Novec Flow Calc Manual Rev A

May 3, 2017 | Author: Jubert Raymundo | Category: N/A
Share Embed Donate


Short Description

Download Novec Flow Calc Manual Rev A...

Description

NOVEC MENU

DESIGN & FLOW CALCULATION MANUAL FOR

ENGINEERED FIRE SUPPRESSION SYSTEMS Designed for use with

3M™ NOVEC™ 1230 FIRE PROTECTION FLUID For use with Chemetron Flow Calculation Program CHEM-1230, Version 1.0.2

Issued July 1, 2004 Revision A October 5, 2004 Manual Stock Number 30000066

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Contents

1

LIST OF ILLUSTRATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LIST OF TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . REVISION PAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . FOREWORD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . GENERAL COMMENTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

ii iii iv v vi

ENGINEERED SYSTEM DESIGN

1

1.1 1.2 1.3 1.4

2

Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Agent Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 The Piping System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 The Discharge Nozzle . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

FLOW CALCULATIONS 2.1 2.2 2.3 2.4 2.5

9

Design Criteria . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Design Philosophy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13 Nozzle and Piping Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Hydraulic Flow Calculation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Two-Phase Hydraulics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

APPENDIX Example 1 Example 2 Example 3 Example 4 Example 5 Example 6

ISSUED:

7/1/2004

REV. A

51 ............................................................. ............................................................. ............................................................. ............................................................. ............................................................. .............................................................

REVISED:

10/5/2004

52 60 68 76 84 92

S/N 30000066 Page i

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

LIST OF ILLUSTRATIONS FIGURE NUMBER

DESCRIPTION OF ILLUSTRATION

PAGE NO.

1.2.4.1A

Graph: Novec 1230 Fluid - Calculated Cylinder Pressure vs. Percent of Agent Supply Discharged . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.2.4.1B

Graph: Novec 1230 Fluid Discharge Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

1.4.1

Graph: Novec 1230 Fluid Density Specific Nozzle Flow Rates . . . . . . . . . . . . . . . . . . . . . . 7

1.4.2

Graph: Chemetron 8 Port Nozzle Efficiencies . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

1.4.5

Graph: Cylinder Pressure Recession . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

2.1.1.5A

Orientation of Tees . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.1.1.5B

Minimum Distance From Elbow to Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.3A

Plan View - Above Floor System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.3B

Plan View - Underfloor System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

2.4.1

Flow Calc Program Screen View - System Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

2.4.1.1.A

Flow Calc Program Screen View - Project Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.4.1.1.B

Flow Calc Program Screen View - Revision Version . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.4.1.1.C

Flow Calc Program Screen View - Cylinder Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.4.1.1.E2

Flow Calc Program Screen View - Configuration Variables - Altitude . . . . . . . . . . . . . . . . . 21

2.4.1.2

Flow Calc Program Screen View - Hazard Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

2.4.1.2.A2

Flow Calc Program Screen View - Class B fuels list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

2.4.1.3

Flow Calc Program Screen View - Piping Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

2.4.1.3.A3

Flow Calc Program Screen View - Nozzle Reference Box . . . . . . . . . . . . . . . . . . . . . . . . . 24

2.4.1.3.A7

Flow Calc Program Screen View - Piping Data - Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

2.4.1.3.A8

Flow Calc Program Screen View - Piping Data - Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

2.4.1.3.A9

Flow Calc Program Screen View - Piping Data - Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . 28

2.4.1.3.C

Flow Calc Program Screen View - Piping Data - Fixed Pounds & Orifices . . . . . . . . . . . . . 30

2.4.1.4.A

Flow Calc Program Screen View - Calculation Results . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

2.4.1.4.B

Flow Calc Program Screen View - Nozzle Performance . . . . . . . . . . . . . . . . . . . . . . . . . . 33

2.4.1.4.C

Flow Calc Program Screen View - Hazard Concentration Results . . . . . . . . . . . . . . . . . . . 38

2.4.1.4.D

Flow Calc Program Screen View - Error Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

2.4.1.5

Flow Calc Program Screen View - Print Data and Results or Print Output Results . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

2.4.1.5.C

Flow Calc Program Screen View - Configure Printer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

2.4.3.1

Flow Calc Program Screen View - Load Data File . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

2.4.5

Flow Calc Program Screen View - Volume/Weight/Concentration Calculator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page ii

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

LIST OF TABLES TABLE NUMBER

DESCRIPTION

PAGE NO.

