DS Agile OI OVERVIEW DS Agile Training Level 1 Global Systems Engineering 03/05/2012

GRID

GSE

SAM

Summary

1) DS Agile Operator Interface Features

Page 3

2) DS Agile Operator Interface Description

Page 8

L1-07-DS Agile OI Overview - Rev G - P 2

GSE

1.1) DS Agile OI Basic Purpose Basic Purpose :

Which DS Agile element ?

Display business views SCP : Substation Control Point Get data, Archive and logging

OI Client OI Server

Composition : 1) OI Server IS main SBUS Client (also server of few System Info like Printer status) HAS Hard Disk for Archives (Historian SQL server) HAS Printers (for SOE…) IS Server of All OI Client

2) OI Client Subscribe to OI Server Display data L1-07-DS Agile OI Overview - Rev G - P 3

GSE

1.2) DS Agile OI Sub-components What is, and how is composed DS Agile OI ? OI Clients

Internet

OI Servers

SCADA 2000 Factory Link

Alarm and Events

Historian Trends

Data Processing

Communication

Controls

SQL Server INFRASTRUCTURE

SBUS Agency

Ethernet SBUS

L1-07-DS Agile OI Overview - Rev G - P 4

GSE

1.3) DS Agile OI Technical Data

Common DS Agile OI capabilities : – From 1 to 8 OI Client (including remote and embedded OI client(s)) – Up to 4 VDU on each OI Client – Multi-active OI server

(redundancy, twin servers)

– Watchdog : DS Agile OI server application must be launched through DS Agile Watch, so application can restart automatically in case of unexpected failure. (continuity) (available from V4.6.x) – Watchdog : DS Agile OI Client application must start using DS Agile Client Watch.

L1-07-DS Agile OI Overview - Rev G - P 5

GSE

1.4) DS Agile OI Hardware Composition Hardware composition and required OS : PC with : - At least 3 GBytes RAM and 1.5 GHz processor (better if dual core) - Up to 4 monitor screens Ethernet connection, Maximum resolution 3200*2400 - Windows XP SP3 - SQL Server (Personal Edition),(SQL2005, SQL2005 embedded)

Available from DS Agile 5.0.2: Windows Seven Windows 2008 server Microsoft SQL server 2008

L1-07-DS Agile OI Overview - Rev G - P 6

GSE

Summary

1) DS Agile Operator Interface Features

Page 3

2) DS Agile Operator Interface Description

Page 8

L1-07-DS Agile OI Overview - Rev G - P 7

GSE

2.1) DS Agile OI Windows 1) Title 2) Tools

3) Mimic

4) Short Alarms 5)Navigator L1-07-DS Agile OI Overview - Rev G - P 8

GSE

2.2) Title Bar ALSTOM logo animated by DS Agile OI Server State Substation Name defined into the SCE

Connected OI server for this OI client

User and Profile names are updated after logging in or out. Time and Date are given by PC synchronised by OI Server

icon displaying SBUS coupling status between DS Agile OI Server and the SBUS agency

Mode status, Substation control mode. •Remote

substation driven from RCP.

•Local

substation driven through DS Agile OI.

L1-07-DS Agile OI Overview - Rev G - P 9

GSE

2.3) Command Bar Opens the Password Utility dialog box. Indicates if at least one memo is active in mimics.

Launches Operator Station tools Launches DS Agile SMT HMI

Opens the User Management dialog box. Alternately Log in and Log off (default user profile). Short cut : F2 L1-07-DS Agile OI Overview - Rev G - P 10

Stops the DS Agile OI Client. Short cut : F10

Archive Restore

Stops audible alarms

Prints : •full screen (F5) •active mimic (Shift+F5) GSE

2.4) Custom General View Mimic General View Mimic : (Substation, Voltage Level, …)

Electrical controllable devices (Various representations : IEC, ANSI, customised) Measurements, Viewers, Memos, Navigation buttons ...

L1-07-DS Agile OI Overview - Rev G - P 11

Fully configurable

GSE

2.5) Custom Bay Mimic Detailed Bay Mimic :

Electrical controllable devices (Various representations : IEC, ANSI, customised) Measurements, Viewers, Memos, Navigation buttons ...

Fully configurable L1-07-DS Agile OI Overview - Rev G - P 12

GSE

2.6) Custom System View Mimic System View Mimic :

DS Agile System devices (MiCOM Computers, DS Agile OI, DS Agile Gateway,…) IED (Protections, Measurement Centres, …)

Fully configurable L1-07-DS Agile OI Overview - Rev G - P 13

GSE

2.7) Alarm Viewer

Browser (option)

Alarm List Colours, columns configurable

L1-07-DS Agile OI Overview - Rev G - P 14

GSE

2.8) States Viewer Print Filter Stop

L1-07-DS Agile OI Overview - Rev G - P 15

GSE

2.9) Events Viewer Print Filter Refresh

L1-07-DS Agile OI Overview - Rev G - P 16

GSE

2.10) Trend Viewer

Multi MV trend viewer L1-07-DS Agile OI Overview - Rev G - P 17

GSE

2.11) Direct Control Pop-up

SPC one state

SPC

DPC

L1-07-DS Agile OI Overview - Rev G - P 18

GSE

2.12) SBO FSS Control

Select Before Operate

SBO for Synchronised CB

Force Substitute Suppress L1-07-DS Agile OI Overview - Rev G - P 19

GSE

2.13) Hot Redundancy for OI Server 1) On DS Agile, Hot redundancy is possible => no manual operations 1.1) OI Client is connected to “preferred” OI Server. If server not available it will immediately try connect to the other one. Client A

Client B

Client C

Server 1

Server 2

SQL database

SQL database

IEC 61850 Station Bus

1.2) Both OI server perform DP acquisition simultaneously. There is a consolidating mechanism insuring all historized data are the same on both. L1-07-DS Agile OI Overview - Rev G - P 20

GSE