Differential Protection ∗ Works on Merz-price current comparison principle ∗ Relays with bias characteristic should only be used
Applied Where protection co-ordination is difficult / not possible using time delayed elements For fast fault clearance For zone of protection
Issue A
Slide 14
Differential Protection Consideration for applying differential protection Phase correction Filtering of zero sequence currents Ratio correction Magnetizing inrush during energisation Overfluxing Issue A
Slide 15
Differential Protection - Principle • Nominal current through the protected equipment I Diff = 0 : No tripping
R I diff = 0
Issue A
Slide 16
Differential Protection Principle • Through fault current
OLTC SETTING IS AT 10% Differential current = 0.1 A Relay pickup setting = O.2 A, So the Relay restrains Issue A
Slide 21
Biased differential protection 100 / 1
100/50 KV
200 / 1 10 A
9A
2000 A
R
1A
OLTC SETTING IS AT 10% Relay Pickup Setting is O.2 A So the Relay Operates Issue A
Slide 22
Role of Bias 3
2
Operate
Differential current (x In) = I1+ I2 + I3 + I 4
80
1 Setting range (0.1 - 0.5)
%
pe o Sl
Restrain pe
0
lo 20% S
1
2
4
3
Effective bias (x In) = I1 + I 2 + I 3 + I 4 2 Issue A
Slide 23
High Impedance Principle resistor istor Based on Current operated relay with an external stabilising res • Requires matched current transformers of low reactance design, typically class X or equivalent • Equal CT ratios • NonNon-linear resistor may be required to limit voltage across relay circuit during internal faults • Suitable for zones up to 200 - 300 metres (typically)
Issue A
Slide 24
High Impedance Principle RCT
2RL
M
2RL
A
ZM
RCT
ZM
RCT 2RL M
Issue A
2RL
TC RCTsaturé Slide 25
High Impedance Principle RCT
ZM
2RL
M
A
2RL
RCT
ZM
M
Issue A
Slide 26
High Impedance Principle RCT
ZM
2RL
M
A
2RL
RCT
ZM
M
TC saturé Issue A
Slide 27
High Impedance Principle RCT
ZM
2RL
M
A
2RL
RCT
ZM
M
Issue A
Slide 28
High Impedance Principle RCT
ZM
2RL
M
A
2RL
RCT
ZM
M
TC saturé Issue A
Slide 29
High Impedance Principle RCT
ZM
2RL
M
A
2RL
RCT
ZM
M
Issue A
Slide 30
High Impedance Principle RCT
ZM
2RL
M
A
2RL
RCT
ZM
TC saturé M
Issue A
Slide 31
High Impedance Principle RCT
2RL
M
2RL
A
ZM
RCT
ZM=0
False tripping RCT 2RL M
CT Saturation 2RL
RCT
TC saturé Issue A
Slide 32
High Impedance Principle M RCT
2RL
2RL
RCT
RS A
ZM
ZM=0
RCT 2RL M
2RL
RCT
TC saturé Issue A
Slide 33
High Impedance Principle RCT
2RL
2RL
M
RCT
RS A
ZM
ZM=0
Stabilising resistor
RCT 2RL M
2RL
RCT
TC saturé
Issue A
Slide 34
High Impedance Principle RCT
2RL
2RL
M
RCT
RS A
ZM
ZM
Vset
RCT 2RL M
Issue A
2RL
RCT
Slide 35
High Impedance Principle RCT
2RL
2RL
M
RCT
RS A
ZM
ZM=0
RCT 2RL M
Issue A
ZM = 0
Vset 2RL
RCT
(CT "short circuited" )
Slide 36
High Impedance Principle RCT
2RL
2RL
M
RCT
RS A
ZM
ZM
RCT
RCT 2RL
2RL M Vset
Issue A
Slide 37
High Impedance Principle RCT
2RL
2RL
M
RCT
RS A
ZM
ZM
RCT
RCT 2RL
2RL M
Vset
Issue A
Slide 38
High Impedance Principle RCT
2RL
2RL
M
RCT
RS A
ZM
Metrosil may be required for voltage limitation
RCT 2RL
M
ZM
RCT 2RL
M
Vset
Issue A
Slide 39
Restricted Earthfault Protection Uses high impedance principle
Increased sensitivity for earth faults REF elements for each transformer winding CTs may be shared with differential element
64
64
Issue A
64 Slide 40
Restricted Earthfault Protection REF Case I : Normal Condition transformer sformer Stability level : usually maximum through fault level of tran P1
P2
S1
S2 P1 S1
P1
S1
P2
S2
P2 S2 P1
P2
S1
S2
Under normal conditions no current flows thro’ Relay So, No Operation Issue A
Slide 41
Restricted Earthfault Protection REF Case II : External Earth Fault
External earth fault - Current circulates between the phase & neutral CTs; no current thro’ the relay
So, No Operation Issue A
Slide 42
Restricted Earthfault Protection REF Case III : Internal Earth Fault
For an internal earth fault the unbalanced current flows thro’ the relay
Setting will require calculation of : 1) Setting stability voltage (VS)
80MVA
2) Value of stabilising resistor required 1600/1 RCT = 4.8Ω
RS
2 Core 7/0.67mm (7.41Ω/km) 100m Long
Issue A
MCAG14 IS = 0.1 Amp
3) Peak voltage developed by CT’ CT’s for internal fault
Slide 44
Restricted Earthfault Protection Example : Earth fault calculation ::Using 80MVA base Source impedance = 1 p.u. 1 P.U.
