Application Note
Application-oriented testing of a distance teleprotection function end to end in the field using the corresponding RelaySimTest template Author Jens Baumeister |
[email protected] Date Feb 28, 2014 Related OMICRON Product CMC - RelaySimTest Application Area Distance teleprotection end to end testing Keywords RelaySimTest, application-oriented testing, distance teleprotection, end to end testing, GPS synchronization, PTP Version v1.1 Document ID ANS_14004_ENU
Abstract Due to the increasing complexity of our electrical power systems, the need for highly selective protection is increasingly being fulfilled by the use of distance teleprotection. To test a teleprotection function thoroughly, a distributed end to end test with synchronized injection can be utilized. This application note describes how this could be done in an easy and comfortable way using the corresponding OMICRON RelaySimTest test template. RelaySimTest offers simulation based system testing methods. To perform a test a fault scenario is calculated based on the simulation of the power system network. The resulting voltages and currents for the different relay locations can be used to test the correct behavior of the distance teleprotection system. For this reason RelaySimTest offers the possibility to control several distributed and time synchronized CMC test sets.
© OMICRON
Page 1 of 24
General information OMICRON electronics GmbH including all international branch offices is henceforth referred to as OMICRON. The product information, specifications, and technical data embodied in this application note represent the technical status at the time of writing and are subject to change without prior notice. We have done our best to ensure that the information given in this application note is useful, accurate and entirely reliable. However, OMICRON does not assume responsibility for any inaccuracies which may be present. OMICRON translates this application note from the source language English into a number of other languages. Any translation of this document is done for local requirements, and in the event of a dispute between the English and a nonEnglish version, the English version of this note shall govern. All rights including translation reserved. Reproduction of any kind, for example, photocopying, microfilming, optical character recognition and/or storage in electronic data processing systems, requires the explicit consent of OMICRON. Reprinting, wholly or in part, is not permitted. © OMICRON 2014. All rights reserved. This application note is a publication of OMICRON.
© OMICRON 2014
Page 2 of 24
Content 1
2
3
4
Safety instructions .......................................................................................................................... 4 1.1
Requirements to use this application note ................................................................................. 4
1.2
Safety instructions for this application note ................................................................................ 4
Introduction ..................................................................................................................................... 5 2.1
What this application note describes ......................................................................................... 5
2.2
Distance teleprotection ............................................................................................................. 5
System under test ........................................................................................................................... 7 3.1
Application example - protected line and time grading ............................................................... 7
3.2
Settings of the system under test menu in RelaySimTest .......................................................... 8
Test cases.......................................................................................................................................10 4.1
Application example – grid topology .........................................................................................10
4.2
Suitable test cases ...................................................................................................................11
4.3 5
6
4.2.1
Test case 1 – double infeed, fault on line .................................................................................... 12
4.2.2
Test case 2 and 3 – double infeed, line fault at 0 and 100%, RF and load current......................... 12
4.2.3
Test case 4 and 5 – single infeed, fault on line (weak infeed logic test) ........................................ 14
4.2.4
Test case 6 and 7 – single infeed, fault on busbar ....................................................................... 15
4.2.5
Test case 8 and 9 – double infeed, fault on busbar, RF and load current...................................... 15
4.2.6
Test case 10: time grading without teleprotection ........................................................................ 16
Measurement and assessment ................................................................................................16
Test sets configuration ..................................................................................................................18 5.1
Test setup................................................................................................................................18
5.2
The Test sets configurations in RelaySimTest and the Test Set Remote Agent ........................19
Performing the test ........................................................................................................................22 List of literature ..............................................................................................................................23
© OMICRON 2014
Page 3 of 24
1
Safety instructions
1.1
Requirements to use this application note This application note may only be used in combination with the relevant product manuals which contain all safety instructions. The user is fully responsibility for any application that makes use of OMICRON products. Instructions are always characterized by a symbol even if they are included to a safety instruction. DANGER Death or severe injury caused by high voltage or current if the respective protective measures are not complied. Carefully read and understand the content of this application note as well as the manuals of the involved systems before starting its practical application. Please contact OMICRON before you continue the process if you do not understand the safety instructions, operating instructions, or parts of it. Follow each instruction mentioned there especially the safety instructions since this is the only way to avoid danger that can occur when working at high voltage or high current systems. Furthermore, only use the involved equipment according to its intended purpose to guarantee a safe operation. Existing national safety standards for accident prevention and environmental protection may supplement the equipment’s manual.
