5.2 Directional Earth-Fault current test by secondary current/voltage injection: Polarizing Voltage(s)
Current injected
Injected (V)
Angle
Phase(s)
Amps
U0=63V
00
I0(Residual)
5
Angle Boundaries of operating area (Current shifted ref. Vp)
Note: Values of injected quantities exceeded threshold values of I>, I0> and Vp 5.3 Sensitivity and timing test by secondary current injection: 5.3.1 Over current and Earth fault: See attached Report 5.3.2 Sensitivity test to Polarizing Voltage: Min. Polarizing Voltage:
L12=
V
L13=
V
L23=
V
7.4 Other Tests and Checks Circuit breaker tripping and signaling: …………………………………………………………….…….
On load tests and checks performed: …………………………………………………………….…………….
Test Equipment: Observation of testing engineer:
Site tests results within factory assigned and PTR values TESTS PASSED SATISFACTORY.