© 2008 ABB Oy 1MRS756670 B

Front panel HMI

REF615 Front panel HMI Three dedicated LEDs: Ready, Start,Trip

4 x 16 character display (LCD)

11 programmable LEDs ENTER button CLEAR button

CB Control, OPEN and CLOSE buttons

Front communication port MENU button

© 2008 ABB Oy 1MRS756670 B

ESC button LOCAL/REMOTE button, HELP

Navigation buttons AUTHORIZATION

REF615 LCD display options Small LCD, mono-spaced 4 x 20 characters, variable width 4 x 8 (or more) characters

„

Large LCD, mono-spaced 10 x 20 characters, variable width 8 x 8 (or more) characters

„

Background light with powersaving mode

© 2008 ABB Oy 1MRS756670 B

„

© 2008 ABB Oy 1MRS756670 B

REF615 LCD display readouts „

IEC 61850 naming, “classic” IEC symbols or ANSI codes: (PHLPTOC1, 3I>, 51P-1)

„

Fault indications

„

Four fault recordings with time stamp

„

Measurements: „

Currents

„

Historical data

„

Number of auto-reclosures (ARs) etc.

© 2008 ABB Oy 1MRS756670 B

REF615 LCD display readouts, cont’d

© 2008 ABB Oy 1MRS756670 B

REF615 keypad

„

Name or code of protected objects

„

Settings in 4 setting groups

„

Configurations such as protocol settings etc.

„

Product information, serial number, software version, identification etc.

REF615 keypad „

Closing circuit breaker

„

Opening circuit breaker

The circuit breaker can be controlled via the LHMI with the Open and Close buttons when the IED is set to local control mode and you are authorized to access control operations.

© 2008 ABB Oy 1MRS756670 B

To confirm the operation, select Yes or No and press Enter

© 2008 ABB Oy 1MRS756670 B

REF615 keypad

© 2008 ABB Oy 1MRS756670 B

REF615 keypad

REF615 keypad

© 2008 ABB Oy 1MRS756670 B

Press Clear button to activate the Clear view. The items that can be cleared are as below: „

Indications and LEDs

„

Alarm LEDs

„

Events

„

Disturbance records

„

Trip lockout functions

„

Condition monitoring functions

„

Demand values

„

Fault records

„

Thermal overload alarm

REF 615 LEDs Protection indication LEDs Ready LED „

Off : Auxiliary supply voltage is disconnected.

„

On : Normal operation

„

Blinking mode: Internal Relay Fault or relay in test mode

Start LED „

Off : Normal operation

„

On : Protection has started

„

Blinking mode: Protection has started and blocked

© 2008 ABB Oy 1MRS756670 B

Trip LED „

Off : Normal operation

„

On : Protection has tripped

REF 615 LEDs Alarm indicator LEDs (11 pcs) Off „

Normal operation. No alarms.

On „

Non-latched mode: alarm is still on.

„

Latched mode: alarm is still on or it is off but has not been acknowledged.

„

Latched blinking mode: alarm is still on but has been acknowledged.

© 2008 ABB Oy 1MRS756670 B

Blinking „

Latched blinking mode: alarm is on and it has not been acknowledged.

© 2008 ABB Oy 1MRS756670 B

O261 REF615 and PCM600

SETTING EXERCISE FOR REF615

Setting exercises for REF615 by using the local HMI Use the navigation push buttons to navigate in the menu structure. To change a setting, press the Enter button. The user authorization is set off in the training relays. You can first use about 10-15 minutes for browsing in the different menus to see what information is available in the menu tree. Please do not change the IP address of the relays in the training room. All REF615 relays and the computers are in the same network and a specific IP address is reserved for each relay and computer. The IP address of each relay is mentioned in the sticker near the relay. You can also check the IP address for the rear port via relay menu Main menu / Configuration / Communication / Ethernet / Rear port(s)

Change the following parameters Change the overcurrent protection 3I> settings (setting group 1). You should find the setting via the following menu: Settings - Settings - Edit Group 1 - Current protection - 3I> Operation: On Start value: 2.0 x In Operate delay time: 750 ms Operationg curve type: IEC Def. Time Measurement mode: DFT

ABB Oy

O261 REF615 and PCM600

SETTING EXERCISE FOR REF615

Change the overcurrent protection 3I>> (1) settings (setting group 1). You should find the setting via the following menu: Settings - Settings - Edit Group 1 - Current protection - 3I>>(1)

Operation: On Start value: 4.5 x In Operate delay time: 200 ms Operationg curve type: IEC Def. Time Measurement mode: P-to-P + backup

Change the overcurrent protection 3I>> (2) settings (setting group 1). You should find the setting via the following menu: Settings - Settings - Edit Group 1 - Current protection - 3I>>(2) Operation: Off Change the overcurrent protection 3I>>> settings (setting group 1). You should find the setting via the following menu: Settings - Settings - Edit Group 1 - Current protection - 3I>>> Operation: On Start value: 7.0 x In Operate delay time: 40 ms

Change the circuit breaker control settings. You should find the settings via the following menu: Configuration - Control - I CB Select timeout: 10 000 ms Pulse lenght: 100 ms Change the current measurement settings. You should find the settings via the following menu: Configuration - Measurements - 3I Measurement mode: RMS Demand interval: 15 min

ABB Oy

O261 REF615 and PCM600

SETTING EXERCISE FOR REF615

Change the settings of the trip logic. You should find the settings via the following menu: Configuration - Trip logic - Master Trip(1) Trip pulse time: 160 ms Trip output mode: Non-latched

Set the threshold voltage for the binary inputs. Main Menu/Configuration/ I/O modules / Common settings Threshold voltage: 32V

Inject current to the relay by using the SIM600 simulator. Verify the operation of the start and trip leds and indications on the display. Use Clear button to clear the Indications, LEDs and Alarm LEDs after each trip. Read the fault records. Main Menu/Monitoring / Recorded data / Fault record 1....4

Open and close the circuit breaker by using the local HMI: At first set the Local / Remote button to Local mode (L). The interlocking rules in REF615 are programmable. In the training relays the interlockins are programmed as follows: Open the CB: Close the CB:

Always possible Earth-switch has to in open position and protection trip signal is not active and CB truck (disconnector) is in OK position

Try to open and close the circuit breaker by using Open (0) and Close (I) buttons in the relay HMI. Try also close the circuit breaker when the earthswitch is closed.

ABB Oy