0178-444-ENG
Short Description
Download 0178-444-ENG...
Description
03.10
Instruction Manual
COMSAB II Computerized Control System for refrigerating compressors
Version 1.06
0178-444--ENG
1
Preface The present instruction manual, that covers the COMSAB II gateway, describes how to install the unit and how to use the SABROE protocol 0178-400. COMSAB II gives the user access to read and write data in the following SABROE compressor control units: PROSAB II, UNISAB S/R/RT/RTH and UNISAB II.
COMSAB II vers. 1.06 additionally gives the user access to read and write data in the Sabroe Chiller Control Unit. The COMSAB II functions as a gateway, converting from the proprietary HDLC/RS485 protocol, which is used between the compressor control units, to a very simple ascii/ RS232 protocol (0178-400) which is described in this manual. This manual refers to COMSAB software version 1.06.
YORK Refrigeration P.O. Box 1810, DK--8270 Hoejbjerg Chr. X’s Vej 201, Aarhus, Denmark
2
Phone: +45 87 36 70 00 Fax: +45 87 36 77 05
0178-444--ENG
Contents Preface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Port 1 -- RS485 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Port 2 - RS232 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diodes: . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4 5 5 5 6 6
Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Message format . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reply from the COMSAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Possible error messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Response time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7 7 7 8 8 8 8
Table 0178-402 - Points to READ for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
12
COP - valves Points to READ . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
19
Table 0178-402 - Points to WRITE for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Capacity Control (communication) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COMPRESSOR CONTROL MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . COMPRESSOR MODES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CONTROL SYSTEMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MULTISAB STATE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
21 26 28 28 28 28
Table of alarms/warnings for UNISAB II . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
29
Chiller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
31
List of Versions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
42
0178-444--ENG
3
Installation: COMSAB II is installed as shown in the figure below. You would need:
-- a 2 wire screened RS485 communication cable (See the instruction book, Installing a data
-- a 2 wire power cable
communications cable for the right commu-
-- a 3 wire RS232 cable
nication cable type). RS232 cable
PLC/PC
J2 Code
J6 J7 CPU51 Interface
COMSAB II Power J1 4 1 Power cable 24 VAC/VDC RS485 BUSS
Port 1 J3 9 1
Diodes Port 3 J5 Port 2 J4 9 1
RS485 cable
UNISAB/PROSAB II 1
2
There are no jumpers or switches on COMSAB II which have to be set before operation. Place the COMSAB II, the RS232 cable and the RS485 communication cable in a distance of minimum 30 cm from contactors, high power cables or any other unit radiating electromagnetic noise.
4
Max 14
Protective ground potential should best be the same for UNISAB and COMSAB as well as for any PCs or PLCs connected to it. A eavy gauge wire (6 mm2) running along with the communications tables from one protective ground to the next, may prevent a lot of trouble. Please observe local safety regulations which may not allow this.
0178-444--ENG
Dimensions: 237 mm
110 mm
J6
J2 Code
J7
Diodes
UNISAB
J5 4
J1
1
9
J3
1
J4
9
1
Depht = 68 mm incl. coverplate
Power:
Pin #1:
Chassis (Ground connection)
COMSAB II has to be supplied with either 15-28 VAC or 18-40 VDC on plug J1:
Pin #2:
AC / DC +
Pin #3:
AC / DC --
Pin #4:
Not connected
Consumption 12 VA.
Power J1 1
2
3
Port 1 -- RS485:
4
The plug (J3) connections are:
Ground +
Pin #1:
--
Gnd
Signal ground.
Pin #2 + 8: Tx/Rx + Transmit/Receive Data.
24 VAC or DC
Pin #4 + 6: Tx/Rx -- Transmit/Receive Data.
Port 1 J3 TX+Term. Gnd TX+Data 1
2
TX-Term. TX--Data
3
4
RX-Term.
RX--Data 5
6
RX+Term.
RX+Data 7
8
9
Cable screen
+
0178-444--ENG
--
5
nected to the RS485 network. The setting in UNISAB II must be 1200 and 9600 baud.
*In order to terminate the communication, pins 2 + 3 and pins 4 + 5 must be connected together -- as shown.
Port 2 - RS232: The data transmission to PLC/PC is based on the RS232C async serial standard.
The baud rate between COMSAB II and Danbuss is set up automaltically to be the same
No handshake signals are being used, so the plug (J4) connections are very simple:
as configured in the UNISAB/PROSAB con-
Port 2 J4
Gnd
TxD
1
2
Signal ground
RxD 3
4
6
Transmitted Data
Pin #1:
Gnd
Signal ground.
Pin #2:
TxD
Transmitted Data.
Pin #8:
RxD
Received Data.
The data format is: 8 data bit, 1 stop bit and even parity. Note that the COMSAB II is functioning as a DTE (Data Terminal Equipment). The baud rate between COMSAB II and PLC/PC is set up automatically, the baud rate setting in the PLC/PC must be 9.600 or 19.200 baud. Communication is initiated by the PLC/PC issuing a number of READ messages (1-3)
6
5
7
8
9
Received Data
until COMSAB II responds. (COMSAB II initialize at 19.200 baud at power on).
Diodes: There are 4 diodes on COMSAB II, with the following function: Yellow ª (Idle) -- Light when net activity on port 1 (RS485). Green ª (Frame err.) -- Light when COMSAB II has synchronized itself to the baud rate on the net (RS485). Red ª (Overfl.) -- Light when COMSAB II is master. Yellow ª= (Power) -- Light when power is on.
0178-444--ENG
Protocol: SABROE protocol 0178-400 describes the data communication between a central computer (PLC or PC), and a COMSAB II module. This protocol allows any type of computer (when above hardware is available) to retrieve data from a UNISAB or a PROSAB control panel, through the COMSAB II module. The protocol always waits to get polled by the central computer. It never starts a communication by it self. The communication is based on the central computer sending a telegram (a message) to the COMSAB II module. The telegram should always consist of a total of 11 (ascii) characters, that is 9 message characters plus 2 control characters STX (Start of TeXt) and ETX (End of TeXt).
Index
The value must be 20H [¬] = UNISAB/PROSAB # 1. The value must be 21H [!] = UNISAB/PROSAB # 2. The value must be 2EH [.] = UNISAB/PROSAB # 14. Point
Data field The Data field contains always 6 characters. The Data field can contain any integer value from --990 to + 99999. The value must be right justified. Not used characters must be space filled.
Message format:
The value in the Data field may be multiplied by a factor of 10. See Data format/Range in Read table and/or Write table.
Stx - Code - Index - Point - Data--field - Etx Starts the telegram (1 character). Stx = 02H [ ^B] Code
Indicates read/write telegram (1 character). The value should be 20H [¬] when reading data. The value should be 21H [!] when writing data. The value should be 22H [”] when reading COP data from UNISAB II.
0178-444--ENG
Indicates the address of the variable which should be read or changed (1 character). The value must be 20H-FFH according to the table 0178-402.
(The corresponding ASCII character is shown in sharp parenthesis, where [¬] means an ASCII ’space’)
Stx
Indicates the dialing # of the UNISAB/PROSAB which must receive this telegram (1 character).
Etx
Ends the telegram (1 character). Etx= 03H [^C]
Reply from the COMSAB II: When writing data by a COMSAB II, the reply message is a copy of the message sent to the COMSAB II. Data written to UNISAB II is checked in the UNISAB II. If the value exceeds the limits that are built into UNISAB II (see UNISAB II
7
instruction book for reference) then UNISAB II accepts and returns the lowest or highest of the built-in limits, depending on which limit is exceeded. Data written to UNISAB I or PROSAB II is checked in the COMSAB II. If the value exceeds the limits that are build into COMSAB II, then COMSAB II returns an error message with code F____6. For reference -- see the limits table under note (5), placed under notes following the table Points to Write. When reading data by a COMSAB II, the reply message is a copy of the message sent to the COMSAB II, except from the Data field which will be filled with the value asked for. Depending on the data type then the value returned may be in 1/10 of the unit asked for, i.e. +/-- xx.x BAR, +/-- xxx.x ’C, xxx.x % etc, se Data format/Range for the specific point asked for.
If a parity error occurs, or the number of characters received in a message by the COMSAB II is different from 11, no reply will be given to the central computer.
Tables: In the table 0178-402 /Read and Write, details about selecting the correct point, details about translating the reply for compressor control mode etc are given.
Response time: There is always a time delay from the moment a change in e.g. pressure on the compressure unit is seen until it actually can be read by the COMSAB II module. The worst case time delay can approximately be calculated with this equation: TimeDelay = 13 + ( 1,5 * N ) seconds at 1200 Baud. TimeDelay = 7 + ( 0,8 * N ) seconds at 2400 Baud.
Possible error messages:
TimeDelay = 1 + ( 0,1 * N ) seconds at 19200 Baud.
