHH

X

32

TE-6027A

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

-48

200

DEG F

93

DEG C

x10

TAH

X

33

TE-6027A

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

34

TE-6027B

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

408

DEG F

35

TE-6027B

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

230

DEG F

36

TE-6027B

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

37

TE-6027B

TEMPERATURE ELEMENT-TURBINE HYDRAULIC STARTER CLUTCH OIL DRAIN

40 -40

400

-48

DEG F

200 40

-40

204

-44

DEG F DEG F

DEG C

4 -40

TAL

FSLO

X

209

DEG C

x10

SF

X

110

DEG C

x10

TAHH

X

DEG C

x10

TAH

X

DEG C

x10

TAL

X

93 4

x10

X

FSLO

38 39

ORIGINATED: 09/02/2013 PRINTED: 11/03/2014 03:11 p. m. REV DATE: NA

CAUSE AND EFFECT MATRIX HYDRAULIC STARTER SYSTEM

GE CLASS II (INTERNAL) DWG NO: 7245381-752149 REV: A EC-11200 SHEET 1 OF 12 PAGE 1 OF 2

GE PACKAGED POWER, L.P.

CUSTOMER: ECOPETROL

©Copyright, 2013, GE Packaged Power, L.P., All Rights. Reserved.

CAUSE AND EFFECT MATRIX HYDRAULIC STARTER SYSTEM

SITE: COLOMBIA

This Drawing Is The Proprietary Information Of Ge Packaged Power, L.P., And Is Loaned In Strict Confidence With The Understanding That It Will Not Be Reproduced Nor Used For Any Purpose Except That For Which It Is Loaned. It Shall Be Immediately Returned On Demand, and Is Subject To All Other Terms and Conditions Of Any Written Agreement Or Purchase Order Which Incorporates Or Relates To This Drawing.

IMS-2013 - TM029 - TM2500 / TM2500+

LINE

REV

TAG NO.

PROCESS DESCRIPTION

RANGE LOW

RANGE HIGH

LIMIT DECR.

LIMIT INCR.

ENGLISH UNIT

RANGE LOW

RANGE HIGH

LIMIT DECR.

LIMIT INCR.

METRIC UNIT

RANGE MULT.

ACTION

NOTE

ALARM

ALARM DELAY (S)

SHUT DOWN

ABORT START

START PERM

CRANK PERM

MOTORS

HEATERS

VALVES

COMMENTS

NOTES 1. PART OF AUXILIARY CHECK SEQUENCE, MUST BE OUT OF ALARM TO GRANT PERMISSION. 2. SHUTDOWN START SYSTEM 3. ACTIVE ONLY DURING STARTUP BY START SYSTEM 4. ACTIVE WHEN START SYSTEM DORMENT 5. HYDRAULIC START & TURBINE / GENERATOR LUBE OIL FANS a. IF FAN SELECTED AND WHEN UNIT RUNNING, RUN b. IF FAN SELECTED AND GENERATOR NOT AT ZERO SPEED, RUN c. INTENTIONALLY LEFT BLANK. d. IF FAN SELECTED FAN RUNNING HAS A VIBRATION ALARM, SWAP SELECT TO BACKUP FAN. 6. HYDRAULIC STARTER OIL TANK HEATER a. ON: TE6003 < 90 DEG. F. b. OFF: TE6003 > 95 DEG. F OR LT6001 < 74% 7. WHEN STARTER HIGH SPEED START COMMAND IS REMOVED OR NOTED SHUTDOWNS FOR ANY REASON, WAIT 10 SEC. TO ALLOW PUMP TO RESET TO NEUTRAL POSITION BEFORE DE-ENERGIZING HYD START MOTOR.

LEGEND 1. SEE LEGEND TAB

A

REVISION LIST

DATE

ORIGINAL ISSUE

9/02/2013 HCL

=== END ===

ORIGINATED: 09/02/2013 PRINTED: 11/03/2014 03:11 p. m. REV DATE: NA

CAUSE AND EFFECT MATRIX HYDRAULIC STARTER SYSTEM

GE CLASS II (INTERNAL) DWG NO: 7245381-752149 REV: A EC-11200 SHEET 1 OF 12 PAGE 2 OF 2

Tab C

Tab D

View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF