Application of Non-Directional Overcurrent and Earthfault Protection
Non-Directional Overcurrent and Earth Fault Protection
Overcurrent Protection Purpose of Protection z Detect abnormal conditions z Isolate faulty part of the system z Speed z Fast operation to minimise damage and danger z Discrimination z Isolate only the faulty section z Dependability / reliability z Security / stability z Cost of protection / against cost of potential hazards
Overcurrent Protection Co-ordination
F1
F2
F3
z Co-ordinate protection so that relay nearest to fault operates first z Minimise system disruption due to the fault
Fuses
Overcurrent Protection Fuses z Simple z Can provide very fast fault clearance z Is
I > Is 0.1 0.1 0.2 0.4 0.4 0.4 0.8
0.05 0 0 0 0 0 0
0 0 0
1 1 1
0.025 0 0 0 0 0
0.05 0.05 0.1 0.2 0.3 0.4
0 0 0 0 0 0
1 2 4 8 10
∝
0.05 0 0 0 0 0 0
Is = Σ x Is
Hz V
Is =
Σ x Is RESET
1 1 1
Σ
I
INST
D
0.05 0.05 0.1 0.2 0.3 0.4
x t =
=
Σ x Is
1 2 4 8 10
∝
x t = Σ
I
INST
LT1
t S1 V1 E1
I
=
Σ x Is
z Electronic, multi characteristic z Fine settings, wide range z Integral instantaneous elements
Overcurrent Protection Numerical Relay
I>1 I>2 Time
I>3 I>4 Current
z Multiple characteristics and stages z Current settings in primary or secondary values z Additional protection elements
Co-ordination
Overcurrent Protection Co-ordination Principle z Relay closest to fault must operate first R1
R2
IF1
T
z Other relays must have adequate additional operating time to prevent them operating z Current setting chosen to allow FLC
IS2 IS1
Maximum Fault Level
I
z Consider worst case conditions, operating modes and current flows
Overcurrent Protection Co-ordination Example E
D
B
C
A
Operating time (s)
10
E D
1
C B 0.1
0.01
Current (A)
FLB
FLC
FLD
Overcurrent Protection IEC Characteristics 1000
t =
0.14 (I0.02 -1)
z VI
t = 13.5 (I2 -1)
z EI
t =
80 (I2
Operating Time (s)
z SI
100
10 LTI SI
1
-1)
z LTI t = 120 (I - 1)
VI EI
0.1 1
10
100
Current (Multiples of Is)
Overcurrent Protection Operating Time Setting - Terms Used
z Published characteristcs are drawn against a multiple of current setting or Plug Setting Multiplier z Therefore characteristics can be used for any application regardless of actual relay current setting z e.g at 10x setting (or PSM of 10) SI curve op time is 3s
1000
Operating Time (s)
z Relay operating times can be calculated using relay characteristic charts
100
10
1
0.1 1
100 10 Current (Multiples of Is)
Overcurrent Protection Current Setting z Set just above full load current z allow 10% tolerance z Allow relay to reset if fault is cleared by downstream device z consider pickup/drop off ratio (reset ratio) z relay must fully reset with full load current flowing z PU/DO for static/numerical = 95% z PU/DO for EM relay = 90% z e.g for numerical relay, Is = 1.1 x IFL/0.95
Overcurrent Protection Current Setting
z Current grading z ensure that if upstream relay has started downstream relay has also started
R1
R2
IF1
z Set upstream device current setting greater than
downstream relay e.g. IsR1 = 1.1 x IsR2
Overcurrent Protection Grading Margin
z Operating time difference between two devices to ensure that downstream device will clear fault before upstream device trips z Must include z breaker opening time z allowance for errors z relay overshoot time z safety margin
GRADING MARGIN
Overcurrent Protection Grading Margin - between relays
R1
R2
z Traditional z breaker op time
-
0.1
z relay overshoot
-
0.05
z allow. For errors
-
0.15
z safety margin
-
0.1
z Total z Calculate using formula
0.4s
Overcurrent Protection Grading Margin - between relays z Formula z t’ = (2Er + Ect) t/100 + tcb + to + ts z Er = relay timing error z Ect = CT measurement error z t = op time of downstream relay z tcb = CB interupting time z to = relay overshoot time z ts = safety margin z Op time of Downstream Relay t = 0.5s z 0.375s margin for EM relay, oil CB z 0.24s margin for static relay, vacuum CB
Overcurrent Protection Grading Margin - relay with fuse
z Grading Margin = 0.4Tf + 0.15s over whole characteristic z Assume fuse minimum operating time = 0.01s z Use EI or VI curve to grade with fuse z Current setting of relay should be 3-4 x rating of fuse to ensure co-ordination
Overcurrent Protection Grading Margin - relay with upstream fuse
Tf Tr I FMAX
z 1.175Tr
+
Allowance for CT and relay error
or z Tf = 2Tr + 0.33s
0.1 CB
+
0.1 Safety margin
=
0.6Tf Allowance for fuse error (fast)
Overcurrent Protection Time Multiplier Setting
z Used to adjust the operating time of an inverse characteristic z Not a time setting but a multiplier z Calculate TMS to give desired operating time in accordance with the grading margin
Operating Time (s)
100
10
1
0.1 1
100 10 Current (Multiples of Is)
Overcurrent Protection Time Multiplier Setting - Calculation
z Calculate relay operating time required, Treq z consider grading margin z fault level z Calculate op time of inverse characteristic with TMS = 1, T1 z TMS = Treq /T1
