DS Agile System Presentation DS Agile Training Level 1 Global Systems Engineering 03/05/2012
GRID
SAM
GSE
Summary
1) What is a DCS?
Page 3
2) DS Agile Devices and Tools
Page 6
3) DS Agile Architectures
Page 10
4) DS Agile Station Bus
Page 17
5) DS Agile Key Concept and Synthesis
Page 23
L1-01-DS Agile System Presentation - Rev G - P 2
GSE
1.1) System Definition DCS System is a set of devices with specific functions that interact one to/with other with common rules BCU
To SCADA
GTW HMI
Fast Ethernet IEC61850
I/Os
IED
IED BCU
System is
BCU
CONFIGURATION & COMMUNICATION
SBUS TBUS
Station BUS (system federal network ...) Tele control BUS (Remote Control Point or SCADA)
LBUS
Legacy BUS (Field BUS to IED)
L1-01-DS Agile System Presentation - Rev G - P 3
GSE
1.2) Main System Functions
Supervision
Control from - Bay - Substation - SCADA
Maintenance
L1-01-DS Agile System Presentation - Rev G - P 4
HMI Station/Bay Flow Printing Sequence Of Event, Log in Archives with reports Alarms Manage/audible/viewer/printing State/Event viewer/printing Control Mode (local/remote : Bay, Substation) Exploitation Mode (run, stand-by, maintenance…) Uniqueness, InterLocK, automation running Force - Suppress - Substitute of DP Basic control sequence (DE, SBO) Built-in Control (ATCC, Synchrocheck, AutoRecloser) PSL, PLC Time management Databases management (download, switch, version) Test mode, SBMC Disturbance upload/viewing GSE
Summary
1) What is a DCS?
Page 3
2) DS Agile Devices and Tools
Page 6
3) DS Agile Architectures
Page 10
4) DS Agile Station Bus
Page 17
5) DS Agile Key Concept and Synthesis
Page 23
L1-01-DS Agile System Presentation - Rev G - P 5
GSE
2.1) DS Agile Devices Range
Visible DS Agile Operator Interface DS Agile System Management Tool MiCOM C264 Computer MiCOM Ethernet Switches DS Agile GTW (Gateway)
Hidden DS Agile Agency (Station BUS) DS Agile System Configuration Editor
Tools DS Agile Equipment Simulator
L1-01-DS Agile System Presentation - Rev G - P 6
GSE
2.2) DS Agile Devices MiCOM A300 : Gateways and Wide Area Control Units MiCOM C264/C264P: Bay Computer, RTU, Feeder Protection, Automatic Voltage Regulator MiCOM Hxxx: Manageable Ethernet Switch MiCOM Mxxx: Measurement & Disturbance Recorders
MiCOM Pxxx: Protection Relays Operator Interface NMU4 00
NXMU
L1-01-DS Agile System Presentation - Rev G - P 7
Process bus Equipments (Merging Units, Breakers IEDs) GSE
2.3) DS Agile Tools
SMT - DS Agile System Management Tool
SCE - DS Agile System Configuration Editor
ES - DS Agile Equipment Simulator CMT - DS Agile Computer Maintenance Tool (for C264)
L1-01-DS Agile System Presentation - Rev G - P 8
GSE
Summary
1) What is a DCS?
Page 3
2) DS Agile Devices and Tools
Page 6
3) DS Agile Architectures
Page 10
4) DS Agile Station Bus
Page 17
5) DS Agile Key Concept and Synthesis
Page 23
L1-01-DS Agile System Presentation - Rev G - P 9
GSE
3.1) MiCOM Computer Stand-Alone Example Up to 4 Serial Links (RS 485/232) for SCADA & IED interface C264C 2 x DIU200
1
2 3
4
IEC-60870-5-101
3xModbus RS485
11HKL
12HKL
Regional center
RS232
ION7330
ION7330
WAGO Vesuvius
13HKL
14HKL
ION7330
21HKL
ION7330
22HKL
WAGO
23HKL
ION7330
ION7330
Etna WAGO Ketelhuis
L1-01-DS Agile System Presentation - Rev G - P 10
GSE
3.2) Principle System Architecture IEC 61850
OI + EWS (MiCOM S1 , SMT) till 8 Clients
OI + EWS (MiCOM S1 SMT)
SCADA / Upper ring
Serial Link
OPC T104/103 Modbus 61850 DNP3
OI Server
OI Server
Fast Ethernet IEC 61850 Third party 61850 IED’s BCU
Alstom 61850 IED’s Third party IED’s L1-01-DS Agile System Presentation - Rev G - P 11
Redundancy
T104/103 Modbus DNP3… Legacy IED’s
GSE
3.3) Distributed Architecture Example Applications : HV Substations Distribution Stations Industry Railway Oil & Gas
DS Agile Hot Redundancy SOE printing Data reports
MiCOM C264 Redundancy Internal Synchrocheck Auto Recloser IED Management Advanced automation L1-01-DS Agile System Presentation - Rev G - P 12
DS Agile Gateway Serial SCADA communication Ethernet SCADA communication GSE
3.4) Process Bus Architecture Traditional
Full Digital
Grid Control Rooms SCS HMI
WAN
Grid Control Rooms
PDC
Remote tools/ Cyber Security
WAN SCS HMI
Proxy
Proxy
Switches IEC61850.8-1
BCUs
Prot.