Only experienced and competent professionals that are trained for working in high voltage or high current environments may perform this application note. Additional the following qualifications are required:
1.2
•
authorized to work in environments of energy generation, transmission or distribution and familiar with the approved operating practices in such environments.
•
familiar with the five safety rules.
•
good knowledge of the CMC test system.
Special safety instructions for the application note DANGER Death or severe injury caused by high voltage or current. Always turn off each system involved to the test process before wiring up or rewiring the equipment.
NOTICE Equipment damage or loss of data possible. Always turn off each system involved to the test process before wiring up or rewiring the equipment.
© OMICRON 2014
Page 4 of 24
2
Introduction
2.1
What this application note describes The application note describes the End to end relay tests of the RelaySimTest predefined Distance Teleprotection template. Therefore it covers the following content of the test template. 1. 2. 3. 4.
Distance teleprotection (general information) System under test Test cases Test sets configuration
The application note doesn’t describe a distance protection test itself. It doesn’t describe reach tests for the distance zones, single end tests, wiring checks and parameter tests. To test the protection thoroughly such tests are also recommended.
2.2
Distance teleprotection The zone grading of distance protection has the problem that zone 1 (Z1) does not protect the entire length of the line. This means that instantaneous tripping is only possible for around 80% to 90% of the line (see Figure 1).
Figure 1: Fault in zone 2
© OMICRON 2014
Page 5 of 24
If a fault occurs, communication between both sides of the protected line allows instantaneous tripping for the entire line. This scheme is generally referred to as "teleprotection".
Figure 2: Functional principle of teleprotection: Fault between the teleprotection system (left side); Fault behind substation B (right side)
Figure 2 describes the principle of teleprotection: > Left side: The fault is in zone 2 (Z2) for relay A and in Z1 for relay B. Relay B uses telecommunication to show relay A that the fault is between them. This allows relay A to trip instantaneously, it doesn’t has to delay the tripping with the time of Z2. > Right side: The fault is behind substation B. For relay A the fault is in Z2, for relay B it is in backwards direction. Therefore relay B doesn’t send a signal to relay A, that would allow relay A to trip instantaneously. Relay A trips with the delay time of Z2 There are different teleprotection schemes. Figure 2 describes a permissive underreach transfer tripping scheme (PUTT). Here a signal is only sent to the other end if a fault is detected in zone 1. It’s enough if only one relay detects a fault in its zone 1 to ensure that the fault is between side A and B. In this case the relays on both sides have to trip instantaneously. Zone 1 doesn’t cover the whole length of the line, this is why such a scheme is classed as “underreaching”.
Figure 3: Principle of PUTT
In contrast a permissive overreach transfer tripping scheme (POTT) uses typically an extended zone (Z1B). This zone extends Z1 to cover a length that is longer than the line length (overreaching). Relay A and B send a release signal to the other end if a fault is within the respective extended zone. That means if both relays send a signal the fault is between them (see Figure 4). In this case the relays on both sides have to trip instantaneously.
Figure 4: Principle of POTT
The example of this application note uses a POTT scheme. For more information about Distance protection see [2].
© OMICRON 2014
Page 6 of 24
3
System under test
3.1
Application example - protected line and time grading The following figure shows the line protected by distance teleprotection using a POTT scheme as described in chapter 2.2.
Line Data 50 Hz Solidly grounded 1 110 kV 600 A 32.5 km R‘ = 0.193 Ohm/km X‘ = 0.4 Ohm/km RN/R = 0.6 XN/X = 0.6
1
A Z1
130%
1
Z1B Z2
CT A 3 600 A / 1 A
70%
2
Z1B
1
Relay A
130%
Z1
70%
CT B 600 A / 1 A 3 1
1
4
B
Z2
VT A 110 kV / 100 V
VT B 110 kV / 100V
communication connection
Relay B
4 1
Figure 5: Example – Line protected by Distance Teleprotection using a POTT scheme (CT: Current Transformer; VT: Voltage Transformer)
Figure 5 shows that the extended zone (Z1B) reaches from 70% to 130% of the line length. A fault in the area of 0% to 100% of the line length should lead to an instantaneous trip of relay A and B. It is assumed that the relays of the example have an impedance tolerance of 5%. Figure 6 illustrates the time grading of the distance protection. Both relays have two distance zones for their forward and one zone for their reverse direction. The first zone has no delay which means the nominal trip time is 0 s. In the second zone the nominal trip time is 400 ms. The reverse zone has a delay time of 1.2 s.