This protocol gives an error message if the communication fails. The error message is given in the Data field:
N is the number of compressors connected to this COMSAB II module.
Data field:
_____
No error ( 6 spaces ).
Data field:
F___3
Code does not exist.
Data field:
F___4
Index does not exist.
Data field:
F___5
Point does not exist.
Data field:
F___6
Read/write not possible.
Another delay occurs in the communication between the COMSAB II and the central computer. This delay depends on the sequence of communications from the central computer to the COMSAB II. (As worst case). At worst, this time delay must be added to the time delay calculated above.
Data field:
F___7
UNISAB/PROSAB does not exist.
Examples:
Data field:
F___8
No such control system.
Data field:
F___9
Syntax error in message received.
8
In the following some message examples are given. The message codes are shown both as HEX values and as ASCII characters [in sharp parenthesis].
0178-444--ENG
Example 1: Read the oil temperature in compressor #5:
Telegram from the central computer to the COMSAB II:
Telegram from the central computer to the COMSAB II:
Stx - Code - Index - Point - Data--field - Etx 02H 21H 20H 30H _ _ -- 2 5 0 03H [^B!!0¬¬--250^C]
Stx - Code - Index - Point - Data--field - Etx 02H 20H 24H 22H _ _ _ _ _ _ 03H [^B¬$”¬¬¬¬¬¬^C]
Reply from the COMSAB II to the central computer:
Reply from the COMSAB II to the central computer:
Stx - Code - Index - Point - Data--field - Etx 02H 21H 20H 30H _ _ -- 2 5 0 03H [^B!!0¬¬--250^C]
Stx - Code - Index - Point - Data--field - Etx 02H 20H 24H 22H _ _ _ 5 3 1 03H [^B¬$”¬¬¬531^C]
Set point 2 for suction pressure control has now been changed to the value --25,0 ’C/R.
This means that the oil temperature is 53,1 ’C. Example 2: Read the control mode of compressor #2: Telegram from the central computer to the COMSAB II: Stx - Code - Index - Point - Data--field - Etx 02H 20H 21H 3FH _ _ _ _ _ _ 03H [^B¬!?¬¬¬¬¬¬^C] Reply from the COMSAB II to the central computer:
Example 4: Start compressor #3. Telegram from the central computer to the COMSAB II: Stx - Code - Index - Point - Data--field - Etx 02H 21H 22H 35H _ _ _ _ _1 03H [^B!”5¬¬¬¬¬1^C] Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 21H 22H 35H _ _ _ _ _1 03H [^B!”5¬¬¬¬¬1^C]
Stx - Code - Index - Point - Data--field - Etx 02H 20H 21H 3FH _ _ _ _ 3 0 03H [^B¬!?¬¬¬¬30^C]
Compressor #3 will now start.
According to the table Control modes this means the compressor is in remote control.
Telegram from the central computer to the COMSAB II:
Example 3: Write a new set point 2 for suction pressure control, on compressor #1:
Stx - Code - Index - Point - Data--field - Etx 02H 21H 22H 35H _ _ _ _ _1 03H [^B!”5¬¬¬¬¬1^C]
0178-444--ENG
Example 5: Start compressor #3 -- error message.
9
Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 21H 22H [^B!”5F¬¬¬¬6^C]
35H
F _ _ _ _ 6 03H
Compressor #3 will not start. Perhaps because compressor #3 does not exist (in the communications system), maybe the compressor is not in remote control or the compressor cannot start because of an alarm in the control system. Example 6: Read alarms from compressor #3.
Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 34H _ _ _ _ _ _ 03H [^B¬”4¬¬¬¬¬¬^C] read first alarm in the queue Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 34H _ _ _ _ _ 0 03H [^B¬”40¬¬¬¬¬^C] no alarm in the queue OR: Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx
In the UNISAB II all alarms, i.e. an alarm number, are stored in an alarm-queue, containing max. 5 alarms.
02H 20H 22H 34H _ _ _ _ 4 2 03H [^B¬”4¬¬¬¬42^C] first alarm is ”High oil temperature”
The first (oldest) alarm is stored in ”alarm 1” (read point 52), the next alarm in ”alarm 2” (read point 53) and the last (newest) alarm is stored in ”alarm 5” (read point 56) -- see read table.
Telegram from the central computer to the COMSAB II:
To read the UNISAB II alarm-queue you will have to do the following: Send a read message -- reading point 52. If there isn’t any alarm in the UNISAB II then the reply will be a 0 (zero). If there is one (or more) alarms in the UNISAB II then the reply will be the number of the oldest alarm, i.e. a alarm number from 31 to 76 -- see the table of alarm/warnings. To see if there is more than one alarm in the queue, send a read message reading point 53, then point 54, 55 and 56 until the reply from the COMSAB II is a 0 (zero). Telegram from the central computer to the COMSAB II:
10
Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 35H _ _ _ _ _ _ 03H [^B¬”5¬¬¬¬¬¬^C] read second alarm in the queue Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 35H _ _ _ _ _ 0 03H [^B¬”5¬¬¬¬¬0^C] no more alarms in the queue OR: Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 34H _ _ _ _ 4 7 03H [^B¬”5¬¬¬¬47^C] second alarm is ”Compressor motor error” and so on...
0178-444--ENG
Example 7: Read warnings from compressor #3.
Reply from the COMSAB II to the central computer:
In the UNISAB II all warnings, i.e. a warning number, are stored in an warning-queue, containing max. 5 warnings.
Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 39H _ _ _ _ _ 0 03H [^B¬”9¬¬¬¬¬0^C] no warnings in the queue
The first (oldest) warning are stored in ”warning 1” (read point 57), the next warning in ”warning 2” (read point 58) and the last (newest) warning are stored in ”warning 5” (read point 61) -- see read table.
OR: Reply from the COMSAB II to the central computer:
The procedure for reading the warning-queue is the same as for reading the alarm-queue, see example 6.
Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 39H _ _ _ _ 4 2 03H [^B¬”9¬¬¬¬42^C] first warning is ”High oil temperature”
To read the UNISAB II warning-queue you will have to do the following:
Telegram from the central computer to the COMSAB II:
Send a read message -- reading point 57.
Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 3AH _ _ _ _ _ _ 03H [^B¬”:¬¬¬¬¬¬^C] read second warning in the queue
If there isn’t any warning in the UNISAB II then the reply will be a 0 (zero). If there is one (or more) warnings in the UNISAB II then the reply will be the number of the oldest warning, i.e. a warning number from 31 to 76 -- see the table of alarm/warnings. To see if there is more than one warning in the queue, then send a read message reading point 58, then point 59, 60 and 61, until the reply from the COMSAB II is a 0 (zero). Telegram from the central computer, to the COMSAB II: Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 39H _ _ _ _ _ _ 03H [^B¬”9¬¬¬¬¬¬^C] read first warning in the queue
0178-444--ENG
Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 3AH _ _ _ _ _ 0 03H [^B¬”:¬¬¬¬¬0^C] no more warnings in the queue OR: Reply from the COMSAB II to the central computer: Stx - Code - Index - Point - Data--field - Etx 02H 20H 22H 3AH _ _ _ _ 3 2 03H [^B¬”:¬¬¬¬32^C] second warning is ”High suction pressure” and so on...
11
Table 0178-402 - Points to READ for UNISAB II: Name of value:
COMSAB II
Available on:
Data format
POINT
PII/UI
U-II
Range
UNIT
Suction gas temp.
32
X
X
I*0,1
°C
Disch. gas temp.
33
X
X
I*0,1
°C
Oil temp
34
X
X
I*0,1
°C
Suct.pressure
35
X
X
I*0,1
BAR
Disch.pressure
36
X
X
I*0,1
BAR
Suct.pressure
37
X
X
I*0,1
’C/R
Disch.pressure
38
X
X
I*0,1
’C/R
Capacity position
39
X
X
I*0,1
%
Volume slide position
40
X(7)
X
I*0,1
%
Motor current
41
X
X
I*0,1
Amps
Universal regulator
42
X
I*0,1
%
Oil filter diff.pressure (s) / intermediate pressure (r)
43
X(8)
X
I*0,1
BAR
Suct. gas superheat
44
X
X
I*0,1
°C
Brine /intermediate temperature
45
X(9)
X
I*0,1
°C
Running hours
46
X(10)
X(10)
UI
Hours
Setp.1, suct.press.
47
X
X
I*0,1
°C/R
Setp.2, suct.press.
48
X
X
I*0,1
°C/R
N.zone, suct.press
49
X
X
I*0,1
°C/R
Set point actual, brine temp
50
X
X
I*0,1
°C
N.zone, brine temp
51
X
X
I*0,1
°C
Alarm 1
52
X
X
B
(4)
Alarm 2
53
X
X
B
(4)
Alarm 3
54
X
X
B
(4)
Alarm 4
55
X
X
B
(4)
Alarm 5
56
X
X
B
(4)
Warning 1
57
X
X
B
(4)
Warning 2
58
X
X
B
(4)
Warning 3
59
X
X
B
(4)
Warning 4
60
X
X
B
(4)
Warning 5
61
X
X
B
(4)
12
0178-444--ENG
Name of value:
COMSAB II
Available on:
Data format
POINT
PII/UI
U-II
Range
UNIT
Compressor mode
62
X
X
B
(3)
Control mode
63
X
X
B
(2)
Startsequence no.