Overcurrent Protection Co-ordination - Procedure
z Calculate required operating current z Calculate required grading margin z Calculate required operating time z Select characteristic z Calculate required TMS z Draw characteristic, check grading over whole curve Grading curves should be drawn to a common voltage base to aid comparison
Overcurrent Protection Co-ordination Example
200/5
100/5 I
FMAX = 1400 Amp
B Is = 5 Amp
A Is = 5 Amp; TMS = 0.05, SI
z Grade relay B with relay A z Co-ordinate at max fault level seen by both relays = 1400A z Assume grading margin of 0.4s
Overcurrent Protection Co-ordination Example
200/5
100/5 I
FMAX = 1400 Amp
B Is = 5 Amp
A Is = 5 Amp; TMS = 0.05, SI
z Relay B is set to 200A primary, 5A secondary z Relay A set to 100A ∴ If (1400A) = PSM of 14 relay A OP time = t = 0.14 x TMS = 0.14 x 0.05 = 0.13 (I0.02 -1) (140.02 -1) z Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s z Relay A uses SI curve so relay B should also use SI curve
Overcurrent Protection Co-ordination Example 200/5
B Is = 5 Amp
100/5
A
I FMAX = 1400 Amp
Is = 5 Amp; TMS = 0.05, SI
z Relay B Op time = 0.13 + grading margin = 0.13 + 0.4 = 0.53s z Relay A uses SI curve so relay B should also use SI curve z Relay B set to 200A ∴ If (1400A) = PSM of 7 0.14 = 3.52s relay B OP time TMS = 1 = 0.14 x TMS = (I0.02 -1) (70.02 -1) z Required TMS = Required Op time = 0.53 = 0.15 Op time TMS=1 3.52 z Set relay B to 200A, TMS = 0.15, SI
Overcurrent Protection LV Protection Co-ordination 1000S Long time inverse
100S Fuse
TX damage
1.0S
MCCB (cold)
10S
Relay 3
0.1S
Relay 2
Relay 4
0.01S 0. 1kA ZA2121
10kA
1000kA
Overcurrent Protection Blocked OC Schemes
Graded protection R3 R2 IF2
R1
Block t > I > Start
IF1 M ZA2135
(Transient backfeed ?)
Blocked protection
Delta / Star Transformers
Overcurrent Protection Transformer Protection - 2-1-1 Fault Current Turns Ratio = √3 :1
z A phase-phase fault on one side of transformer produces 2-1-1 distribution on other side z Use an overcurrent element in each phase (cover the 2x phase) z 2∅ & EF relays can be used provided fault current > 4x setting
Iline Idelta
0.866 If3∅
Overcurrent Protection Transformer Protection - 2-1-1 Fault Current
Turns Ratio = √3 :1
z Istar = E∅-∅/2Xt = √3 E∅-n/2Xt z Istar = 0.866 E∅-n/Xt z Istar = 0.866 If3∅
Iline
z Idelta = Istar/√3 = If3∅ /2 Idelta
0.866 If3∅
z Iline = If3∅
Overcurrent Protection Transformer Protection - 2-1-1 Fault Current
51
51
HV
LV
z Grade HV relay with respect to 2-1-1 for ∅-∅ fault z Not only at max fault level
86.6%If3∅
If3∅
Ø/Ø
Use of High Sets
Overcurrent Protection Instantaneous Protection
z Fast clearance of faults z ensure good operation factor, If >> Is (5 x ?) z Current setting must be co-ordinated to prevent overtripping z Used to provide fast tripping on HV side of transformers z Used on feeders with Auto Reclose, prevents transient faults becoming permanent z AR ensures healthy feeders are re-energised z Consider operation due to DC offset - transient overreach
Overcurrent Protection Instantaneous OC on Transformer Feeders
HV2
HV1
LV
z Stable for inrush
HV2 TIME
z Set HV inst 130% IfLV z No operation for LV fault
HV1 LV
z Fast operation for HV fault
IF(LV)
IF(HV)
1.3IF(LV)
CURRENT
z Reduces op times required of upstream relays
Earthfault Protection
Overcurrent Protection Earth Fault Protection
z Earth fault current may be limited z Sensitivity and speed requirements may not be met by overcurrent relays z Use dedicated EF protection relays z Connect to measure residual (zero sequence) current z Can be set to values less than full load current z Co-ordinate as for OC elements z May not be possible to provide co-ordination with fuses
Overcurrent Protection Earth Fault Relay Connection - 3 Wire System
E/F
OC
OC
OC
z Combined with OC relays
E/F
OC
OC
z Economise using 2x OC relays
Overcurrent Protection Earth Fault Relay Connection - 4 Wire System
E/F
OC
OC
OC
z EF relay setting must be greater than normal neutral current
E/F
OC
OC
OC
z Independent of neutral current but must use 3 OC relays for phase to neutral faults
Overcurrent Protection Earth Fault Relays Current Setting
z Solid earth z 30% Ifull load adequate
z Resistance earth z setting w.r.t earth fault level z special considerations for impedance earthing - directional?
Overcurrent Protection Sensitive Earth Fault Relays A B C
z Settings down to 0.2% possible z Isolated/high impedance earth networks
E/F
z For low settings cannot use residual connection, use dedicated CT z Advisable to use core balance CT z CT ratio related to earth fault current not line current z Relays tuned to system frequency to reject 3rd harmonic
z Need to take care with core balance CT and armoured cables z Sheath acts as earth return path z Must account for earth current path in connections - insulate cable gland
Thank you for interesting in our services. We are a non-profit group that run this website to share documents. We need your help to maintenance this website.