© OMICRON 2014
Page 7 of 24
2
Z3
1.2 s
1
0.8 s
Z2
0.4 s
Z1
0s
Z1B
A
0s
Z1B
0.4 s
B
Z1
Z2
0.8 s 1.2 s
Z3
Figure 6: Example - Time Grading for Relay A and B (Blue: Relay A; Green: Relay B)
3.2
Settings of the system under test menu in RelaySimTest The parameter of the protected line, the protection concept and the substations with their bays and relays according to the example (see chapter 3.1 ) are in the System Under Test menu. The red numbers in Figure 8 correspond to the numbers of Figure 5 and Figure 6 to show where the different parameters are defined. Comments: > Number 1 → Protected line: The settings of this menu item use primary values. > Number 3 → Bay A and B: This menu item contains the sub menu Instrument transformers that includes the CT direction and the VT location settings.
Figure 7: Instrument transformers menu © OMICRON 2014
Page 8 of 24
> Number 4 → Relay A and B: This menu item contains the test voltage and current limits. The RelaySimTest template that corresponds to the application note was tested with a Siemens 7SA63 relay system. The relay manual specifies that a current of 150 A for up to 10 s and a continuous voltage of 230V do not cause damage to the relay [4]. The tests with the example data lead to currents that are smaller than 15 A and to voltages smaller 200V (Phase to Phase). The fault duration of one test point is about 2 s. Therefore a current limit of 15 A and a voltage limit of 200V is suitable. Nevertheless it is important to do breaks between the tests to ensure that the relays are not stressed too much.
1 1
2 1
3 1
4 1
Figure 8: System Under Test Menu
© OMICRON 2014
Page 9 of 24
4
Test cases Figure 9 shows the Test cases menu. It contains the tests with their corresponding grid topology (1), test scenarios (2) and test steps (3). The next three chapter describe these menus referring to the test template of the application note.
1
2
3
1
1
1
Figure 9: Test cases Menu
4.1
Application example – grid topology The line protected by distance teleprotection is part of the grid that is shown in Figure 10.
Figure 10: Grid Topology
© OMICRON 2014
Page 10 of 24
4.2
Suitable test cases This chapter describes the test of the corresponding RelaySimTest template. To keep the template simple, it uses only the following Fault types: > L1-N > L2-L3 > L1-L2-L3 All test cases with faults include these fault types. Depending on the relays under test, on the relay’s parameter and on the grid where the protection system is used, it can be necessary to add more fault types. The Initial state of a fault is inactive to get transients in the beginning. To get particularly high currents the fault inception angle is set to 0°.
Figure 11: Example for a fault with Initial state "Inactive"
The nominal trip time of the protection is between 0 and 1.2 s, therefore the simulation time after a fault or switching event is at least 2 s. Hence the protection system has enough time to show its reaction on the event. Sometimes the distance protection relays use the voltage of their voltage memory, if the voltage during a fault is too small to use it. Therefore it is necessary to fill this memory before the fault occurs. How long this takes depends on the relay type. A Siemens 7SA63 relay system was used to test the template. Such a relay for example needs about 2 seconds to fill its voltage memory. Hence a prefault duration of 2 s is used. Some of the test cases use a certain fault resistance RF to find out if the protection system can handle it. In all test cases where the influence of RF is not considered RF is set to 0 . The following chapters describe the different test cases of the template in detail. In all test cases the trip command of relay A and the trip command of relay B is observed. Chapter 4.3 describes how to measure and to assess the trip times.
© OMICRON 2014
Page 11 of 24
Test case 1 – double infeed, fault on line This test case should show that a fault on the protected line leads to an instantaneous trip of the teleprotection system. The fault is placed on different fault locations. > Fault locations: 0%, 50%, 100% of the protected line.