64
X
X
B
0-14
Suct.system 1 regulator
65
X
B
1-14
Suct.system 2 regulator
66
X
B
1-14
Suct.system 3 regulator
67
X
B
1-14
Suct.system 4 regulator
68
X
B
1-14
Suct.system 5 regulator
69
X
B
1-14
Suct.system 6 regulator
70
X
B
1-14
Suct.system 7 regulator
71
X
B
1-14
Suct.system 8 regulator
72
X
B
1-14
Suct.system 9 regulator
73
X
B
1-14
Suct.system 10 regulator
74
X
B
1-14
Suct.system 11 regulator
75
X
B
1-14
Suct.system 12 regulator
76
X
B
1-14
Suct.system 13 regulator
77
X
B
1-14
Suct.system 14 regulator
78
X
B
1-14
System for this unit
79
X
X
B
1-14
Which control system
80
X
X
B
(5)
Oil pressure
81
X
X
I*0,1
BAR
MultiSab state
82
(X)
(X)
B
(6)
Preceding compr
83
(X)
(X)
B
1-14
Next compr.
84
(X)
(X)
B
1-14
Cmp to follow the next
85
(X)
(X)
B
1-14
Selected sysregulator
86
X
X
B
1-14
Communication errors
87
X
X
I
%
Not used
88
Disch.gas superheat
89
X
I*0,1
°C
Switch reg. SP1/SP2
90
X
B
0-1
Set point actual, suct. press.
91
X
I*0,1
°C/R
P.band, suct. press.
92
X
I*0,1
°C/R
Set point 1, brine temp.
93
X
I*0,1
°C
0178-444--ENG
13
Name of value:
COMSAB II POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
Set point 2, brine temp.
94
X
I*0,1
°C
P. band, brine temp.
95
X
I*0,1
°C
Set point actual, discharge
96
X
I*0,1
°C/R
Set point 1, discharge
97
X
I*0,1
°C/R
Set point 2, discharge
98
X
I*0,1
°C/R
N. zone, discharge
99
X
I*0,1
°C/R
P. band, discharge
100
X
I*0,1
°C/R
Set point actual, external
101
X
I*0,1
%
Set point 1, external
102
X
I*0,1
%
Set point 2, external
103
X
I*0,1
%
N. zone, external
104
X
I*0,1
%
P. band, external
105
X
I*0,1
%
Set point 1, oil pressure
106
X
I*0,1
BAR
Set point 2, oil pressure
107
X
I*0,1
BAR
Switch motor SP1/SP2
108
X
B
0-1
Set point 1, motor curr.
109
X
I
Amps
Set point 2, motor curr.
110
X
I
Amps
Ext. starting permission - normal
111
X
B
0-1
Ext. starting permission - instant
112
X
B
0-1
Start request OK (PMS)
113
X
B
0-1
Set point 1, oil temp. -- cooling
114
X
I*0,1
°C
Set point 2, oil temp. -- heating
115
X
I*0,1
°C
N. zone, oil temp.
116
X
I*0,1
°C
P. band, oil temp.
117
X
I*0,1
°C
Set point 1, suct. gas superheat
118
X
I*0,1
°C
Set point 1, disch. gas temp.
119
X
I*0,1
°C
Set point 1, volume slide
120
X
I*0,1
%
Run time since last start
121
X(11)
UI
Sek
Setpoint 1, capacity
122
X
I*0,1
%
N. zone capacity
123
X
I*0,1
%
P. band capacity
124
X
I*0,1
%
Cap. mode
125
X(13)
B
0-1
Software version
127
X
I
Start-start delay
130
X
I
Sek
Stop-start delay
131
X
I
--
14
0178-444--ENG
Name of value:
COMSAB II POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
Delay before start
132
X
I
--
Delay before stop
133
X
I
--
Suct. press. ramp function
134
X
I
--
Slide max. down time (s)/ Delay up (r)
135
X
I
--
Prelubrication (s)/ Delay down (r)
136
X
I
--
Oil flow switch active (s)/ Take over max. time (r)
137
X
I
--
Oil flow switch delay (s)/ Take over delay (r)
138
X
I
--
Oil flow max. drop out (s)/ M-press. (r)
139
X
I
--
Lubrication time after start (s)/ not used (r)
140
X
I
--
Difference pressure OK (s)/ not used (r)
141
X
I
--
Oil pressure low -- delay
142
X
I
--
Oil filter diff. press. high (s)/ oil pressure high (r)
143
X
I
--
Oil temperature low
144
X
I
--
Oil temperature high
145
X
I
--
Superheat low
146
X
I
--
Superheat high
147
X
I
--
Discharge press. overload
148
X
I
--
Motor current overload
149
X
I
--
Compr. motor starting time
150
X
I
--
PMS feed back
151
X
I
--
Full flow pump starting time (s)/ not used (r)
152
X
I
--
Oil pump starting time (s)/ not used (r)
153
X
I
--
Oil rectifier start
154
X
I
--
Oil rectifier delay
155
X
I
--
Oil rectifier suppress
156
X
I
--
0178-444--ENG
15
Name of value:
COMSAB II POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
Start High press.
157
X
I
--
Communication delay
158
X
I
--
Cap. negative
159
x
I
--
P.band factor, start delay
160
X
B
1-10
P.band factor, stop delay
161
X
B
1-10
P.band factor, delay up (r)
162
X
B
1-10
P.band factor, delay down (r)
163
X
B
1-10
Transfer factor, delay down (r)
164
X
B
1-10
Transfer zone, delay down (r)
165
X
I
%
Take over factor, delay up (r)
166
X
B
1-10
Take over factor, start delay (r)
167
X
B
1-10
Take over zone, delay up (r)
168
X
I
%
Compressor type
170
X
I
1-50
Refrigerant type
171
X
B
1-9
Regulation mode
172
X
B
0-5
VI-control mode
173
X
B
0-1
Automatic start
174
X
B
0-1
Automatic stop
175
X
B
0-1
Prelubrication
176
X
B
0-1
Full flow pump
177
X
B
0-1
Booster
178
X
B
0-1
Compressor no.
179
X
B
0-14
Regulation master choice
180
X
B
0-1
Economizer
181
X
B
0-1
Economizer min. capacity
182
X
I*0,1
%
Economizer max. suct. press.
