X Popular, widely used on Sub-Transmission and Transmission Systems X Virtually independent of Fault Current Level (ZS/ZL ratios) X Fast Discriminative Protection:- Zone 1 or ‘Aided’ Distance Scheme X Time Delayed Remote Back-Up:- Incorporated at little extra cost
> Distance Protection - January 2004
Advantages of Distance Protection
X Measures Z, X or R correctly irrespective of System Conditions
X Compare this with Instantaneous Overcurrent Protection:-
> Distance Protection - January 2004
Advantages of Distance Protection
ZS = 10
ZS = 10
Ω ZL = 4
Ω
Ω
IF1 115kV
50
IF1 = 115kV/√3(5+4) = 7380A ∴ Is > 7380A
> Distance Protection - January 2004
F1
Advantages of Distance Protection X Consider with one source out of service:ZS = 10
Ω F2 IF2
50
IF2 = 115kV/√3 x 10 = 6640A ∴ Is
7380A
> Distance Protection - January 2004
- IMPRACTICAL
Simplified Line Diagram
L
R
L C
R
L C
XL = jWL XC = at FN (50Hz)
L
> Distance Protection - January 2004
R
L C
-j WC XC = large :-
R
R
Basic Principle of Distance Protection
ZS
ZL
Generation
IR Distance Relay
> Distance Protection - January 2004
21
VR
Impedance Seen By Measuring Element
jX ZL
R
> Distance Protection - January 2004
Basic Principle of Distance Protection
ZS
VS
Relay PT.
ZLOAD
VR
Impedance measured
> Distance Protection - January 2004
ZL
IR
ZR =
Normal Load
VR = Z L + Z LOAD ΙR
Basic Principle of Distance Protection ZL ZS
VS
IR
ZF
VR
ZLOAD
Fault
X Impedance Measured ZR = VR/IR = ZF X Relay Operates if ZF < Z
where Z = setting
X Increasing VR has a Restraining Effect ∴VR called Restraining Voltage X Increasing IR has an Operating Effect > Distance Protection - January 2004
Plain Impedance Characteristic
jX
ZL
Impedance Seen At Measuring Location For Line Faults
R TRIP
> Distance Protection - January 2004
STABLE
Impedance Characteristic Generation
IF
jIX
zF
IZ VF
V3
V1
V2
IR Trip
TRIP
STABLE
Spring
Restrain
Ampere Turns :
Operate VF
IZ
Trip Conditions : VF < IFZ
Voltage to Relay = Current to Relay = Replica Impedance =
V I Z
Trip Condition :
S2 < S1
where : S1 = IZ ≈ Z S2 = V ≈ ZF
> Distance Protection - January 2004
Basic Principle of Distance Protection ZP
I1/I2 IR 21
VR
V1 V2
VFP
X Relays are calibrated in secondary ohms :VFP x V2 /V 1 VFP Ι1/ Ι 2 Z R = VR/ ΙR = = x V1/V 2 ΙFP x Ι 2 / Ι1 ΙFP ZR = Z P x > Distance Protection - January 2004
C.T. RATIO V.T. RATIO
Example
ZP = 4Ω; V1/V2 = 115kV/115V; I1/I2 = 600/5A
C.T. RATIO ZR = ZP x V.T. RATIO
ZR(5) = 4 x 600/5 x 115/115x103 = 0.48Ω -5A Relay ZR(1) = 2.4 Ω
> Distance Protection - January 2004
- 1A Relay
Input Quantities for ∅-∅ Faults
FAULT
VRESTRAINT
IOPERATE
A-B
VA - VB
IA - IB
B-C
VB - VC
IB - IC
C-A
VC - VA
IC - IA
X VRESTRAINT & IOPERATE are selected inside the relay X No setting adjustments are required apart from Z1 = Phase Replica Impedance
> Distance Protection - January 2004
Input Quantities for Phase to Earth Faults
FAULT
VRESTRAINT
IOPERATE
A-E
VA ?
IA ?