Figure 12: Test case 1
→ The fault is on the protected line, hence the relays have to detect it in zone 1 (Z1) or in the extended zone Z1B. In both cases they have to send a signal immediately to the other site which releases the extended zone of the remote relay. If a relay detects a fault in Z1, it has to trip instantaneously. If it detects a fault in Z1B it has to trip instantaneously when it receives the release signal from the other end. Test case 2 and 3 – double infeed, line fault at 0 and 100%, RF and load current These test cases should show that a fault on the protected line leads to an instantaneous trip of the teleprotection system even under unfavorable conditions. > A fault resistance of 3 is used. It influences the fault loop impedance measured by the relays. (Number [2] of the bibliography shows how to estimate a fault resistance). Figure 13 illustrates such an effect, if there would be only a single infeed at the relays site and no infeed at the remote line end. Furthermore the influence of a load current is neglected.
© OMICRON 2014
Page 12 of 24
X
RF
ZL
ZM
R Figure 13: Influence of a fault resistance (ZL: Line impedance; RF: Fault impedance; ZM: Measured Loop Impedance)
> The influence of the fault resistance increases, if there is a load current and if there is an infeed at the remote end. Depending on the power direction the measured reactance increases or decreases.
X
ZF
ZL
ZM
R Figure 14: Influence of a fault resistance with an infeed at the remote end and a load current (ZL: Line impedance; ZF: Impedance due to the fault resistance; ZM: Measured loop impedance)
> To realize the load current the phase angle of infeed 2 is varied, while the phase angle of infeed 1 stays at 0°. For the tests phase angles of -30°, 0° and +30° are used for infeed 2. +-30° leads in the grid of the example to a load current of about 510 A, this current is assumed as maximum load current. 0° leads to a no load condition. > For test case 2 the fault location is at the beginning of the line (0%) and for test case 3 at the end of the line (100%). Especially these two locations can cause trouble, because they are at the borders of the teleprotected area.
© OMICRON 2014
Page 13 of 24
→ Even if there are unfavorable conditions the fault is inside the area that is protected by the teleprotection system, therefore the relays have to behave in the same way they have to behave in test case 1. Test case 4 and 5 – single infeed, fault on line (weak infeed logic test) These test cases should show that faults on the teleprotected line lead to an instantaneous relay trip even if the remote relay does not detect the fault. The reason why the remote end does not pick up could be a weak infeed. Figure 15 illustrates a weak infeed at site B. The relay on site A detects the fault in Z1B and sends a signal to relay B. On site B the fault current is insufficient to cause a trigger of relay B. Hence relay B would not send a release signal and relay A would trip with zone 2. Relay B on the other hand would not trip at all. If a logic for weak infeed signals is used and relay B receives a signal while it has not detected the fault, this logic checks whether the voltage is below a specific value. If this is the case, Relay B trips and sends an echo to relay A to release its extended zone. With test cases 4 and 5 this logic is tested.
Figure 15: Weak infeed at site B
> The fault is placed at different fault locations: 0%, 50% and 100% of the line > In test case 4 only Infeed 1 is modeled.
Figure 16: Test case 4
→ There is no infeed at the site of relay B, therefore it will not detected the fault. Nevertheless the faults on the line have to lead to an instantaneous trip command of relay A and B due to the weak infeed logic. > In test case 5 only infeed 2 is modeled. → There is no infeed at the site of relay A, therefore it will not detected the fault. Nevertheless the faults on the line have to lead to an instantaneous trip command of relay A and B due to the weak infeed logic. © OMICRON 2014
Page 14 of 24
Test case 6 and 7 – single infeed, fault on busbar A fault on the busbar is out of the teleprotected area. These test cases should show that in such a case Z1B is not released and that the trip times of the relays fit to the time grading of their distance protection. > In test case 6 only infeed 1 is modeled > The fault is placed on busbar B
Figure 17: Test case 6
→ The fault is out of the teleprotected area. Relay A has to trip with Z2. Relay B has to trip with its reverse tripping zone (Z3). > In test case 7 only infeed 2 is modeled > The fault is placed on busbar A → The fault is out of the teleprotected area. Relay B has to trip with Z2. Relay A has to trip with its reverse tripping zone (Z3). Test case 8 and 9 – double infeed, fault on busbar, RF and load current This test cases are similar to test case 6 and 7 but with unfavorable conditions. As shown in chapter 4.2.2 a fault resistance as well as a load current and a remote infeed can cause trouble for the distance teleprotection. These test cases should show that the relays can deal with this influences if a fault occurs on the busbar. > A fault resistance of 3 Ohm is used. > The phase angle of infeed 2 is varied: -30°, 0°, +30° are used as phase angle of infeed 2, while the phase angle of infeed 1 stays at 0°. > For test case 8 the fault is placed at busbar A → The fault is out of the teleprotected area. Relay B has to trip with Z2. Relay A has to trip with its reverse tripping zone (Z3).