183
X
I*0,1
°C/R
Common condenser
184
X
B
0-3
HP compr. on two stage
185
X
B
0-1
Discharge cooling
186
X
B
0-1
Oil cooling type
187
X
B
0-4
Motor current range
188
X
I
Amps
Swept volume
189
X
I
m3/h
Cold store control
190
X
B
0-1
16
0178-444--ENG
COMSAB II
Name of value:
POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
Out door temp. compensation
191
X
B
0-1
Total unload
192
X
B
0-1
Baud rate
193
X
I
baud
Oil rectifier
194
X
B
0-1
Eur./US-units
195
X
B
0-1
Factory reset
196
X
B
0-1
Language
197
X
B
1-15
Contrast
198
X
I
%
Aux. analog input function
199
X
B
0-6
Aux. digital output function
200
X
B
0-5
Cap. lim. low
201
X
I*0,1
%
Cap. lim. high
202
X
I*0,1
%
Manual zero
203
X
I*0,1
%
-- high alarm
204
X
I*0,1
BAR
Suct. pressure limits --
--
-- high warning
205
X
I*0,1
BAR
--
--
-- low warning
206
X
I*0,1
BAR
--
--
-- low alarm
207
X
I*0,1
BAR
Disch.pressure limits
-- high alarm
208
X
I*0,1
BAR
--
--
-- high warning
209
X
I*0,1
BAR
--
--
-- low warning
210
X
I*0,1
BAR
--
--
-- low alarm
211
X
I*0,1
BAR
-- high alarm
212
X
I*0,1
BAR
Oil pressure limits --
--
-- high warning
213
X
I*0,1
BAR
--
--
-- low warning
214
X
I*0,1
BAR
--
--
-- low alarm
215
X
I*0,1
BAR
Oil filter diff. press. limits (s) / Interm.press.limits(r) -- high alarm
216
X
I*0,1
BAR
--
--
-- high warning
217
X
I*0,1
BAR
--
--
-- low warning
218
X
I*0,1
BAR
--
--
-- low alarm
219
X
I*0,1
BAR
-- high alarm
224
X
I*0,1
°C
-- high warning
225
X
I*0,1
°C
Disch.temp. limits --
--
0178-444--ENG
17
Name of value:
COMSAB II POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
--
--
-- low warning
226
X
I*0,1
°C
--
--
-- low alarm
227
X
I*0,1
°C
-- high alarm
228
X
I*0,1
°C
Oil temp. limits --
--
-- high warning
229
X
I*0,1
°C
--
--
-- low warning
230
X
I*0,1
°C
--
--
-- low alarm
231
X
I*0,1
°C
Brine temperature (a) limits / intermediate temp. (b) limits -- high alarm
232
X
I*0,1
°C
--
--
-- high warning
233
X
I*0,1
°C
--
--
-- low warning
234
X
I*0,1
°C
--
--
-- low alarm
235
X
I*0,1
°C
-- high alarm
236
X
I*0,1
°C
Suct.gas superheat --
--
-- high warning
237
X
I*0,1
°C
--
--
-- low warning
238
X
I*0,1
°C
--
--
-- low alarm
239
X
I*0,1
°C
Disch.gas superheat
-- high alarm
240
X
I*0,1
°C
--
--
-- high warning
241
X
I*0,1
°C
--
--
-- low warning
242
X
I*0,1
°C
--
--
-- low alarm
243
X
I*0,1
°C
External input limits
-- high alarm
244
X
I*0,1
%
--
--
-- high warning
245
X
I*0,1
%
--
--
-- low warning
246
X
I*0,1
%
--
--
-- low alarm
247
X
I*0,1
%
Suct. pressure limits
-- high alarm
248
X
I*0,1
°C/R
--
--
-- high warning
249
X
I*0,1
°C/R
--
--
-- low warning
250
X
I*0,1
°C/R
--
--
-- low alarm
251
X
I*0,1
°C/R
Disch.pressure limits
-- high alarm
252
X
I*0,1
°C/R
18
--
--
-- high warning
253
X
I*0,1
°C/R
--
--
-- low warning
254
X
I*0,1
°C/R
--
--
-- low alarm
255
X
I*0,1
°C/R
0178-444--ENG
COP - valves Points to READ: Name of value:
COMSAB II POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
COP
32
X
I*0.1
COP Carnot
33
X
I*0.1
COP Mechanical
34
X
I*0.1
Cooling Power
35
X
I
Kw
Mass Flow
36
X
I
kg/h
Shaft Power
37
X
I
Kw
Motor COP
38
X
I*0.1
--
Volume Flow
39
X
I
m3/h
Superheated Spec. Volume
40
X
I*0.1
l/kg
Saturated Spec. Volume
41
X
I*0,1
l/kg
Enthalpy H1
42
X
I
kJ/kg
Enthalpy H4
43
X
I
kJ/kg
Enthalpy H2
44
X
I
kJ/kg
Please note that the command for reading these points has code 22H.
0178-444--ENG
19
Note the following: X:
Read point 52. If there isn’t any alarm in the UNISAB II then the reply will be a 0 (zero). If there is one (or more) alarms in the UNISAB II then reply will be the number of the oldest alarm, i.e. a alarm number from 31 to 76 - see the table of alarm/warnings. Too see if there are more than one alarm in the queue, then send a read message reading point 53, then point 54, 55 and 56, until the reply from the COMSAB II is a 0 (zero).
Valid for this control system: PII/UI = PROSAB II and UNISAB S/ R/ RT/ RTH. UII = UNISAB II.
(X):
Not used for normal control purpose.
Range: I = Integer, ie. data range -- 32268 -- + 32267 UI= Unsigned integer, ie.data range 0 -- 65535 I*0,1 = Integer value in 1/10 of the unit for this point. I.e. for point 32 ”suction gas temp.” this means that a read value of 325 is 32,5°C. B = Byte, ie. data range -- 128 -- + 127 or 0 -- 255. (1):
Only when hardware option available.
(2):
See ”TABLE OF COMPRESSOR CONTROL MODES”.
(3):
See ”TABLE OF COMPRESSOR MODES”.
(4):
See ”TABLE OF ALARM/ WARNINGS”. In the UNISAB II all alarms, i.e. a alarm number, are stored in an alarm-queue, containing max. 5 alarms. The first (oldest) alarm are stored in ”alarm1” (read point 52), the next alarm in ”alarm 2” (read point 53) and the last (newest) alarm are stored in ”alarm 5” (read point 56) - see read table. To read the UNISAB II alarm-queue you will have to do the following:
20
The same procedure is used when reading the warnings-que. (5):
See ”TABLE OF CONTROL SYSTEMS”.
(6):
See ”TABLE OF MULTISAB STATES”.
(7):
Only PROSAB II and UNISAB S. For UNISAB S this is a calculated value. Not a measured value.
(8):
Only PROSAB II, UNISAB S and UNISAB R.
(9):
Not UNISAB R.
(10):
Running hours are read as hours x 1.
(11):
Run time since last start are read in sec.
(12):
Not implemented.
(13):
Only UNISAB II. See notes for capacity control
(s):
Only screw compressors.
(r):
Only reciprocating compressors.
0178-444--ENG
Table 0178-402 - Points to WRITE for UNISAB II: Name of value:
COMSAB II
Available on:
Data format
POINT
PII/UI
U-II
Range
UNIT
Start sequence no.
32
X
X
B
0-14
Suct.system 1 regulator
33
X
B
1-14
Suct.system 2 regulator
34
X
B
1-14
Suct.system 3 regulator
35
X
B
1-14
Suct.system 4 regulator
36
X
B
1-14
Suct.system 5 regulator
37
X
B
1-14
Suct.system 6 regulator
38
X
B
1-14
Suct.system 7 regulator
39
X
B
1-14
Suct.system 8 regulator
40
X
B
1-14
Suct.system 9 regulator
41
X
B
1-14
Suct.system 10 regulator
42
X
B
1-14
Suct.system 11 regulator
43
X
B
1-14
Suct.system 12 regulator
44
X
B
1-14
Suct.system 13 regulator
45
X
B
1-14
Suct.system 14 regulator
46
X
B
1-14
Setp.1, suct.press.
47
X
X
I*0,1
°C/R
Setp.2, suct.press.
48
X
X
I*0,1
°C/R
N.zone, suct.press
49
X
X
I*0,1
°C/R
Setpoint 1, brine temp
50
X
X
I*0,1
°C
N.zone, brine temp
51
X
X
I*0,1
°C
Setpoint for capacity
52
X (1)
X (1)
I*0,1
%
Start compressor
53
X (3)
X (3)
B
1
Stop compressor
54
X (4)
X (4)
B
0
Select suction system
55
X
X
B
1-14
Setpoint 2, brine temp
56
X
X
I*0,1
°C
Control mode
63
X (2)
B
0-3
P.band, suct. press.
92
X
I*0,1
°C/R
P. band, brine temp.
95
X
I*0,1
°C
Set point 1, discharge
97
X
I*0,1
°C/R
Set point 2, discharge
98
X
I*0,1
°C/R
N. zone, discharge
99
X
I*0,1
°C/R
0178-444--ENG
21
Name of value:
COMSAB II POINT
P. band, discharge
100
Available on: PII/UI
Data format
U-II
Range
UNIT
X
I*0,1
°C/R
101 Set point 1, external
102
X
I*0,1
%
Set point 2, external
103
X
I*0,1
%
N. zone, external
104
X
I*0,1
%
P. band, external
105
X
I*0,1
%
Set point 1, oil pressure
106
X
I*0,1
BAR
Set point 2, oil pressure
107
X
I*0,1
BAR
Set point 1, motor curr.
109
X
I
Amps
Set point 2, motor curr.
110
X
I
Amps
Set point 1, oil temp. -- cooling
114
X
I*0,1
°C
Set point 2, oil temp. -- heating
115
X
I*0,1
°C
N. zone, oil temp.
116
X
I*0,1
°C
P. band, oil temp.
117
X
I*0,1
°C
Set point 1, suct. gas superh.
118
X
I*0,1
°C
Set point 1, disch. gas temp.
119
X
I*0,1
°C
N. zone, capacity
123
X
I*0,1
°C
P. band, capacity
124
X
I*0,1
°C
Start-start delay
130
X
I
Sek
Stop-start delay
131
X
I
--
Delay before start
132
X
I
--
Delay before stop
133
X
I
--
Suct. press. ramp function
134
X
I
--
Slide max. down time (s)/ Delay up (r)
135
X
I
--
Prelubrication (s)/ Delay down (r)
136
X
I
--
PMS feed back
151
X
I
--
Oil rectifier start
154
X
I
--
Oil rectifier delay
155
X
I
--
Oil rectifier suppress
156
X
I
--
Start High press.