B-E
C-E
> Distance Protection - January 2004
Neutral Impedance Replica Vectorial Compensation
Replica impedance circuit :IRA
Z1
∑IZN Z1 Z1
Z1 = Phase replica impedance ZN = Neutral replica impedance IRA passes through Z1 IRN passes through ZN
N
IRN
ZN
> Distance Protection - January 2004
ZT = Z1 + ZN
Neutral Impedance Compensation For a single phase to ground fault the total earth loop impedance is given by :- (Z1 + Z2 + Z0)/3 = ZT ZT = (Z1 + Z2 + Z0)/3 = Z1 + ZN ZN = (Z1 + Z2 + Z0)/3 - Z1 = (2Z1 + Z0)/3 - Z1 = - Z1 + 3 = KN Z1
Z0 3
where KN = (Z0 - Z1) 3Z1 > Distance Protection - January 2004
Neutral Impedance Vectorial Replica Compensation Line CT’s A ZPH
IAZPH
ZPH
IBZPH
ZPH
ICZPH
ZN
INZN
B
C
Set Z PH = Z F1 Set Z N = (Z F0 - Z F1 ) 3 Usually ∠ Z N = ∠ Z PH for OHL’s > Distance Protection - January 2004
Neutral Impedance Replica Compensation
For cables ∠Z0 ≠ ∠Z1 ∴ VECTORIAL COMPENSATION MUST BE USED KN = Z0 - Z1 = ⏐KN⏐ ∠∅N 3Z1
> Distance Protection - January 2004
Characteristics
> Distance Protection - January 2004
Distance Characteristics
jX
jX
jX
jX Zn
Zn
R MHO
Zn
R
Zn R Zn′
Zs
IMPEDANC E
CROSSPOLARISED MHO
R OFFSE T MHO
jX Zn
Zn
Zn R
LENTICULA R
> Distance Protection - January 2004
R
R QUADRILATERAL
POLYGON
Self Polarised Mho Relays
jX
X Very popular characteristic X Simple
RESTRAIN
X Less sensitive to power swings
Z
X Inherently directional X Operates for F1, but not for F2
Neutral Impedance Replica Vectorial Compensation Vectorial compensation allows for ∠ZN ≠ ∠ZPH which is especially important for cable distance protection where ∠ZN < ∠ZPH and ∠ZN is sometimes negative. jX ZPH
ZN ZE
ZE = R
> Distance Protection - January 2004
Earth-loop impedance for ∅ - earth fault on a cable
Offset Mho Characteristic
jX Z
X Normally used as backup protection
R -Z’
> Distance Protection - January 2004
X Operates for zero faults (close up faults) X Generally time delayed (as not discriminative)
Mho Relays
Directional circular characteristic obtained by introducing VPOLARISING X VF → self polarised X VSOUND PHASE → fully cross-polarised X VF + xVS.F. → partially cross-polarised X VPRE-FAULT → ‘memory’ polarised Purpose for this is to ensure operation for close up faults where measured fault voltage collapses
> Distance Protection - January 2004
Quadrilateral Characteristic
jX ZL Z1
Load RF RS
> Distance Protection - January 2004
R
Lenticular Load Avoidance Characteristic
jIX
Lenticular characteristic created from two offset Mho comparators Aspect ratio = a/b b
a
IR
> Distance Protection - January 2004
Lenticular Characteristic
X
Z3 a
Aspect ratios a/b 0.41 0.67 1.00
b Load impedance area R Z3 reverse
> Distance Protection - January 2004
Forward Offset Characteristic Z3
X Rf Z2
Forward blinder Z1 Load area R
X Enhanced resistive coverage for remote faults > Distance Protection - January 2004
Zones of Protection
> Distance Protection - January 2004
Zones of Protection Time
Z3A
T3
Z3C
Z2A
T2
Z2C
Z1A A
Z1B
Z1C B
C
D
T2 Z2B
Z1A = 80% of ZAB Z2A = 120% of ZAB Z3A(FORWARD) = 120% of {ZAB + ZCD} > Distance Protection - January 2004
Zones of Protection jX
Z3A
D
C B
Z2A Z1A
A
> Distance Protection - January 2004
R
Zone 1 X FAST OPERATION Trips circuit breaker without delay as soon as fault within Zone 1 reach is detected. X REACH SETTING Cannot be set to 100% of protected line or may overreach into next section. Overreach caused by possible errors in :CTs VTs ZLINE information Relay Measurement > Distance Protection - January 2004
Zone 1
Possible Overreach
ZONE 1 = ZL ZL F
Possible incorrect tripping for fault at ‘F’ ∴ Zone 1 set to ∼ 0.8ZL ZONE 1 = 0.8ZL ZL
> Distance Protection - January 2004
Zone 1 Settings for Teed Feeders
Z1C = 0.8ZAC
A
C Z1A = 0.8ZAB
Z1B = 0.8ZBA B
Z1C
Z1A Z1B
> Distance Protection - January 2004
Zone 1 Settings for Direct Intertrip Schemes
Z1A A
ZL B
Z1B
Z1A
Send
Receive Trip ‘B’
Receive
> Distance Protection - January 2004
Send
Z1B
Zone 1 Settings for Direct Intertrip Schemes
Effective Zone 1 reaches at A and B must overlap. Otherwise :- No trip for fault at ‘F’
A
Z1A
F
Z1B
∴ Effective Z1A and Z1B must be > 0.5ZL Settings for Zone 1 > 0.8ZL are o.k.