2.1.1.4

Pipe Size vs. Flow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

2.4.1.1.C

Cylinder Capacity Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.4.1.3A8

Pipe Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Fitting Equivalent Length Chart . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28 Cylinder/Check Valve Equivalent Length Table . . . . . . . . . . . . . . . . . . . . . . . . . . 29 3/8" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . 34 1/2" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . 34 3/4" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . 35 1" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . . 35 1-1/4" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . 36 1-1/2" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . 36 2" 8-Port Styles F & G Nozzle Drill Nos/Diameter Chart . . . . . . . . . . . . . . . . . . . 37

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page iii

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

REVISION SHEET Date of issue for original and revised pages is: Original . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . July 1, 2004 Revision A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . October 5, 2004 Section Number

Page Numbers

Revision Date

Title Page (blank) . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . i . . . . . . . . . . . . . . . . . . October 5, 2004 List of Illustrations . . . . . . . . . . . . . . . . . . . . . . . . . . ii . . . . . . . . . . . . . . . . . . October 5, 2004 List of Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . iii . . . . . . . . . . . . . . . . . . October 5, 2004 Foreword . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . v . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 General Comments . . . . . . . . . . . . . . . . . . . . . . . . vi . . . . . . . . . . . . . . . . . . October 5, 2004 Section 1.0 - 1.4.7 . . . . . . . . . . . . . . . . . . . . . . . . 1 - 8 . . . . . . . . . . . . . . . . . October 5, 2004 Section 2.0 - 2.5.1.4 . . . . . . . . . . . . . . . . . . . . . . . 9 - 50 . . . . . . . . . . . . . . . . October 5, 2004 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0 Appendix - Example #1 . . . . . . . . . . . . . . . . . . . 52 - 59 . . . . . . . . . . . . . . . . October 5, 2004 Appendix - Example #2 . . . . . . . . . . . . . . . . . . . 60 - 67 . . . . . . . . . . . . . . . . October 5, 2004 Appendix - Example #3 . . . . . . . . . . . . . . . . . . . 68 - 75 . . . . . . . . . . . . . . . . October 5, 2004 Appendix - Example #4 . . . . . . . . . . . . . . . . . . . 76 - 83 . . . . . . . . . . . . . . . . October 5, 2004 Appendix - Example #5 . . . . . . . . . . . . . . . . . . . 84 - 91 . . . . . . . . . . . . . . . . October 5, 2004 Appendix - Example #6 . . . . . . . . . . . . . . . . . . . 92 - 99 . . . . . . . . . . . . . . . . October 5, 2004

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page iv

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Foreword Chemetron Fire Systems reserves the right to revise and improve its products as it deems necessary without notification. This publication is intended to describe the state of this product at the time of its publication, and may not reflect the product at all times in the future. The software screen prints depicted in this manual are presented for reference and example purposes only and may not reflect the most current version of the Novec 1230 Fluid Flow Calculation software (CHEM-1230.exe and support files). This technical manual provides the necessary information for designing and performing flow calculations for a Chemetron Engineered System with Novec 1230 fluid. This is a single volume technical manual arranged in 2 sections, followed by an Appendix. This publication, or parts thereof, may not be reproduced in any form, by any method, for any purpose, without the express written consent of Chemetron Fire Systems. Any questions concerning the information presented in this manual should be addressed to the Matteson Office. Copyright © 2004 Chemetron Fire Systems. All Rights Reserved. Chemetron Fire Systems™ and Cardox® are registered trademarks of Chemetron Fire Systems. 3M and Novec are trademarks of 3M Company.