157
X
I
--
P.band factor, start delay
160
X
B
1-10
P.band factor, stop delay
161
X
B
1-10
P.band factor, delay up (r)
162
X
B
1-10
22
0178-444--ENG
COMSAB II
Name of value:
POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
P.band factor, delay down (r)
163
X
B
1-10
Transfer factor, delay down (r)
164
X
B
1-10
Transfer zone, delay down (r)
165
X
I
%
Take over factor, delay up (r)
166
X
B
1-10
Take over factor, start delay (r)
167
X
B
1-10
Take over zone, delay up (r)
168
X
I
%
Regulation mode
172
X
B
0-5
Automatic start
174
X
B
0-1
Automatic stop
175
X
B
0-1
Regulation master choice
180
X
B
0-1
Economizer
181
X
B
0-1
Economizer min. capacity
182
X
I*0,1
%
Economizer max. suct. press.
183
X
I*0,1
°C/R
Cold store control
190
X
B
0-1
-- high alarm
204
X
I*0,1
BAR
Suct. pressure limits --
--
-- high warning
205
X
I*0,1
BAR
--
--
-- low warning
206
X
I*0,1
BAR
--
--
-- low alarm
207
X
I*0,1
BAR
-- high alarm
208
X
I*0,1
BAR
Disch.pressure limits --
--
-- high warning
209
X
I*0,1
BAR
--
--
-- low warning
210
X
I*0,1
BAR
--
--
-- low alarm
211
X
I*0,1
BAR
-- high alarm
212
X
I*0,1
BAR
Oil pressure limits --
--
-- high warning
213
X
I*0,1
BAR
--
--
-- low warning
214
X
I*0,1
BAR
--
--
-- low alarm
215
X
I*0,1
BAR
Oil filter diff. press. limits (s) / Intermed. press. limits (r)-- high alarm
216
X
I*0,1
BAR
--
--
-- high warning
217
X
I*0,1
BAR
--
--
-- low warning
218
X
I*0,1
BAR
--
--
-- low alarm
219
X
I*0,1
BAR
-- high alarm
224
X
I*0,1
°C
Disch.temp. limits
0178-444--ENG
23
Name of value:
COMSAB II POINT
Available on: PII/UI
Data format
U-II
Range
UNIT
--
--
-- high warning
225
X
I*0,1
°C
--
--
-- low warning
226
X
I*0,1
°C
--
--
-- low alarm
227
X
I*0,1
°C
-- high alarm
228
X
I*0,1
°C
Oil temp. limits --
--
-- high warning
229
X
I*0,1
°C
--
--
-- low warning
230
X
I*0,1
°C
--
--
-- low alarm
231
X
I*0,1
°C
Brine temperature (a) limits / intermediate temp. (b) limits -- high alarm
232
X
I*0,1
°C
--
--
-- high warning
233
X
I*0,1
°C
--
--
-- low warning
234
X
I*0,1
°C
--
--
-- low alarm
235
X
I*0,1
°C
-- high alarm
236
X
I*0,1
°C
Suct.gas superheat --
--
-- high warning
237
X
I*0,1
°C
--
--
-- low warning
238
X
I*0,1
°C
--
--
-- low alarm
239
X
I*0,1
°C
-- high alarm
240
X
I*0,1
°C
Disch.gas superheat --
--
-- high warning
241
X
I*0,1
°C
--
--
-- low warning
242
X
I*0,1
°C
--
--
-- low alarm
243
X
I*0,1
°C
-- high alarm
244
X
I*0,1
%
External input limits --
--
-- high warning
245
X
I*0,1
%
--
--
-- low warning
246
X
I*0,1
%
--
--
-- low alarm
247
X
I*0,1
%
-- high alarm
248
X
I*0,1
°C/R
Suct. pressure limits --
--
-- high warning
249
X
I*0,1
°C/R
--
--
-- low warning
250
X
I*0,1
°C/R
--
--
-- low alarm
251
X
I*0,1
°C/R
-- high alarm
252
X
I*0,1
°C/R
Disch.pressure limits
24
--
--
-- high warning
253
X
I*0,1
°C/R
--
--
-- low warning
254
X
I*0,1
°C/R
--
--
-- low alarm
255
X
I*0,1
°C/R
0178-444--ENG
Note the following:
Start conditions are:
X :
-- Control mode = Remote + Config/Auto Start = YES or NO
Valid for this control system. PII/UI= PROSAB II and UNISAB S/ R/ RT/ RTH UII= UNISAB II
-- Compressor mode = Ready (4)
Range: I = Integer, ie. data range -- 32268 -- + 32267
Stop conditions are:
UI= Unsigned integer, ie.data range 0 -- 65535 I*0,1 = Integer value in 1/10 of the unit for this point. I.e. for point 32 ”suction gas temp.” this means that a read value of 325 is 32,5°C. B = Byte, ie. data range -- 128 -- + 127 or 0 -- 255 (1)
(2):
(3)
Only PROSAB II, UNISAB S and UNISAB II. Se notes for Capacity Control.
”STOP COMPRESSOR”, point = 54, must have datafield = 0
-- Control mode = Remote + Config/Auto Stop = YES or NO -- Compressor mode = Running (-- overload/suct.lim./disch.lim.) etc. (5)
Min/max limits for values written to PROSAB II or UNISAB I.
Point No.
Min-limit Max-limit Unit
32
0
14
--
33 -- 46 + 55
1
14
--
See ”TABLE OF COMPRESSOR CONTROL MODES”. It is only possible to change to and from mode 0, 2 and 3.
47 + 48
--200
100
°C/R
50 + 56
-- 70
210
°C
49 + 51
0
100
°C
52
0
100
%
”START COMPRESSOR”, poin =53, must have datafield = 1
53
1
1
--
54
0
0
--
0178-444--ENG
25
Capacity Control (communication) It is possible directly to control the capacity of the compressor by sending a capacity setpoint by communication. For UNISAB II it is possible to control the capacity on both screw compressors and reciprocating compressors. For PROSAB II and UNISAB S it is only possible to control the capacity on screw compressors. UNISAB II must be set to REMOTE in picture CONTROL. PROSAB II and UNISAB must be set to REMOTE mode by using the SET button. Screw compressors (when running) will directly follow the capacity value (0--100%) whitch is specified in ”Setpoint for capacity”, point 52 (remember the setpoint is in 1/10 of percent). Notice, however, that the various limiting functions may reduce the compressor capacity. Reciprocating compressors will shift one capacity stage up or down, depending on whether the value specified in ”Setpoint for capacity”, point 52, is above or below the percentage value that correspondes to the capacity stage in question.
26
The timers DELAY UP and DELAY DOWN will be in function if the UNISAB II program version is 1.08 or later. Notice, however, that the various limiting functions may reduce the compressor capacity. When a capacity setpoint is sent to UNISAB II, UNISAB S or PROSAB II it will enter the capacity regulation mode, this can be seen by the fact that the start number is set to zero (the ”old” start number is remembered, UNISAB II stores the number itself and for UNISAB S/ PROSAB II the number is stored in PCCOMSAB II) . UNISAB II, UNISAB S or PROSAB are taken out of capacity regulation mode by sending a new setpoint 1 or 2, neutral zone (NZ) or proportional band (PB) value to one of the other regulators, e.g. suction regulator, brine regulator etc. When UNISAB / PROSAB II are taken out of capacity regulation mode the old start number is reinserted. It is possible to take UNISAB II out of capacity regulation mode by changing START NO back to the old start number on the UNISAB II display. In that case you must reset COMSAB II. This is done by making a power off/ on. Read point 125 ”Cap. mode” will be ”1” if UNISAB II is in capacity regulation mode, else ”Cap mode” will be ”0”.
0178-444--ENG
Start:
Stop:
The compressor can be started in two ways (situation 2 is only possible for UNISAB II)
The compressor can be stopped in two ways (situation 2 is only possible for UNISAB II)
1. By sending the start command ”START COMPRESSOR”, point 53. 2. When the capacity setpoint sent is above 5 % and AUTO START = YES has been configured, the timer START DELAY begins to count down in case of screw compressors. For reciprocating compressors the timer START DELAY starts once the signal is above the lowest capacity stage, i.e. above 25%, 33% or 50%, depending on type. When the timer START DELAY has counted down, the compressor starts and will now follow the setpoint up/down.
0178-444--ENG
1. By sending the stop command ”STOP COMPRESSOR”, point 54 2. When the capacity setpoint sent is below 5 % and AUTO STOP = YES has been configured, the timer STOP DELAY begins to count down in case of screw compressors. For reciprocating compressors the timer STOP DELAY starts once the signal is below the lowest capacity stage, ie below 25%, 33% or 50% depending on type, however, for reciprocating compressors with total unloading, the timer STOP DELAY starts counting down, once the signal is below 0%. When the timer STOP DELAY has counted down, the compressor will stop.
27
COMPRESSOR CONTROL MODES:
Type = 1 = ”PROSAB II”
Control mode = 0 = ”STOPPED”
Type = 2 = ”UNISAB, recip. compr.”
Control mode = 1 = ”MANUAL CONTROL”
Type = 3 = ”UNISAB, screw compr.”
