Application of Directional Overcurrent and Earthfault Protection
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Protection
Application of Directional Overcurrent and Earthfault Protection - January 2004
Need for Directional Control Generally required if current can flow in both directions through a relay location e.g. Parallel feeder circuits Ring Main Circuits
0.9
0.1
0.5
0.5
0.1
0.9
Relays operate for current flow in direction indicated. (Typical operating times shown).
Application of Directional Overcurrent and Earthfault Protection - January 2004
Ring Main Circuit With ring closed : Both load and fault current may flow in either direction along feeder circuits. Thus, directional relays are required. Note: Directional relays look into the feeder. Need to establish principle for relay.
51
67
67
67
Load
51
67
Load
67
Load Application of Directional Overcurrent and Earthfault Protection - January 2004
67
Ring Main Circuit Procedure : 1. Open ring at A Grade : A' - E' - D' - C' - B' 2. Open ring at A' Grade : A - B - C - D - E Typical operating times shown. Note : Relays B, C, D’, E’ may be non-directional. A
B'
B
C'
C
0.1
1.3
0.5
0.9
1.7
A'
E
E'
0.1
1.3
1.7
Application of Directional Overcurrent and Earthfault Protection - January 2004
0.9
D'
0.5
D
Ring System with Two Sources Discrimination between all relays is not possible due to different requirements under different ring operating conditions.
}
For F1 :- B’ must operate before A’ For F2 :- B’ must operate after A’
Not Compatible B
F1 B'
A
B
C'
C
A' F2 Application of Directional Overcurrent and Earthfault Protection - January 2004
D
D'
Ring System with Two Sources Option 1 Trip least important source instantaneously then treat as normal ring main. Option 2 Fit pilot wire protection to circuit A - B and consider as common source busbar. B
A
Option 1
50
Option 1
PW
PW
Option 2
Option 2
Application of Directional Overcurrent and Earthfault Protection - January 2004
Option 1
Parallel Feeders Non-Directional Relays :‘F’
51 A
51 C
51 B
51 D
“Conventional Grading” :Grade ‘A’ with ‘C’ and Grade ‘B’ with ‘D’
Load
A&B C&D
Relays ‘A’ and ‘B’ have the same setting. Fault level at ‘F’ Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders Consider fault on one feeder :I1 + I2 I1
51 A
I2
51 B
C
51
D
51
LOAD
Relays ‘C’ and ‘D’ see the same fault current (I2). As ‘C’ and ‘D’ have similar settings both feeders will be tipped. Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders Solution:- Directional Control at ‘C’ and ‘D’ I1 + I2 I1
51 A
C I2
51 B
D
67
LOAD
67
Relay ‘D’ does not operate due to current flow in the reverse direction.
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders Setting philosophy for directional relays E 51 A
C
Load
67 51
51 B
D
67
Load current always flows in ‘non-operate’ direction. Any current flow in ‘operate’ direction is indicative of a fault condition. Thus Relays ‘C’ and ‘D’ may be set :- Sensitive (typically 50% load) - Fast operating time (i.e. TMS=0.1) Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders
Usually, relays are set :50% full load current (note thermal rating) Minimum T.M.S. (0.1) Grading procedure :1. Grade ‘A’ (and ‘B’) with ‘E’ assuming one feeder in service. 2. Grade ‘A’ with ‘D’ (and ‘B’ with ‘C’) assuming both feeders in service.
Application of Directional Overcurrent and Earthfault Protection - January 2004
Parallel Feeders - Application Note
Grade B with C at If1 Grade B with D at If2 (in practice) A Grade A with B at If Load - but check that sufficient margin exists for bus fault at Q when relay A sees total fault current If2, but relay B sees only If2/2.
If2
P B
D
Load
C B
If1:One Feeder If2:Two Feeders
D
D
C
B
A M = Margin If2
If2/2
M
M
If2/2 If1If2
Application of Directional Overcurrent and Earthfault Protection - January 2004
Q
M
If
Establishing Direction
Application of Directional Overcurrent and Earthfault Protection - January 2004
Establishing Direction:- Polarising Quantity
The DIRECTION of Alternating Current may only be determined with respect to a COMMON REFERENCE. In relaying terms, the REFERENCE is called the POLARISING QUANTITY. The most convenient reference quantity is POLARISING VOLTAGE taken from the Power System Voltages.