A World of Protection

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

4801 Southwick Drive, 3rd Floor Matteson, IL 60443 Phone 708/748-1503 • Fax 708/748-2847 Customer Service Fax 708/748-2908

S/N 30000066 Page v

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

General Comments Factory Mutual Research Corporation does not accept metric unit calculations. They will not be approved for Factory Mutual installations. UL, ULC & FMRC require multiple tiers of nozzles for heights above 16' 0" (4.88 M). The calculation method used by Chemetron Fire Systems has been investigated using A-53, Schedule 40 pipe and 300 lb malleable iron fittings for test installations. When specified limitations noted in this manual and in the Chemetron software are not maintained, there is the risk that the system will not supply the required amount of extinguishing agent. For installation, design, operation and maintenance of Chemetron Fire Systems Fire Suppression Systems designed for use with Novec 1230 fluid, please refer to the Beta, Gamma, & Sigma Series Engineered Systems Design, Installation, Operation and Maintenance Manual, Part Number 30000058. For installation, design, operation and service of Chemetron Fire Systems Marine Fire Suppression Systems designed for use with Novec 1230 fluid, please refer to the Fire Protection System for Marine Service with Novec 1230 Fire Protection Fluid Design, Installation, Operation and Service Manual, Part Number 30000067.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page vi

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1

ENGINEERED SYSTEM DESIGN

1.1

Introduction

1.1.1

Decomposition An adverse characteristic of Novec 1230 fluid is that it will decompose into toxic and corrosive byproducts if exposed to fire or to objects heated above 1,300oF (704oC). Such decomposition is kept at a negligible level by rapidly discharging the agent so as to extinguish the flames promptly. This minimizes the quantity of agent that passes through a flame front at concentrations too low for flame extinguishment. The problem of Novec 1230 fluid decomposition has led to a requirement in NFPA 2001 that discharge of 95 percent of the agent mass needed to achieve minimum design concentration be discharged within 10 seconds. This 10 second discharge time requirement is very important in hazards where flammable liquids are likely to be the fuel.

1.1.2

Design Difficulties The requirement for a rapid discharge makes it more difficult to adequately mix or distribute Novec 1230 fluid in the hazard area, but proper nozzle and orifice design can overcome this problem. The two-phase nature of the Novec 1230 fluid as it flows through pipes and orifices complicates the design of agent distribution piping networks. The use of a computer program overcomes this difficulty. The “two-phase” compressible nature of agent flow also demands that piping installations are done in rigorous conformance to the system design parameters. Such things as pipe that is rougher than the norm or the addition of unanticipated changes in pipe direction can introduce performance problems - especially if the system is “unbalanced” and intended to simultaneously flood separate compartments. Simple piping layouts help overcome this difficulty.

1.1.3

Flow Calculation Pipe and nozzles for Chemetron systems with Novec 1230 fluid are sized using a computer program. The program is based on recognized hydraulic theory and the results of the program have been verified in rigorous laboratory tests. Calculations made with this program have been checked by FMRC, UL, and ULC to assure accuracy and determine the limitations beyond which it is not practicable to predict results accurately. The calculations are based on an ambient cylinder temperature of 70oF ±10oF (21.1oC ±5.5oC). Therefore, the cylinder shall be located in a climate controlled environment to ensure a temperature consistently within this range. Calculations performed on systems where the cylinders are not maintained within this range may not be accurate and the designed quantities of agent may not be discharged from one or more discharge nozzles.

1.1.4

System Check While the basic computer program used for calculating pipe and orifice sizes cannot be checked by manual means, there is a definite need to check the input information upon which the calculation is based. Since there may be inadvertent or necessary changes due to on-site job conditions, it is also essential to check the system as calculated against the system as installed. All of this does not preclude the desirability of an actual discharge test on the installed system to check for unanticipated circumstances that might influence overall system performance.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 1

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1.2

Agent Characteristics

1.2.1

Pressure vs. Temperature For optimum pipeline flow characteristics over the entire range of possible ambient temperatures, it is necessary to superpressurize the agent with another gas such as nitrogen. At the present time, one pressurization level is permitted: 360 psig measured at 70oF (25.8 bar at 21.1oC).

1.2.2

Nitrogen Superpressure When a storage container is pressurized with nitrogen, some of the nitrogen goes into solution in the liquid phase. The volume of the liquid phase increases slightly because of the addition of nitrogen, which behaves as though it were liquefied. The remainder of the nitrogen remains in the vapor phase where it combines with the partial pressure of Novec 1230 fluid vapor to produce the desired level of pressurization when the system is in equilibrium at 70oF (21.1oC). If the ambient temperature rises, the pressure will increase and the volume of the liquid portion will also increase.

1.2.3

System Discharge The delivery of Novec 1230 fluid into the hazard area is accomplished by means of a piping network that terminates in one or more specially designed discharge nozzles. In order to best study the discharge of Novec 1230 fluid from the storage cylinder to the hazard area, it is desirable to consider the delivery system in three parts: the storage container, the piping system, and the discharge nozzle.