Control mode = 2 = ”AUTOMATIC CONTROL”
Type = 4 = ”UNISAB II”
Control mode = 3 = ”REMOTE CONTROL”
MULTISAB STATE: Mode = 0 = ”NO PERMISSION TO START”
COMPRESSOR MODES: Mode = 0 = NO UNIT CONNECTED Mode = 1 = ”READY” Mode = 2 = ”RUNNNING” Mode = 3 = ”STARTING” Mode = 4 = ”SHUTDOWN” Mode = 5 = ”PAUSE” Mode = 6 = ”PRELUB” Mode = 7 = ”CAPACITY SLIDE DOWN” Mode = 8 = ”RUNNING -- OVERLOAD” Mode = 9 = ”RUNNING DISCH. PRESSURE LIMITATION” Mode = 10 = ”RUNNING SUCT. PRESSURE LIMITATION”
Mode = 1 = ”DO NOT START” (1) Mode = 2 = ”MAY START”
(1)
Mode = 3 = ”RUNS AT 100 % CAPACITY” Mode = 4 = ”LEAD COMPRESSOR” Mode = 5 = ”LAG COMPRESSOR” Mode = 6 = ”STOPPING” Mode = 7 = ”RUNS, BUT WITHOUT LEAD--LAG CONTROL” Mode = 8 = ”STOPPING -RAMPS CAPACITY UP” Mode = 9 = ”STOPPING -RAMPS CAPACITY DOWN” Mode = 10 = ”ROTATUNE MASTER” Mode = 11 =
”ROTATUNE SLAVE”
Mode = 11 = ”STOPPED”
CONTROL SYSTEMS: Type = 0 = NO SYSTEM
28
Note: (1) MULTISAB STATE mode 1 and 2 are reversed in PROSAB II.
0178-444--ENG
Table of alarms/warnings for UNISAB II
Id
Alarm/warning text
Alarm
Warning
#31
Low suction pressure
X
X
#32
High suction pressure
#33
Low suction superheat
X
X
#34
High suction superheat
X (8)
X (8)
#35
Low discharge pressure
X
#36
High discharge pressure
X
X
#37
High discharge temperature
X
X
#38
Low oil pressure
X
X
#39
Low brine-/interm. temperature
X
X
#40
Low discharge temperature
#41
Low oil temperature
X
X
#42
High oil temperature
X
X
#43
High oil filter diff. press.
2)
X
X
#44
Oil system error
2)
X
#45
Capacity error
2)+4)
X
#46
Compressor motor overload
X
#47
Compressor motor error
X
#48
Oil pump error
#49
High motor temperature
#51
Prom error
X (5)
#52
Ram error
X (5)
#53
Cpu error
X (5)
#54
Sensor error
#55
PMS error
#56
No start permision
#57
High differential pressure
#58
High brine-/interm. temperature
#59
High oil pressure
#60 #61
X (7)
X (8)
2)+3)+9)
X (7) X
X (5) X (6) X (6) X (6)
X (6)
X (6)
X (6)
1)
X (6)
X (6)
High intermediate pressure
1)
X (6)
X (6)
Low intermediate pressure
1)
X (6)
X (6)
0178-444--ENG
1)
29
Id
Alarm/warning text
#62
Full-flow pump error
2)+3)
#64
Oil rectifier error
2)
#65
Wrong start no. in sequence
#66
Diagnose EEPROM error
X (6)
#67
Low external input signal
X (6)
X (6)
#68
High external input signal
X (6)
X (6)
#69
Low discharge superheat
X (6)
X (6)
#70
Discharge pressure overload
X (6)
#73
Limiting suction pressure
X (6)
#74
Limiting discharge pressure
X (6)
#75
Limiting brine temp.
X (6)
#76
Limiting hot water
X (6)
#77
Evolution, warning from PLC
X (6)
#78
Limiter, discharge temperature
X (6)
#79
Watch the oil pressure
X (2) (6)
#80
Common alarm from Chiller
X (6)
#81
Chiller, no communication to Chiller
X (6)
#82
Cooling fan error
X (2) (6)
#83
Vi position error
X (2) (6)
#84
Lube press
X (2) (6)
Alarm
Warning
X (6) X (6) X (6)
X (6)
X (2) (6)
Note the following: (1):
Reciprocating Compressors only
(2):
Screw Compressors only
(3):
The alarm will function as a warning when the compressor is running, i.e. after prelubrication.
(4):
30
The alarm will only stop the compressor in mode remote/ multisab, in mode manual or auto the compressor will not be stopped, i.e. the alarm will function as a warning.
(5):
Alarm/warning #51 -- #54 only for PROSAB II.
(6):
Alarm/warning #55 -- #84 only for UNISAB II.
(7):
Not UNISAB R/RT/RTH/S.
(8):
Not PROSAB II
(9):
The alarm LOW OIL PUMP PRESSURE DURING OPERATION applies to SAB 80. The alarm is only activated at a discharge pressure level below 16 Bar.
0178-444--ENG
Chiller The following tables are valid for UNISAB Chiller only. Codes for read and write dommando are the same as for UNISAB II. The index= Chiller no. will make the difference between UNISAB II (1--14) and UNISAB Chiller (16--31).
Points to READ for Chiller: Parameter Name BRINE LINE PRESS IN BRINE LINE PRESS OUT COOLING WATER LINE PRESS IN COOLING WATER LINE PRESS OUT BRINE LINE TEMP IN BRINE LINE TEMP OUT COOLING WATER LINE TEMP IN COOLING WATER TEMP OUT SUCTION SUPERHEAT AT EVAPORATOR MODE STATE CAPACITY (of expansion valve) BRINE TEMP – SUCT PRESS . value BRINE TEMP – SUCT PRESS . actual sp “Hostdata_1 to _5 has changed” ALARM CODE (Word 0) ALARM CODE (Word 1) ALARM CODE (Word 2) WARNING CODE (Word 3) WARNING CODE (Word 4) WARNING CODE (Word 5)
UNISAB Point No 32 33 34 35 36 37 38 39 40 41 42 43 44 45 -70 71 72 73 74 75
BRINE TEMP – SUCT PRESS . setpoint 1 BRINE TEMP – SUCT PRESS . setpoint 2 BRINE TEMP – SUCT PRESS . neutral zone BRINE TEMP – SUCT PRESS . gain BRINE TEMP – SUCT PRESS . t sample BRINE TEMP – SUCT PRESS . t integrating BRINE TEMP – SUCT PRESS . t diff BRINE TEMP – SUCT PRESS . P part BRINE TEMP – SUCT PRESS . I part BRINE TEMP – SUCT PRESS . D part BRINE TEMP – SUCT PRESS . min pulse BRINE TEMP – SUCT PRESS .actuator time BRINE TEMP – SUCT PRESS . reg output SUCTION SUPERHEAT . value SUCTION SUPERHEAT . actual setpoint SUCTION SUPERHEAT . setpoint 1 SUCTION SUPERHEAT . setpoint 2 SUCTION SUPERHEAT . neutral zone SUCTION SUPERHEAT . gain
80 81 82 ----------85 86 87 88 89 90 91 ----------94 95 96 97 98 ---------------
0178-444--ENG
Decimals
Unit
I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I I I*0.1 I*0.1 I*0.1 I I I I I I I
BAR BAR BAR BAR _C _C _C _C _C
I*0.1 I*0.1 I*0.1 I0.01 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I0.01
_C _C _C
% _C _C
Sec Sec Sec % % % Sec Sec % _C _C _C _C _C
31
SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . SUCTION SUPERHEAT . No Valid Data No Valid Data No Valid Data No Valid Data Soft ware version
---------------------------------------------------------------------------------------------------127
I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I0.01
Sec Sec Sec % % % Sec Sec %
PUMPS PRE RUN COMPR START START PUMP DOWN PUMP DOWN BRINE PUMP POST RUN WATER PUMP POST RUN BRINE FLOW START NO BRINE FLOW WATER FLOW START NO WATER FLOW OIL RETURN PUMP PERIOD OIL RETURN PUMP PULSE BRINE PUMP 1 MOTOR START BRINE PUMP 2 MOTOR START WATER PUMP 1 MOTOR START WATER PUMP 2 MOTOR START OFFSET DELAY NO COMMUNICATION
130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147
I I I I I I I I I I I I I I I I I I
Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec
BAUD RATE NODE NUMBER PRESSURE UNIT COMPRESSOR NUMBER BRINE PUMP MODE WATER PUMP MODE P1+ P1-P2+ P2-P3+ P3-C+ C-C cap START PUMP DOWN OIL RETURN PUMPING FUNCTION TWO AKV VALVES
170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187
I I I I I I I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I I
% % % % % %
32
t sample t integrating t differentiating P part of output I part of output D part of output min pulse actuatortime regulator output
_C _C
0178-444--ENG