Figure 18: Test case 8
> For test case 9 the fault is placed at busbar B
© OMICRON 2014
Page 15 of 24
→ The fault is out of the teleprotected area. Relay A has to trip with Z2. Relay B has to trip with its reverse tripping zone (Z3).
Test case 10: time grading without teleprotection For this test case the teleprotection function has to be disabled. After the test it is very important to enable the teleprotection function again. This test case should show that the relays use the distance time grading if the teleprotection is disabled. > The zone borders between Z1 and Z2 are at 30% of the line for relay B and at 70% of the line for relay A > The zone tolerance is assumed to be 5% > The fault is located around the zone borders but not inside the tolerance band > Fault locations: 24%, 36%, 64%, 76%
Figure 19: Test Case 10
→ According to the time grading of the distance protection the relays have to show the following trip times:
Fault Location
4.3
24%
36%
64%
76%
Trip Time Relay A
0s
0s
0s
400 ms
Trip Time Relay B
400 ms
0s
0s
0s
Measurement and assessment The Define Measurements menu of the Test steps tab (see Figure 9 number 3) defines the start and stop event for the trip time measurements. > The “start measuring event” is the beginning of a fault. > The trip command is observed. The moment when the trip signal becomes active is the “stop measuring event”. > The trip time is measured for relay A and B.
© OMICRON 2014
Page 16 of 24
Figure 20: Measurement
The Set Assessment Condition menu (next to the Define Measurements menu) defines the assessment of the test steps. For all test cases (except test case 10) where the fault’s location is on the protected line the “Automatically obtain min/max time grading set in System under Test” option is active to use the time assessment of the menu Protection concept (see Figure 8 number 2). For all the other test cases the min and max trip time values are entered manually. To do so the option “Custom min/max values” can be used (see Figure 21).
Figure 21: Automatically obtain min/max
© OMICRON 2014
Page 17 of 24
5
Test sets configuration
5.1
Test setup Due to the distribution of the protection system an end to end test of a distance teleprotection system with two ends requires two CMCs. RelaySimTest offers the possibility to control both CMCs with one main application via Internet. For this reason two computers with Internet access are necessary – one at the local and one at the remote end. The local PC runs the RelaySimTest main application, the remote PC just a proxy application which takes care of network connection issues and announces the test device to the controlling software application at the other end. This proxy application is the OMICRON Test Set Remote Agent. How to configure RelaySimTest and the Test Set Remote Agent for such an application is described in the next chapter. Figure 22 illustrates the end to end test setup. To perform a test the main application of RelaySimTest on the local PC calculates a fault scenario based on the simulation of the power system network. It calculates the voltages and currents not only for its own end but also for the remote end. The results are used for the end to end test where the main application controls the local and the remote CMC. To perform an end to end test for a distance teleprotection system synchronized injection of test voltages and currents is necessary. The synchronization ensures that both test sets – the local and the remote one – start the test at the same time. This is very important since any inaccuracy can result in an unwanted test impedance and thus in an unexpected relay behavior. For this reason RelaySimTest supports the use of CMGPS 588 an antenna-integrated GPS controlled time reference to synchronize the starting point of a CMC test process. Each end needs its own CMGPS 588 (see Figure 22). It delivers a time signal using PTP (Precision Time Protocol). For more information about PTP see [3].
Figure 22: Scheme of an end to end test
© OMICRON 2014
Page 18 of 24
5.2
The Test sets configurations in RelaySimTest and the Test Set Remote Agent This chapter assumes that the test set up according to chapter 5.1 is already done: > > > > >
The local PC is running RelaySimTest, the remote PC the Test Set Remote Agent. Both have Internet access. The wiring between the CMCs and the relays is already done. The local and the remote CMC are already switched on and synchronized via CMGPS 588. If the connections between the CMCs and the PCs are done by Ethernet, it has to be ensured that both CMCs are associated to the local PC.
The Test sets configurations menu (local PC) defines the CMCs and their configuration used for the tests. At first the test template includes two general CMCs as shown in Figure 23. The label on the left site of the CMC icon shows that the first CMC belongs to substation A and the second one to substation B.