> Distance Protection - January 2004
B
Minimum Zone 1 Reach Setting
Dictated by :Minimum relay voltage for fault at Zone 1 reach point to ensure accurate measurement. Minimum voltage depends on relay design typically 1 → 3 volts.
> Distance Protection - January 2004
System Impedance Ratio :- SIR SIR = ZS/Zn where :-
VRPA = Minimum voltage for reach point accuracy Can be expressed in terms of an equivalent value of SIRMAX SIRMAX = ZS MAX Zn MIN ∴ Zn MIN ≡ ZS MAX SIRMAX > Distance Protection - January 2004
Zone 2 X Covers last 20% of line not covered by Zone 1. X Provides back-up protection for remote busbars. Z2G TIME Z1G G
Z1H H F
To allow for errors :Z2G > 1.2 ZGH Zone 2 is time delayed to discriminate with Zone 1 on next section for faults in first 20% of next section. > Distance Protection - January 2004
Zone 2 Zone 2 on adjacent line sections are not normally time graded with each other Z2G
Z2H
Z1G
‘G’
Z1H
‘H’ F
X Overlap only occurs for faults in first 20% of following line. X Faults at ‘F’ should result in operation of Z1H and tripping of circuit breaker ‘H’. If ‘H’ fails to trip possible causes are :Î Z1H operates but trip relays fail. Z2H may operate but will not trip if followed by the same trip relays. Fault must be cleared at ‘G’ by Z2G. Z1H and trip relays operate but circuit breaker fails to trip. > Distance Protection - January 2004
Zone 2
No advantage in time grading Z2G with Z2H Ð Unless Z2H + trip relays energise a 2nd circuit breaker trip coil.
> Distance Protection - January 2004
Zone 2 Î Z1H fails to operate. Ð Results in race between breakers ‘G’ and ‘H’ if Z2H and Z2G have the same time setting. Ð Can only be overcome by time grading Z2G with Z2H. Z2G Z2H Z1G ‘G’
Z1H ‘H’
Problem with this :Zone 2 time delays near source on systems with several line sections will be large. End zone faults on lines nearest the infeed source point will be cleared very slowly. > Distance Protection - January 2004
Maximum Allowable Zone 2 Reach to Allow for Equal Zone 2 Time Settings Z2A (EFF) MAX Z1B (EFF) MIN ZL1
A
B
ZL2
Z2A must not reach beyond Z1B i.e. Z2A(EFF) MAX must not reach further than Z1B(EFF) MIN
∴ ∴
Z1BSETTING = 0.8ZL2 Z1B(EFF) MIN = 0.8 x 0.8ZL2 = 0.64ZL2 Z2A(EFF) MAX < ZL1 + 0.64ZL2 1.2 Z2ASETTING < ZL1 + 0.64ZL2 Z2ASETTING < 0.83ZL1 + 0.53ZL2
> Distance Protection - January 2004
Zone 2 Time Settings on Long Line Followed by Several Short Lines Z2G Z3H Z3J Z2H Z2J Z1G ‘G’
Z1H ‘H’
Z1J ‘J’
F
Z2G reaches into 3rd line section. To limit remote back-up clearance for a fault at ‘F’, the time setting of Z2G must discriminate with Z3H. > Distance Protection - January 2004
Zone 3 X Provides back-up for next adjacent line. X Provides back-up protection for busbars (reverse offset). X Actual Zone 3 settings will be scheme specified, i.e. permissive or blocking schemes. X Many modern relays have more than 3 Zones to allow the use of three forward and an independent reverse zone. Z3G REV
Z3G FWD Z2G
Time
Z1G G
Z1H H
K
Typical settings : Z3FWD > 1.2 x (ZGH + ZHK) Z3REV 0.1 to 0.25 of Z1G > Distance Protection - January 2004
Zone Time Coordination - Ideal Situation Zone 1 :- tZ1 = instantaneous (typically 15 - 35mS) Zone 2 :- tZ2 = tZ1(down) + CB(down) + Z2(reset) + Margin e.g. tZ2 = 35 + 100 + 40 + 100 = 275mS Zone 3 :- tZ3 = tZ2(down) + CB(down) + Z3(reset) + Margin e.g. tZ3 = 275 + 100 + 40 + 100 = 515mS Note: Where upper and lower zones overlap, e.g. Zone 2 up sees beyond Zone 1 down, the upper and lower zone time delays will need to be coordinated, e.g. tZ2(up) to exceed tZ2(down). > Distance Protection - January 2004
Underreaching Due to Busbar Infeed between Relay and Fault
IA
ZA
IA+IB
IB
Relay Location
VR = IAZA + (IA + IB) ZB IR = IA ZR = ZA + ZB + IB . ZB IA > Distance Protection - January 2004
ZB
Underreaching Due to Busbar Infeed between Relay and Fault ∴ Relay with setting ZA + ZB will underreach with infeed. Relay with setting ZA + ZB + IB . ZB will measure IA correctly with infeed present but if infeed is removed the relay will overreach. Maximum allowable setting dictated by load impedance
> Distance Protection - January 2004
Under-Reach IP
IG+IP
ZG
ZK
F
IG
RELAY
What relay reach setting is required to ensure fault at F is at boundary of operation ? Impedance seen for fault at F = ZG + IG + IP . ZK IG Limit of operation is when Impedance Seen = Reach Setting ∴ Reach setting required = ZG + IG + IP . ZK IG > Distance Protection - January 2004
Over-Reach
Impedance seen < apparent impedance %age Overreach = ZF - ZR x 100% ZR where ZR = Reach setting ZF = Effective reach
> Distance Protection - January 2004
Mutual Coupling
> Distance Protection - January 2004
Mutual Coupling
X Mutual coupling causes distance relays to either underreach or overreach. X Positive and negative sequence has no impact. X Zero sequence mutual coupling can have a significant influence on the relay. X Only affects ground fault distance.