DOUBLE EVAPORATOR MANUAL STEP SIZE FACTORY RESET BRINE LINE PRESS IN High Alarm Limit BRINE LINE PRESS IN High Warning Limit BRINE LINE PRESS IN Low Warning Limit BRINE LINE PRESS IN Low Alarm Limit BRINE LINE PRESS OUT High Alarm Limit BRINE LINE PRESS OUT High Warning Limit BRINE LINE PRESS OUT Low Warning Limit BRINE LINE PRESS OUT Low Alarm Limit COOLING WATER LINE PRESS IN High Alarm Limit COOLING WATER LINE PRESS IN High Warning Limit COOLING WATER LINE PRESS IN Low Warning Limit COOLING WATER LINE PRESS IN Low Alarm Limit COOLING WATER LINE PRESS OUT High Alarm Limit COOLING WATER LINE PRESS OUT High Warning Limit COOLING WATER LINE PRESS OUT Low Warning Limit COOLING WATER LINE PRESS OUT Low Alarm Limit BRINE TEMP IN High Alarm Limit BRINE TEMP IN High Warning Limit BRINE TEMP IN Low Warning Limit BRINE TEMP IN Low Alarm Limit BRINE TEMP OUT High Alarm Limit BRINE TEMP OUT High Warning Limit BRINE TEMP OUT Low Warning Limit BRINE TEMP OUT Low Alarm Limit COOLING WATER TEMP IN High Alarm Limit COOLING WATER TEMP IN High Warning Limit COOLING WATER TEMP IN Low Warning Limit COOLING WATER TEMP IN Low Alarm Limit COOLING WATER TEMP OUT High Alarm Limit COOLING WATER TEMP OUT High Warning Limit COOLING WATER TEMP OUT Low Warning Limit COOLING WATER TEMP OUT Low Alarm Limit SUCT.SUPERHT. High Alarm Limit SUCT.SUPERHT. High Warning Limit SUCT.SUPERHT. Low Warning Limit SUCT.SUPERHT. Low Alarm Limit BRINE SUCTION DIFFERENCE High Alarm Limit BRINE SUCTION DIFFERENCE High Warning Limit BRINE SUCTION DIFFERENCE Low Warning Limit BRINE SUCTION DIFFERENCE Low Alarm Limit
188 189 190 200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239
I I*0.1 I I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1
DIGITAL INPUTS Please see digital input packing description DIGITAL OUTPUTS Please see digital output packing description DIGITAL OUTPUTS Please see digital output packing description
253 254 255
I I I
0178-444--ENG
0--1 BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C
33
MODE description Point No 41 0 = STOPPED 1 = MANUAL 2 = AUTO STATE description Point No 42 0 = STOPPED 1 = SHUTDOWN Alarm code 45 Alarm code 44 Alarm code 43 Alarm code 42 Alarm code 41 Alarm code 40 Alarm code 39 alarm code 38 alarm code 37 alarm code 36 alarm code 35 alarm code 34 alarm code 33 alarm code 32 alarm code 31 alarm code 30
2 = READY 3 = PUMP START 4 = START PUMP--DOWN 5 = RUNNING 6 = PUMP--DOWN 7 = PUMP POST RUN ALARM packing description WORD 0 – Point No 70:
COOLING WATER DIFF PRESS LOW COOLING WATER DIFF PRESS HIGH COOLING WATER TEMP OUTLET LOW COOLING WATER TEMP OUTLET HIGH COOLING WATER TEMP INLET LOW COOLING WATER TEMP INLET HIGH BRINE LINE PRESS OUT LOW BRINE LINE PRESS OUT HIGH BRINE LINE PRESS IN LOW BRINE LINE PRESS IN HIGH BRINE DIFF PRESS LOW BRINE DIFF PRESS HIGH BRINE TEMP OUT LOW BRINE TEMP OUT HIGH BRINE TEMP IN LOW BRINE TEMP IN HIGH
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 9 bit no 8 bit no 7 bit no 6 bit no 5 bit no 4 bit no 3 bit no 2 bit no 1 bit no 0
WORD 1 – Point No 71: No Valid Data No Valid Data No Valid Data No Valid Data alarm code 73 alarm code 72 alarm code 71 alarm code 70 alarm code 61 alarm code 60 alarm code 59 alarm code 58 alarm code 49 alarm code 48 alarm code 47 alarm code 46
34
No Valid Data No Valid Data No Valid Data No Valid Data SUCT.SUPERHT. LOW SUCT.SUPERHT. HIGH BRINE OUTLET TEMP – SUCT.PRESS LOW BRINE OUTLET TEMP – SUCT.PRESS HIGH SUCTION SUPERHEAT 2 LOW SUCTION SUPERHEAT 2 HIGH SUCTION SUPERHEAT LOW SUCTION SUPERHEAT HIGH COOLING WATER LINE PRESS OUTLET LOW COOLING WATER LINE PRESS OUTLET HIGH COOLING WATER LINE PRESS INLET LOW COOLING WATER LINE PRESS INLET HIGH
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 9 bit no 8 bit no 7 bit no 6 bit no 5 bit no 4 bit no 3 bit no 2 bit no 1 bit no 0
0178-444--ENG
WORD 2 – Point No 72: alarm code alarm code alarm code alarm code alarm code alarm code alarm code alarm code alarm code alarm code No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data
NO COMMUNICATION WITH UNISAB BRINE PUMP 1 MOTOR ALARM BRINE PUMP 2 MOTOR ALARM NO BRINE FLOW WATER PUMP 1 MOTOR ALARM WATER PUMP 2 MOTOR ALARM NO WATER FLOW BOTH BRINE PUMPS UNAVAILABLE BOTH WATER PUMPS UNAVAILABLE STARTING PUMP OUT TIMER EXPIRED No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 9 bit no 8 bit no 7 bit no 6 bit no 5 bit no 4 bit no 3 bit no 2 bit no 1 bit no 0
WARNING packing description WORD 3 – Point No 73: warning code 45 warning code 44 warning code 43 warning code 42 warning code 41 warning code 40 warning code 39 warning code 38 warning code 37 warning code 36 warning code 35 warning code 34 warning code 33 warning code 32 warning code 31 warning code 30
0178-444--ENG
COOLING WATER DIFF PRESS LOW COOLING WATER DIFF PRESS HIGH COOLING WATER TEMP OUTLET LOW COOLING WATER TEMP OUTLET HIGH COOLING WATER TEMP INLET LOW COOLING WATER TEMP INLET HIGH BRINE LINE PRESS OUT LOW BRINE LINE PRESS OUT HIGH BRINE LINE PRESS IN LOW BRINE LINE PRESS IN HIGH BRINE DIFF PRESS LOW BRINE DIFF PRESS HIGH BRINE TEMP OUT LOW BRINE TEMP OUT HIGH BRINE TEMP IN LOW BRINE TEMP IN HIGH
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 9 bit no 8 bit no 7 bit no 6 bit no 5 bit no 4 bit no 3 bit no 2 bit no 1 bit no 0
35
WORD 4 – Point No 74: No Valid Data No Valid Data No Valid Data No Valid Data warning code 73 warning code 72 warning code 71 warning code 70 warning code 61 warning code 60 warning code 59 warning code 58 warning code 49 warning code 48 warning code 47 warning code 46
No Valid Data No Valid Data No Valid Data No Valid Data SUCT.SUPERHT. LOW SUCT.SUPERHT. HIGH BRINE OUTLET TEMP – SUCT.PRESS LOW BRINE OUTLET TEMP – SUCT.PRESS HIGH SUCTION SUPERHEAT 2 LOW SUCTION SUPERHEAT 2 HIGH SUCTION SUPERHEAT LOW SUCTION SUPERHEAT HIGH COOLING WATER LINE PRESS OUTLET LOW COOLING WATER LINE PRESS OUTLET HIGH COOLING WATER LINE PRESS INLET LOW COOLING WATER LINE PRESS INLET HIGH
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 9 bit no 8 bit no 7 bit no 6 bit no 5 bit no 4 bit no 3 bit no 2 bit no 1 bit no 0
WORD 5 – Point No 75: No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data
36
No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data BRINE PUMP 1 NOT AVAILABLE BRINE PUMP 2 NOT AVAILABLE WATER PUMP 1 NOT AVAILABLE WATER PUMP 2 NOT AVAILABLE COMPR START TIMER EXPIRED
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 9 bit no 8 bit no 7 bit no 6 bit no 5 bit no 4 bit no 3 bit no 2 bit no 1 bit no 0
0178-444--ENG
Digital input packing description Point No 253 No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data Digital Input No 10 Digital Input No 09 Digital Input No 08 Digital Input No 07 Digital Input No 06 Digital Input No 05 Digital Input No 04 Digital Input No 03 Digital Input No 02 Digital Input No 01 Digital Input No 00
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 09 bit no 08 bit no 07 bit no 06 bit no 05 bit no 04 bit no 03 bit no 02 bit no 01 bit no 00
Digital Output packing description (INTEGER 02) Point No 255 No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data Digital Output No 17 Digital Output No 16
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 09 bit no 08 bit no 07 bit no 06 bit no 05 bit no 04 bit no 03 bit no 02 bit no 01 bit no 00
Digital Output packing description (INTEGER 01) Point No 254
Digital Output packing description (INTEGER 02) Point No 255
Digital Output No 15 Digital Output No 14 Digital Output No 13 Digital Output No 12 Digital Output No 11 Digital Output No 10 Digital Output No 09 Digital Output No 08 Digital Output No 07 Digital Output No 06 Digital Output No 05 Digital Output No 04 Digital Output No 03 Digital Output No 02 Digital Output No 01 Digital Output No 00