Wired I/O
PDC
CM
Eng. tools
Switches
Station Bus
IEC61850.8-1
Station Bus
BCU
sPDC
PRP / HSR / 1588 sPDC
Prot.
SACU WACU
Wired VT&CT IEC61850.9-2
Process Bus HSR / 1588
FO
NMU Conventional VT&CT
Primary Devices L1-01-DS Agile System Presentation - Rev G - P 13
DMU/ CMU
AMU
NCiT
Primary Devices
GSE
3.5) Digital substation : Overview
L1-01-DS Agile System Presentation - Rev G - P 14
GSE
3.6) Digital substation WAN
inter-substation link
Inter-substation GOOSE switches
Router
Wide Area Control Units
P847
C264
P14D Agile
MS3000 CMU
Condition Monitoring field bus
Hardwired process bus
P645
C264
Cyber Security
SCADA Gateways
Station Bus PRP/HSR/IEEE1588
Red box Switches
to Grid Control room
C264
Digital process bus
P546
GPS/IEEE1588
Metering IEC61850
Digital process bus MU Agile DMU
MU Agile AMU
XMU820
MU Agile XMU MU Agile NXMU
Circuit Breakers w/mounted COSI-CT Circuit Breakers
Voltage Transformers
Current Transformers
L1-01-DS Agile System Presentation - Rev G - P 15
Circuit Breakers
Voltage Transformers
Current Transformers
COSI-CT
COSI-VT
GSE
Summary
1) What is a DCS?
Page 3
2) DS Agile Devices and Tools
Page 6
3) DS Agile Architectures
Page 10
4) DS Agile Station Bus
Page 17
5) DS Agile Key Concept and Synthesis
Page 23
L1-01-DS Agile System Presentation - Rev G - P 16
GSE
4.1) Station BUS : Definition
SBUS Station BUS (federate all system devices) Except DS Agile SCE for configuration
Use a Communication Agency Common Application Program. Interface
to all system device
L1-01-DS Agile System Presentation - Rev G - P 17
GSE
4.2) Station BUS : Overview Protocol: IEC61850
Client/Server Standard/Open N Clients M Servers Optimized traffic Fast Communication
L1-01-DS Agile System Presentation - Rev G - P 18
GSE
4.3) Station BUS : Client/Server Mechanism (1) Protocol: IEC61850 SERVER
Client/Server These are all my data
DS Agile OI Server
MiCOM C264
SBUS IED
CLIENT
I subscribe to these data I report the change of state of this data you subscribed
DS Agile Gateway MiCOM C264 (TBUS)
OPTIMIZED TRAFFIC L1-01-DS Agile System Presentation - Rev G - P 19
GSE
4.3) Station BUS : Client/Server Mechanism (2) Protocol: IEC61850
Client/Server
SERVER Send Reports (RP) Receive Controls Send Control Acknowledgements
CLIENT Receive Reports (RP) Send Controls Receive Control Acknowledgements
Send
GOOSE (fast message for shared automation)
L1-01-DS Agile System Presentation - Rev G - P 20
GSE
4.3) Unbuffered report and buffered report By default, the reports are Unbuffered Data are loosed in OI or GTW in case of network disconnection. Goal : Keep the report inside the C264 (till 100 reports) and send them after reconnection
Two clients can be selected separately to receive the buffered reports when the connection is back: an OI to display the corresponding events, and trigger alarms if the need arises a GTW to avoid a discrepancy between OI and SCADA
L1-01-DS Agile System Presentation - Rev G - P 21
GSE
Summary
1) What is a DCS?
Page 3
2) DS Agile Devices and Tools
Page 6
3) DS Agile Architectures
Page 10
4) DS Agile Station Bus
Page 17
5) DS Agile Key Concept and Synthesis
Page 23
L1-01-DS Agile System Presentation - Rev G - P 22
GSE
5.1) DS Agile Key Concept System is
Communication Configuration
DS Agile Devices
DS Agile OI, DS Agile SMT MiCOM C264, MiCOM Switches, DS Agile Gateway SBUS Agency, DS Agile SCE, DS Agile ES DS Agile Architectures Distributed Computer Stand alone RTU Networks
SBUS TBUS LBUS
L1-01-DS Agile System Presentation - Rev G - P 23
Station BUS Tele control BUS Legacy BUS
Client/Server protocol (61850) T101, T104, DNP3 ModBus, T103
GSE
Synthesis BAY INCOMER
DS Agile OI Server + Client
MiCOM C264
I/O IED
DS Agile Gateway
TBUS
SBUS LBUS
SCADA
BAY FEEDER 1
BAY FEEDER 2
L1-01-DS Agile System Presentation - Rev G - P 24
SITE / SUBSTATION
GSE
www.alstom.com
GRID
GSE
SAM