Protection and control IED manager PCM600 Exercise 1 - Prepare the t he PCM600 project 1MRG003744
Exercise 1 - Create a project
Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Trademarks ABB is a registered trademark of ABB Group. All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders.
On completion of this exercise you should be abl e to ·
·
Understand what is needed to establish the communication between the PCM600 and an Intelligent Electronic Device (IED) Create a new project in PCM600 and configure an IED object
Protection and control IED manager PCM600 1MRG003744
Page 1
Exercise 1 - Create a project
IPAddressing As preparation for the upcoming PCM600 exercises, you need to configure the IP address for both the IED and the PC. This is needed since the PC running PCM600 and the IED(s) that PCM600 shall communicate with must belong to the same sub network.
IPAddr ess of the IED's rear port 1. On the local HMI of the IED, select Settings\General Settings\Communication\Ethernet con figu ration \REAR-OEM Port AB
2. Set the Mode to Normal and the IPAddress to for example 172.16.0.10 . 3. Press the Menu button and save the changes.
Ethernet port settings of the PC The Ethernet settings of the PC are managed in the Windows Control Panel.
4. Open the Control Panel (Start Menu in Windows), see the figures below.
Exercise 1 - Create a project
5. Choose Network and Sharing Center .
6. Select Change adapter settings .
Protection and control IED manager PCM600 1MRG003744
Page 3
Exercise 1 - Create a project
7. Open the properties of the network connection you are using.
8. Select the properties of Internet Protocol Version 4 (TCP/IPv4)
Exercise 1 - Create a project
9. Configure the IP-address and the Subnet mask
Protection and control IED manager PCM600 1MRG003744
Page 5
Exercise 1 - Create a project
Create the PCM600 pro ject PCM600 works with projects. Within these projects, you create and configure your plant structure and the IED objects representing your real substation.
10. Start PCM600
11. Create a new project
12. Name your project. Question: What is missing in the fi gure below?
Exercise 1 - Create a project
Create the plant st ructure 13. Create the plant structure according to the below picture. Name the substation, voltage level and bay level objects according to your own needs.
14. Create a REC670 IED object
15. Select Online Configuration (because we have the physical IED available)
Protection and control IED manager PCM600 1MRG003744
Page 7
Exercise 1 - Create a project
16. Select the IEC61850 protocol
17. Select the LAN port and provide the IP-address corresponding to your IED rear port settings.
Exercise 1 - Create a project
18. Select Scan. PCM600 will read version, hardware, housing size information etc from the IED.
19. Finalize the configuration wizard.
Protection and control IED manager PCM600 1MRG003744
Page 9
Exercise 1 - Create a project
HW confi guration The HW information was read from the IED when you created the IED object in PCM600 (in online mode). Open the Hardware Configuration tool to view the hardware options you have in your training setup.
20. Open the Hardware Configuration tool
Exercise 1 - Create a project
21. Explore the HW configuration tool. What can be done with this tool?
22. Make a project backup.
Protection and control IED manager PCM600 1MRG003744