Transformer impedance = 0.05 x 80 = 4 p.u. 1 1
1
4 I1
1
4 I2
∴ I1 = 1 = 0.0714 p.u. 14 Base current = 80 x 106 √3 x 415 = 111296 Amps
4 I0
Issue A
Total impedance = 14 p.u.
∴ IF = 3 x 0.0714 x 111296 = 23840 Amps (primary) = 14.9 Amps (secondary) Slide 45
Restricted Earthfault Protection (1) Setting voltage VS = IF (RCT + 2RL) Assuming “earth” earth” CT saturates, RCT = 4.8 ohms 2RL = 2 x 100 x 7.41 x 10-3 = 1.482 ohms ∴ Setting voltage = 14.9 (4.8 + 1.482) = 93.6 Volts (2) Stabilising Resistor (RS) RS = {Vs - [VA/(Is^2)]} /Is Where IS = relay current setting ∴ RS = {93.6 - [ 1/0.1^2]}/0.1
Issue A
= 836 ohms
Slide 46
Restricted Earthfault Protection 3) Peak voltage = 2√ 2√2 √VK (VF - VK) VF = 14.9 x VS = 14.9 x 936 = 13946 Volts IS For ‘Earth’ Earth’ CT, VK = 1.4 x 236 = 330 Volts (from graph) ∴ VPEAK = 2√ 2√2 √330 (13946 - 330) = 6kV Thus, metrosil voltage limiter will be required.
Issue A
Slide 47
Magnetising Inrush • Transient condition - occurs when a transformer is energised • Normal operating flux of a transformer is close to saturation level • Residual flux can increase the mag-current • In the case of three phase transformer, the point-on-wave at switch-on differs for each phase and hence, also the inrush currents
Issue A
Slide 48
Magnetising Inrush Transformer Magnetising Characteristic Twice Normal Flux
Normal Flux
Normal No Load Current No Load Current at Twice Normal Flux Issue A
Slide 49
Magnetising Inrush Inrush Current + Φm
V
Φ Im
STEADY STATE - Φm Im
2 Φm
Φ V
Issue A
SWITCH ON AT VOLTAGE ZERO - NO RESIDUAL FLUX
Slide 50
Magnetising Inrush
Issue A
Slide 51
Magnetising Inrush Effect of magnetising current
• Appears on one side of transformer only - Seen as fault by differential relay - Transient magnetising inrush could cause relay to operate • Makes CT transient saturation - Can make mal-operation of Zero sequence relay at primary
Issue A
Slide 52
Magnetising Inrush
IR IS
P1
P2
S1
S2 P1
IT
S1
P2 S2 P1
P2
S1
S2
IR + IS + IT = 3Io = 0 Issue A
Slide 53
Magnetising Inrush Effect of magnetising current
Example of disurbance records with detail
Issue A
Slide 54
Magnetising Inrush Restrain 2nd (and 5th) harmonic restraint • Makes relay immune to magnetising inrush • Slow operation may result for genuine transformer faults if CT saturation occurs
Issue A
Slide 55
Overfluxing - Basic Theory Overfluxing = V/F
Causes Low frequency High voltage Geomagnetic disturbances Issue A
Slide 57
Overfluxing - Basic Theory V = kfΦ
2Φm
Φm Ie Effects Transient Overfluxing - Tripping of differential element Prolonged Overfluxing - Damage to transformers Issue A
Slide 58
Overfluxing - Condition Differential element should be blocked for transient overfluxing-+ 25% OVERVOLTAGE CONDITION
Overfluxing waveform contains very high 5th Harmonic content
43% 5TH HARMONIC CONTENT Issue A
Slide 59
Overfluxing - Protection V
KΦ α f
• Trip and alarm outputs for clearing prolonged overfluxing • Alarm : Definite time characteristic to initiate corrective action • Trip : IT or DT characteristic to clear overfluxing condition
Issue A
Slide 60
BUCCHOLZ PROTECTION Oil conservator
Bucholz Relay