> Distance Protection - January 2004
Mutual Coupling Example Under Reach
Z2 ‘Boost’ G/F Z2 PH
Zmo
> Distance Protection - January 2004
Mutual Coupling Example Over Reach
Z2 ‘reduced’ G/F Z2 PH
> Distance Protection - January 2004
Mutual Coupling Example Over Reach
Z1 G/F (optional) Z1 G/F (normal)
Zmo
> Distance Protection - January 2004
Ancilliary Functions
> Distance Protection - January 2004
Switch on to Fault (SOTF)
X X X
X Fast tripping for faults on line energisation, even where line VTs provide no prefault voltage memory
> Distance Protection - January 2004
Voltage Transformer Supervision
X A VT fault and subsequent operation of VT fuses or MCB’s results in misrepresentation of primary voltages X Relay will remain stable as the current phase selector will not pick up X Subsequent system fault may cause unwanted / incorrect tripping X VTS operating from presence of V0 with no I0 or V2 with no I2 is used to block relay if required
> Distance Protection - January 2004
VT Supervision X Under load conditions Loss of 1 or 2 phase voltages Loss of all 3 phase voltages X Upon line energisation Loss of 1 or 2 phase voltages Loss of all 3 phase voltages X Digital input to monitor MCB X Set to block voltage dependent functions
> Distance Protection - January 2004
Zone 1 Mho Relay K ZS HH Z1
Ø3
J Ø 2
G
Ø1
ZS G
L
Power Swing Locus
> Distance Protection - January 2004
L O A D
X Will not operate for load or stable power swing X Ø1, Ø2, Ø3, = Angles between system voltages at ‘K’ and ‘L’ Ø increases as power swing approaches relay at G X ‘J’ is point where power swing enters relay characteristic X At ‘J’ the angle between voltages at ‘G’ & ‘H’ is 90° X Normal limit of angle between voltages at ‘G’ & ‘H’ for load is of the order of 30°
Comparison between Stability of Mho and Quadrilateral Impedance Elements during a Power Swing jX Power Swing Locus
θ R
> Distance Protection - January 2004
Illustration of Basic Power Swing Blocking System jX Power Swing Locus ZP Z3
R
> Distance Protection - January 2004
Power Swing Blocking
X A power swing will result in continuous change of current X Continuous output from the relay superimposed current element can be used to block for a power swing X Using this method the relay is able to operate for faults occurring during a power swing
> Distance Protection - January 2004
Directional Earth Fault Protection (DEF) O
High resistance ground faults
O
Instantaneous or time delayed
O
IEC and IEEE curves
O
Single or shared signalling channel
> Distance Protection - January 2004
Transformer Feeders
> Distance Protection - January 2004
Transformer Feeders
ZT ZL
21
Zone 1 = ZL + 0.5ZT T1 = Instantaneous Zone 2 = 1.2 (ZL +ZT) T2 = Co-ordinate with downstream protection Zone 3 T3
> Distance Protection - January 2004
- Back-up use as appropriate
Low Voltage VT, High Voltage CT ZT
ZL
21
* 1 VT may be required to account for phase shift. Example 1 ZT = 10Ω , ZL = 1Ω Set relay Z1 = 0.8 x (ZT + ZL) = 8.8Ω ∴ Z1 does not reach through transformer. Example 2 ZT = 10Ω , ZL = 1Ω Z1 = ZT + 0.8ZL = 10.8Ω with 20% error = 12.96Ω - overreach problem
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.