Figure 23: Test sets configuration menu of RelaySimTest (local PC)
After a click on the “Choose test set” button on the right site of the CMC icon, a new window opens and offers the CMC that is connected to the local PC. A click on the local CMC selects it.
Figure 24: Local CMC is selected
The Test Set Remote Agent on the remote PC (see Figure 25) has to open an Internet session before RelaySimTest can control the remote CMC. The upper part of the Test Set Remote Agent shows the remote CMC. If the correct CMC is not already selected, it has to be chosen by using the “Change test set” button.
© OMICRON 2014
Page 19 of 24
A click on “Grant remote access” announces the remote CMC on an Internet server. After a short time the Test Set Remote Agent displays a session ID for the Internet session. The software offers also the possibility to use a session password, but this is optional.
Figure 25: Test set remote agent (remote PC)
A click on “Connect to Remote Test Set” in the Test sets configurations menu of RelaySimTest (local PC) opens a window to enter the session ID from the remote end (see Figure 26).
Figure 26: Connect to remote test set (local PC) © OMICRON 2014
Page 20 of 24
Afterwards RelaySimTest displays both CMCs – the local and the remote one. Figure 27 illustrates this. The test sets are ready for time synchronized injection due to the use of CMGPS 588. The green clock icon next to the CMC icons indicate that.
Figure 27: Local and remote CMC connected to RelaySimTest
The Getting Started manual of RelaySimTest [1] describes how the wiring between the CMCs and the relays can be configured in the Test sets configurations menu. To perform the tests of this application note the following signals have to be configured for each CMC: > three test voltages > three test currents > the start, trip, send and receive signals of the relay
© OMICRON 2014
Page 21 of 24
6
Performing the test Before a test is started it is strongly recommended to do a wiring check. DANGER Death or severe injury caused by high voltage or current. Always turn off each system involved to the test process before wiring up or rewiring the equipment.
NOTICE Equipment damage or loss of data possible. Always turn off each system involved to the test process before wiring up or rewiring the equipment.
The execute buttons start the tests. There are different execute buttons - “Execute all” and “Execute selected”. What they mean depends on the menu where they are: > If a test case is open a click on the “Execute selected” button executes only the selected test step. A click on the “Execute all” button runs all test steps of the test case sequentially (see Figure 28). > In contrast to this in the Test Manager menu the “Execute selected” button runs all selected test cases, while “Execute all” runs all test cases (see Figure 29). Especially after tests with high currents it is meaningful to interrupt the test sequence with the Stop button. This ensures breaks between the tests to avoid too much stress for the relays.
Figure 28: “Execute selected” and “Execute all” button for a certain test case.
© OMICRON 2014
Page 22 of 24
Figure 29: “Execute selected” and “Execute all” button in the test manager menu.
List of literature [1] Getting Started with RelaySimTest; OMICRON electronics GmbH; 2014 [2] “Numerical Distance Protection: Principles and Applications”; 4th edition; Gerhard Ziegler; PUBLICIS; 2011 [3] “Implementation and Transition Concepts for IEEE 1588 Precision Timing in IEC 61850 Substation Environments”; B. Baumgartner, C. Riesch, M. Rudigier; OMICRON electronics GmbH [4] “SIPROTEC Distance Protection 7SA6 V4.70 Manual”, SIEMENS
© OMICRON 2014
Page 23 of 24
Support When you are working with our products we want to provide you with the greatest possible benefits. If you need any support, we are here to assist you.
24/7 Technical Support – Get Support www.omicron.at/support www.omicronusa.com/support Offering our customers outstanding support is one of our top priorities. At our technical support hotline, you can reach well-educated technicians for all of your questions. Around the clock – competent and free of charge. Make use of our 24/7 international technical support hotline: Europe/Middle East/Africa +43 59495 4444
Americas +1 713 830-4660 +1 800-OMICRON
Asia-Pacific +852 3767 5500
Additionally, you can find our Service Center or Sales Partner closest to you at www.omicron.at or www.omicronusa.com
Customer Area – Stay Informed www.omicron.at/customer www.omicronusa.com/customer The customer area on our website is an international knowledge exchange platform. Download the latest software updates for all products and share your own experiences in our user forum. Browse through the knowledge library and find application notes, conference papers, articles about daily working experiences, user manuals and much more.
OMICRON Academy – Learn More www.omicron.at/academy www.omicronusa.com/academy Learn more about your product in one of the training courses offered by the OMICRON Academy.