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Decision by Phase Comparison (1) S1 = Reference Direction = Polarising Signal = VPOL S2 = Current Signal = I OPERATION when S2 is within ±90° of S1 :S1 S2
S2
S2
S2
Application of Directional Overcurrent and Earthfault Protection - January 2004
S2
S2
S2
Directional Decision by Phase Comparison (2) RESTRAINT when S2 lags S1 by between 90° and 270° :S1
S2
S2
S2
S2
S2
S2 S2
Application of Directional Overcurrent and Earthfault Protection - January 2004
Polarising Voltage for ‘A’ Phase Overcurrent Relay
OPERATE SIGNAL
=
POLARISING SIGNAL :-
Application of Directional Overcurrent and Earthfault Protection - January 2004
IA Which voltage to use ? Selectable from VA VB VC VA-B VB-C VC-A
Directional Relay Applied Voltage Applied Current
: :
VA IA VA IA
Operate IAF VAF
Restrain
Question : - is this connection suitable for a typical power system ? Application of Directional Overcurrent and Earthfault Protection - January 2004
Polarising Voltage Applied Voltage : VBC Applied Current : IA VA IA IAF MAXIMUM SENSITIVITY LINE
VBC IVBC
ØVBC ZERO SENSITIVITY LINE
X Polarising voltage remains healthy X Fault current in centre of characteristic
Application of Directional Overcurrent and Earthfault Protection - January 2004
Relay Connection Angle The angle between the current applied to the relay and the voltage applied to the relay at system unity power factor e.g. 90° (Quadrature) Connection :
IA and VBC
IA VA
90° VBC
VC
VB
The 90° connection is now used for all overcurrent relays. 30° and 60° connections were also used in the past, but no longer, as the 90° connection gives better performance. Application of Directional Overcurrent and Earthfault Protection - January 2004
Relay Characteristic Angle (R.C.A.) for Electronic Relays The angle by which the current applied to the relay must be displaced from the voltage applied to the relay to produce maximum operational sensitivity e.g. 45° OPERATE
RESTRAIN
IA FOR MAXIMUM OPERATE SENSITIVITY
VA
45°
RCA
Application of Directional Overcurrent and Earthfault Protection - January 2004
VBC
90° Connection - 45° R.C.A.
MAX SENSITIVITY LINE
OPERATE
IA VA
RESTRAIN
IA FOR MAX SENSITIVITY
VA 45°
90°
45° VBC
VC
135°
VB
RELAY CURRENT VOLTAGE A
IA
VBC
B
IB
VCA
C
IC
VAB
Application of Directional Overcurrent and Earthfault Protection - January 2004
VBC
90° Connection - 30° R.C.A. OPERATE MAX SENSITIVITY LINE IA FOR MAX SENSITIVITY
RESTRAIN
IA VA
VA 30°
90° VBC
30° 150°
VC
VB
RELAY CURRENT VOLTAGE A
IA
VBC
B
IB
VCA
C
IC
VAB
Application of Directional Overcurrent and Earthfault Protection - January 2004
VBC
Selection of R.C.A. (1) Overcurrent Relays 90° connection 30° RCA (lead) Plain feeder, zero sequence source behind relay
Application of Directional Overcurrent and Earthfault Protection - January 2004
Selection of R.C.A. (2) 90° connection 45° RCA (lead) Plain or Transformer Feeder :- Zero Sequence Source in Front of Relay
Transformer Feeder :- Delta/Star Transformer in Front of Relay
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earthfault Protection
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earth Fault Requirements are similar to directional overcurrent i.e. need operating signal and polarising signal Operating Signal obtained from residual connection of line CT's i.e. Iop = 3Io Polarising Signal The use of either phase-neutral or phase-phase voltage as the reference becomes inappropriate for the comparison with residual current. Most appropriate polarising signal is the residual voltage. Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual Voltage May be obtained from ‘broken’ delta V.T. secondary. A B C VA-G
VB-G VC-G
VRES = VA-G + VB-G + VC-G = 3V0
VRES
Notes : 1. VT primary must be earthed. 2. VT must be of the '5 limb' construction (or 3 x single phase units) Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earth Fault Relays
Relay Characteristic Angle 0 - Resistance earthed systems 45 (I lags V) - Distribution systems (solidly earthed) 60 (I lags V) - Transmission systems (solidly earthed)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual Voltage Solidly Earthed System
E
S
F
R ZL
ZS
A-G VA VA
VB VC
VC VA
VB VC
VB VC
VRES VA VC
VB
VRES VB
VB VC
Residual Voltage at R (relaying point) is dependant upon ZS / ZL ratio.
Z S0 VRES= x 3E 2Z S1 + Z S0 + 2Z L1 + ZL0 Application of Directional Overcurrent and Earthfault Protection - January 2004
Residual Voltage Resistance Earthed System S
E
R
ZS
N
F
ZL
ZE
A-G
G VA-G G.F
VC-G
VB-G VC-G
VRES VA-G VC-G
VRES=
S R G.F
S V A-G R G.F
S
VB-G
VRES VA-G VC-G
VB-G VC-G
VB-G
VB-G
VRES
VB-G
VC-G
Z S0 + 3Z E x 3E 2Z S1 + Z S0 + 2Z L1 + ZL0 + 3Z E
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Earth Fault Relays Relay Characteristic Angle 0 - Resistance earthed systems 45 (I lags V) - Distribution systems (solidly earthed) 60 (I lags V) - Tranmission systems (solidly earthed) Zero sequence network :ZS0
3R
I0
V0
V0 = ( - ) I0 (ZS0 + 3R) Application of Directional Overcurrent and Earthfault Protection - January 2004
ZL0
Current Polarising A solidly earthed, high fault level (low source impedance) system may result in a small value of residual voltage at the relaying point. If residual voltage is too low to provide a reliable polarising signal then a current polarising signal may be used as an alternative. The current polarising signal may be derived from a CT located in a suitable system neutral to earth connection. e.g.
OP POL DEF Relay
Application of Directional Overcurrent and Earthfault Protection - January 2004
Directional Control Static Relay (METI + MCGG)
M.T.A. Selectable
Characteristic Selectable
I
51
V
67 Overcurrent Unit (Static)
Application of Directional Overcurrent and Earthfault Protection - January 2004
Øc - 90° Polarising thresholds Vp > 0.6V Vop > 0.6 to 80V in 0.2V steps for example Application of Directional Overcurrent and Earthfault Protection - January 2004
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.