Contents: 1. INTRODUCTION...................................................................................................................................3 2. INSTALLATION....................................................................................................................................4 3. EXCEL IMPORT....................................................................................................................................6 3.1 PRECONDITION................................................................................................................................. 6 3.2 EDIT THE EXCEL FILE....................................................................................................................... 6 3.3 EDIT THE PATTERN FILE................................................................................................................... 8 ...................................................................................................................................................................11 3.4 START EXCEL IMPORT.................................................................................................................... 14 3.5 BUILD RTU FILES........................................................................................................................... 22 4. RTU560 WEB SERVER.......................................................................................................................27 4.1 PRECONDITION............................................................................................................................... 27 4.2 ESTABLISH PPP- CONNECTION........................................................................................................ 27 4.3 START INTERNET EXPLORER WITH ADDRESS HTTP//10.0.10.50........................................................29 4.4 LOAD CONFIG.IOD (I/O DATA)....................................................................................................... 30 4.5 LOAD CONFIG.GCD (GENERAL CONFIGURATION DATA)...................................................................32 4.6 LOAD CONFIG.IOD (TEXTS FROM ARCHIV OR PRINTER)...................................................................34 4.7 RESTART RTU560.......................................................................................................................... 36
ABB Oy
2-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities 1.
RTU560 Step By Step
Introduction This brief description does not replace the standard 560RTUtil NT User’s Guide and RTU560 Web Servers User’s Guide”. For details please refer to the manuals mentioned. This description is made to show, how to change or add an item to an existing configuration in the RTU, in case the user has not been working with the tool for a while, or to help a newcomer to get easily started with the 560RTUtil NT. This brief description handles: •
•
Installation The description for this installation procedure is complete different from the installation procedure described in the Users’Guide. This way of installation is mainly based on field experience. Excel import This Excel import procedure shows each step that has to be done if a change the RTU configuration is required. The precondition is, that this steps have been carried out before. This is the standard case when the RTU is delivered from the factory with the appropriate configuration files and the customer make changes for example during commissioning. This guide advises you to keep the actual files which are in use in the RTU as backup. If everything goes wrong during Excel-import, you will still have the healthy GCD, IOD and PTX file which can be loaded to the RTU. This steps seem more complicate as they really are. It is a matter of practice. The main goal for Excel import is, if you have a large amaount of I/O’s or IDE’s. The Excel-import helps to keep track of the parameters used in the RTU. The output of this Excel-import chapter are the RTU-Files. The GCD-, IOD- and the PTX File will be loaded to the CPU with the WEB Server Tool.
ABB Oy
3-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities 2.
RTU560 Step By Step
Installation RTUtil NT is distributed as CD-ROM and is developed for the Windows NT 4.0 operating system. Copy the packed file ”RTUtilNT_xx_xx_xxx_00.exe” into a directory with the release name Wbtr xxx and unpack the file into the same directory. This will create the sub-directory Disk1 with additional subdirectories as shown below. Keep this directory for future use, for example when you have to re-install the RTUtil NT
Double-click Setup.exe in the directory Disk1. The installation Process guides you through the installation process.
ABB Oy
4-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Follow the steps from the installation program and click through the following dialog sheets: 1. Acknowledge welcome page 2. Accept license agreements 3. Select the program path, where the files should be installed
4. Select the program group of RTUtil NT 5. Restart your computer. If you are working with different RTUtil NT releases as in the picture above, create your ”Release specific directory” and name it accordingly. Keep your projects in the appropriate release directories. If upgrade is required to the next higher release, please ask your supplier for support. If you currently are working with release 6 and you need to edit a project made with release 5, just re-install RTUtil NT release 5 over the already existing directory from release 5. This will not affect the project files, but will set registry to keep track of internal paths.
ABB Oy
5-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities 3.
Excel import
3.1
Precondition
RTU560 Step By Step
RTUtil NT is installed and at least the Pattern and the Excel file(s) exist in the appropriate directory.
The Pattern file contains: • Complete Network Tree (Including all links to the Hardware Tree) • The Hardware Tree down to RTU560 board level (Without I/O signal definitions and assignments The Excel file(s) contains: • Project Signal Tree (Signal names structured according to the project settings of the project pattern) • The data object’s hardware assignment to RTU I/O points • Data object parameters and addresses The Pattern file and the Excel sheet will be merged into the RTU File! 3.2
Edit the Excel file Open directory ”xls_import” under your current release ant open your project directory.
ABB Oy
6-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Make a copy of the ”ACTIVE xls” file, change the date and remove the ACTIVE from the old version to keep track of history.
Open the Excel file and select the sheet in question.
For example change input range from 20 mA to 5 mA.
Save the changes and close the file.
ABB Oy
7-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities 3.3
RTU560 Step By Step
Edit the Pattern file Open directory ”pattern” under your current release and open your project directory.
Make a copy of the ”ACTIVE TU” file, change the date and remove the ACTIVE from the old version to keep track of history.
ABB Oy
8-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Start RTUtil from your work-directory or create a shortcut on your desktop or.
Start RTUtil via Windows ”Start / Programs / RTUtil NT/ RTUtil NT
ABB Oy
9-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
RTUtil NT workspace offers to setup a new project. As we are editing an already existing Project press Cancel!
Select ”Open” (existing pattern)
ABB Oy
10-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
RTUtil NT offers you as default the project directory. Go one level higher by pressing this button
In the pattern directory select your project directory
Now select the pattern directory.
Now select your ACTIVE pattern file and select Open
Your project specific pattern file with ”View Network Tree” is now open.
ABB Oy
11-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Check that your pattern file does not contain any signals in the ”View Signal Tree”.
Check that your pattern file does not contain any signals in the ”View Signal Tree”.
ABB Oy
12-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Check so that your pattern file does not contain any signals in the ”View Hardware Tree”.
Note: If there are already any signals in the ”View Signal Tree” or in the ”View Hardware Tree” They must be deleted, otherwise due to ”additive” import will signals will be doubled, and will cause an error message for each duplicated signals during RTU file generation.
ABB Oy
13-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities 3.4
RTU560 Step By Step
Start Excel Import From the menu Extra select Excel Import.
As the pattern file is already open, RTUtil NT suggests the open file as pattern file. Accept with Next.
ABB Oy
14-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Accept your RTU ”RHK”. (In standard projects is normally only one RTU available. Accept with Next.
Now select the Excel file that belongs to this project. Select Browse…..
ABB Oy
15-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Select your project directory!
Select the ACTIVE Excel file of the project to be imported and continue with Select
Check that path and filename of the excel file is correct! Then select next!
ABB Oy
16-37
ABB Oy PSS/SAS RTU560 Revision: 4 Cities
RTU560 Step By Step
Now as the Excel file is selected, you have to define the sheet(s) within the excel file to be imported. (The sheet for an IEC 870-5-103 Sub-Dev.Line is currently not used in this example. Otherwise this sheet would have to be selected too.) With the ” > ” or ” < ” button one single file is selected or deselected. With the ” >> ” or ”