Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 1
ABB Power Technologies AB Västerås - Sweden
•
REC670 Product Integration Training Course
The structure of your project shown by CCT should look like this
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 2
ABB Power Technologies AB Västerås - Sweden
Data Set Engineering
REC670 Product Integration Training Course
•
Navigate your “REC670” object down to LD0/LLN0 level:
•
Add a new data set into LLN0 and rename it to “GOOSE”.
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 3
ABB Power Technologies AB
REC670 Product Integration Training Course Click/select on ”GOOSE” dataset. Under “IED Data Model” browse and select the signals you want to add :
Västerås - Sweden
•
-reservation request:
-acknow. the reservation request
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 4
ABB Power Technologies AB Västerås - Sweden
REC670 Product Integration Training Course
-apparatus position QB1+QB2
QB2
QB1
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 5
ABB Power Technologies AB
•
REC670 Product Integration Training Course The complete GOOSE dataset for Line bay should look like this:
•
Create GOOSE dataset for Bus Coupler bay.
•
Add resp. signals from ”IED Data Model” :
Västerås - Sweden
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 6
ABB Power Technologies AB Västerås - Sweden
REC670 Product Integration Training Course
GOOSE Control Engineering • Define a GOOSE control block and insert your dataset. (have remain on the same level in the project structure)
•
Click on Goose Control Engineering and then on GSE Control
•
Associate your GOOSE dataset to this NewGSEControl:
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 7
ABB Power Technologies AB
REC670 Product Integration Training Course
Västerås - Sweden
•
Click on
• •
Save Do the same procedure for BusCouplers IED.:
•
Define a new MAC Address of your GOOSE message:
•
Save
•
Drag and drop the REC670 (client-IED) to REC670_BC (sending-IED) Goose Control Engineerings window .
and then define the MAC Address of your GOOSE message:
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 8
ABB Power Technologies AB Västerås - Sweden
REC670 Product Integration Training Course
•
You can now see the REC670 (client-IED) in the structure
•
Update the data flow you just created and Save.
•
You can now see the “Inputs” for REC670 (client-IED):
•
Do the same procedure for Line Bay IED. Drag and drop the REC670_BC (client-IED) to REC670 Goose Control Engineerings window . Substation Automation & Protection Training
SA.T. Training Product Integration REC670 2007-01-15
Page 9
ABB Power Technologies AB Västerås - Sweden
REC670 Product Integration Training Course
• •
Update the data flow. Save Verify that you can see the “Inputs” under REC670_BC
•
Export SCD file from CCT, now containing the GOOSE part.
•
Import SCD file to PCM600.
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 10
ABB Power Technologies AB Västerås - Sweden
•
REC670 Product Integration Training Course
Start SMT, do the connection both Line bay REC670………
…….and BusCoupler REC670_BC:
• •
Save. Close SMT.
Substation Automation & Protection Training SA.T. Training Product Integration REC670 2007-01-15
Page 11
ABB Power Technologies AB
REC670 Product Integration Training
Västerås - Sweden
•
Start PST. You need to activate IEC61850 communication and GOOSE messaging.
Settings for REC670:
Settings for REC670_BC:
Substation Automation & Protection Training SA.T. REC670 Product Integration Training Course 2007-01-16
Page 12
ABB Power Technologies AB
REC670 Product Integration Training
Västerås - Sweden
•
Save and close PST.
• 1. 2. 3. 4.
Download to IEDs CAP-configuration PST (settings) SMT GDE (If necessary)
•
Verify that horizontal communication (GOOSE) is working.
Substation Automation & Protection Training SA.T. REC670 Product Integration Training Course 2007-01-16
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.