No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data No Valid Data Digital Output No 17 Digital Output No 16
0178-444--ENG
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 09 bit no 08 bit no 07 bit no 06 bit no 05 bit no 04 bit no 03 bit no 02 bit no 01 bit no 00
bit no 15 bit no 14 bit no 13 bit no 12 bit no 11 bit no 10 bit no 09 bit no 08 bit no 07 bit no 06 bit no 05 bit no 04 bit no 03 bit no 02 bit no 01 bit no 00
37
Points to WRITE for Chiller: Parameter Name
Decimals
Unit
BRINE TEMP -- SUCT PRESS . gain BRINE TEMP -- SUCT PRESS . t sample BRINE TEMP -- SUCT PRESS . t integrating BRINE TEMP -- SUCT PRESS . t diff SUCTION SUPERHEAT . setpoint 1 SUCTION SUPERHEAT . setpoint 2
COMSAB POINT NO 85 86 87 88 97 98
I0.01 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1
Sec Sec Sec _C _C
PUMPS PRE RUN COMPR SRART START PUMP DIWN PUMP DOWN BRINE PUMP POST RUN WATER PUMP POST RUN BRINE FLOW START NO BRAINE FLOW WATER FLOW START NO WATER FLOW OIL RETURN PUMP PERIOD OIL RETURN PUMP PULSE BRINE PUMP 1 MOTOR START BRINE PUMP 2 MOTOR START WATER PUMP 1 MOTOR START WATER PUMP 2 MOTOR START OFFSET DELAY NO COMMUNICATION
130 131 132 133 134 135 136 137 138 139 140 141 142 143 144 145 146 147
I I I I I I I I I I I I I I I I I I
Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec Sec
BAUD RATE NODE NUMBER PRESSURE UNIT COMPRESSOR NUMBER BRINE PUMP MODE WATER PUMP MODE P1+ P1-P2+ P2-P3+ P3-C+ C-C cap START PUMP DOWN OIL RETURN PUMPING FUNCTION TWO AKV VALVES DOUBLE EVAPORATOR MANUAL STEP SIZE FACTORY RESET
170 171 172 173 174 175 176 177 178 179 180 181 182 183 184 185 186 187 188 189 190
I I I I I I I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I I I I*0.1 I
38
% % % % % %
_C _C
0--1
0178-444--ENG
BRINE LINE PRESS IN High Alarm Limit BRINE LINE PRESS IN High Warning Limit BRINE LINE PRESS IN Low Warning Limit BRINE LINE PRESS IN Low Alarm Limit BRINE LINE PRESS OUT High Alarm Limit BRINE LINE PRESS OUT High Warning Limit BRINE LINE PRESS OUT Low Warning Limit BRINE LINE PRESS OUT Low Alarm Limit COOLING WATER LINE PRESS IN High Alarm Limit COOLING WATER LINE PRESS IN High Warning Limit COOLING WATER LINE PRESS IN Low Warning Limit COOLING WATER LINE PRESS IN Low Alarm Limit COOLING WATER LINE PRESS OUT High Alarm Limit COOLING WATER LINE PRESS OUT High Warning Limit COOLING WATER LINE PRESS OUT Low Warning Limit COOLING WATER LINE PRESS OUT Low Alarm Limit BRINE TEMP IN High Alarm Limit BRINE TEMP IN High Warning Limit BRINE TEMP IN Low Warning Limit BRINE TEMP IN Low Alarm Limit BRINE TEMP OUT High Alarm Limit BRINE TEMP OUT High Warning Limit BRINE TEMP OUT Low Warning Limit BRINE TEMP OUT Low Alarm Limit COOLING WATER TEMP IN High Alarm Limit COOLING WATER TEMP IN High Warning Limit COOLING WATER TEMP IN Low Warning Limit COOLING WATER TEMP IN Low Alarm Limit COOLING WATER TEMP OUT High Alarm Limit COOLING WATER TEMP OUT High Warning Limit COOLING WATER TEMP OUT Low Warning Limit COOLING WATER TEMP OUT Low Alarm Limit SUCT.SUPERHT. High Alarm Limit SUCT.SUPERHT. High Warning Limit SUCT.SUPERHT. Low Warning Limit SUCT.SUPERHT. Low Alarm Limit BRINE SUCTION DIFFERENCE High Alarm Limit BRINE SUCTION DIFFERENCE High Warning Limit BRINE SUCTION DIFFERENCE Low Warning Limit BRINE SUCTION DIFFERENCE Low Alarm Limit
0178-444--ENG
200 201 202 203 204 205 206 207 208 209 210 211 212 213 214 215 216 217 218 219 220 221 222 223 224 225 226 227 228 229 230 231 232 233 234 235 236 237 238 239
I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1 I*0.1
BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR BAR _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C _C
39
Table of alarms and warnings for UNISAB II Chiller: Id #1 #2 #3 #4 #5 #6 #7 #8 #9 # 10 # 11 # 12 # 13 # 14 # 15 # 16 # 17 # 18 # 19 # 20 # 21 # 22 # 23 # 24 # 25 # 26 # 27 # 28 # 29 # 30 # 31 # 32 # 33 # 34 # 35 # 36 # 37 # 38 # 39 # 40 # 41 # 42 # 43 # 44 # 45 # 46 # 47 # 48 # 49
40
Alarm / warning text No communication with UNISAB Brine pump 1 motor starter error Brine pump 2 motor starter error Brine flow error Water pump1 motor starter error Water pump2 motor starter error Water flow error Both brine pumps unavaliable Both water pumps unavaliable Starting pump down timer expired Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Not used Brine temp in high Brine temp in low Brine temp out high Brine temp out low Brine diff press high Brine diff press low Brine line press in high Brine line press in low Brine line press out high Brine line press out low Cooling water temp at inlet high Cooling water temp at inlet low Cooling water temp at outlet high Cooling water temp at outlet low Cooling water diff press high Cooling water diff press low Cooling water line press at inlet high Cooling water line press at inlet low Cooling water line press at outlet high Cooling water line press at outlet low
Alarm
Warning
X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X
0178-444--ENG
# 50 # 51 # 52 # 53 # 54 # 55 # 56 # 57 # 58 # 59 # 60 # 61 # 62 # 63 # 64 # 65 # 66 # 67 # 68 # 69 # 70 # 71
Suction temp low Suction temp low Suction temp2 high Suction temp2 low Suction press high (Temp. saturated) Suction press low (Temp. saturated) Suction press high Suction press low Suction superheat high Suction superheat low Suction superheat2 high Suction superheat2 low Disch temp high Disch temp low Disch press high (Temp. saturated) Disch press low (Temp. saturated) Disch press high Disch press low Disch superheat high Disch superheat low Brine outlet temp – suct.press high Brine outlet temp – suct.press low
0178-444--ENG
X X X X X X X X X X X X X X X X X X X X X X
X X X X X X X X X X X X X X X X X X X X X X
41
List of Versions Version 1.00 Error when reading motor current and hour counter from Unisab I and Prosab II. Limiting values for external input extended. Version 1.03 Error when reading SP1 and SP2 for brine temperature when ClimateControl has been chosen in Unisab II and when the brine temperature is being regulated. Version 1.04 No errors. Must be upgraded to include COP and chiller data. Version 1.05 We have corrected an error which made the Unisab II change start number to # 0 and at the same time change the control mode to auto. The change was automatically carried out by Unisab II, whenever the direct 4-20 mA capacity signal was connected or disconnected. Version 1.06 The Comsab II now recognizes a Unisab II configurated as a Rotatune controller. In earlier versions it was not possible to see any of the values in the Unisab II if the answer to the parameter Rotatune=(YES/NO) in the Unisab II menu was YES: Main picture > main menu > setup > config > Motor > Rotatune In spite of this problem, the Comsab II was still able to read the values from the other Unisab II in the system (with Rotatune=NO). In the manual the table of alarms/warnings for Unisab II has been updated to comply with the eprom version 2.03.1. Also the list of multisab states has been updated to comply with the eprom version 2.03.1.
42
0178-444--ENG
View more...
Comments