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Installation To oil conservator 3 x internal pipe diameter (minimum) 5 x internal pipe diameter (minimum)
Mercury switch To oil conservator From transformer
Trip bucket
Deflector plate Issue A
Slide 60
BUCCHOLZ PROTECTION Buccholz Protection Application Accumulation of gaz Oil Leakage Severe winding faults
Issue A
Slide 60
BUCCHOLZ PROTECTION Accumulation of Gaz Interturn faults Winding faults to earth with low power (fault (fault close to neutral for example) example)
Issue A
Slide 60
BUCCHOLZ PROTECTION Inter-Turn Fault
E
CT Load
Shorted turn
Nominal turns ratio : 11,000 / 240 Fault turns ratio Current ratio
: 11,000 / 1 :1 / 11,000 Primary
Issue A
Secondary Slide 60
BUCCHOLZ PROTECTION Inter-Turn Fault
E
CT Shorted turn
Nominal turns ratio : 11,000 / 240 Fault turns ratio Current ratio
: 11,000 / 1 :1 / 11,000 Primary
Issue A
Secondary Slide 60
BUCCHOLZ PROTECTION Interturn Fault Current / Number of Turns Short Circuited Primary current (multiples of rated current) 100 Fault current (multiples of rated current)
80
60
40
20
5
Issue A
10
15
20
25
Turn shortshort-circuited (percentage of winding) Slide 60
BUCCHOLZ PROTECTION Interturn Fault Current / Number of Turns Short Circuited Primary current (multiples of rated current) 100 Fault current (multiples of rated current)
80
60
Fault current very high
40
Detected by Bucholz relay
20
Primary phase current very low
5
Issue A
10
15
20
25
Not detected by current operated relays Slide 60
BUCCHOLZ PROTECTION Accumulation of Gaz Interturn faults Winding faults to earth with low power (fault (fault close to neutral for example) example)
Issue A
Slide 60
BUCCHOLZ PROTECTION Earth Fault Current / Number of Turns Short Circuited multiples of max fault current Primary current 100
80 Fault current 60
40
20
5 Issue A
10
15
20
25
Turn shortshort-circuited (percentage of winding) Slide 60
BUCCHOLZ PROTECTION Accumulation of Gaz Operating principle
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Accumulation of gaz
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Accumulation of gaz
Issue A
Slide 60
BUCCHOLZ PROTECTION
Buchholz Relay Accumulation of gaz
Issue A
Slide 60
BUCCHOLZ PROTECTION
Accumulation of gaz
Color of gaz indicates the type of fault White or Yellow : Insulation burnt Grey : Dissociated oil
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Accumulation of gaz
Issue A
Gaz can be extracted for detailled analysis
Slide 60
BUCCHOLZ PROTECTION Effects of Oil Maintenance
• After oil maintenance, false tripping may occur because Oil aeration Bucholz relay tripping inhibited during suitable period
Need of electrical protection
Issue A
Slide 60
BUCCHOLZ PROTECTION Bucholtz Protection Application Accumulation of gaz Oil Leakage Severe winding faults
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Oil Leakage
Issue A
Slide 60
BUCCHOLZ PROTECTION Buccholz Protection Application Accumulation of gaz Oil Leakage Severe winding faults
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Severe winding fault
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Severe winding fault
Issue A
Slide 60
BUCCHOLZ PROTECTION Buchholz Relay Severe winding fault
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.