1.2.4

The Storage Cylinder When the storage cylinder is open to the pipeline, pressure in the cylinder will force liquid from the bottom of the cylinder into the piping network. As the liquid is discharged, the pressure in the cylinder will drop and the volume of the vapor phase will increase. With the drop in pressure, nitrogen gas comes out of solution with the liquid and forms bubbles. These bubbles are not pure nitrogen, but contain proportionate amounts of Novec 1230 fluid vapor, depending upon the partial pressure relationship.

1.2.4.1

Pressure Recession Pressure recession curves for filling densities of 35, 40, 50, 60, and 70 lbs./cu.ft. have been calculated and are plotted in Figure 1.2.4.1A. These calculated pressure recession curves are based upon an assumption of thermodynamic equilibrium between the liquid and vapor phases in the storage cylinder. In an actual system discharge, a sharp drop in pressure is noted during the initial rush of liquid into the pipeline. Figure 1.2.4.1B shows actual pressure versus time data taken during an Novec 1230 fluid discharge. The cylinder pressure initially falls below the pressure calculated for the equilibrium condition. This effect is due to a time lag between the initial depressurization and the boiling of the liquid in the storage container. As soon as the liquid begins to boil violently forming vapor bubbles, the surface area of the liquid-vapor interface increases at a tremendous rate and the cylinder pressure recovers to follow the pressure recession curves for saturation equilibrium. It is assumed that virtually all of the vapor formed by boiling in the cylinder remains in the cylinder during the discharge and only the liquid phase enters the pipeline. Depending upon the initial fill density, between 85% and 96% of the total contents is discharged as liquid, with the remaining agent following as a residual vapor phase.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 2

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

N O V E C C Y L IN D E R P R E S S U R E R E C E S S IO N 400

350

PRESSURE (PSIA)

300

250

200

150

100

50

0 0%

10%

2 0%

3 0%

40 %

50%

6 0%

7 0%

80 %

90%

100 %

P E R C E N T D IS C H AR G E D

70 L B /C U F T

60 L B /C U F T

50 L B /C U F T

40 L B /C U F T

35 L B /C U F T

Figure 1.2.4.1A Calculated pressure in the storage container versus the percent of agent supply discharged from the container is plotted for the 360 psig system.

Figure 1.2.4.1B Pressure versus time data taken during an actual Novec 1230 fluid discharge at 70 lbs/cu.ft. density.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 3

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1.3

The Piping System

1.3.1

Pipeline Flow The liquid continues to boil because of further pressure drop as it flows through the pipeline. Hence, the agent flowing in the pipeline is a true two-phase mixture of liquid and vapor. Since the volume of the vapor phase increases with the dropping pressure, the average density of the mixture falls off from an initial value of about 103 lbs/cu.ft. as it leaves the cylinder to values of 67 lbs/cu.ft. or less, depending upon the pressure at the end of the pipeline. In order to maintain a constant flow rate through the pipeline, the velocity must continuously increase and, of course, the rate of pressure drop per foot of pipe also increases. Hence, the rate of pressure drop for a given flow rate is not linear as with water, but is a variable depending upon the density existing at the particular point in the pipeline.

1.3.2

Pipeline Density The density of the two-phase mixture in the pipeline can be calculated on the basis of the thermodynamic properties of the agent, taking into account the effects of the nitrogen used for superpressurization. The density of the agent as it leaves the cylinder varies from the start to the completion of the liquid phase of the discharge. The starting density is lowest for the first portion of liquid to leave the cylinder and becomes progressively greater until the final portion of liquid leaves the cylinder.

1.3.3

Temperature As the agent flows from the cylinder into the pipeline, the drop in cylinder pressure is accompanied by a drop in temperature. As the agent flows down the pipeline, the additional drop in pressure is likewise accompanied by a further drop in the agent temperature. The net effect is the introduction of a cold liquid into the pipeline at ambient temperature.

1.3.4

Initial Vapor Time After the cylinder valve opens, there is a brief period of time during which the air in the pipeline is discharged from the nozzles. As Novec 1230 fluid begins flowing into the pipe, heat is extracted from the pipe until the temperature of the pipe is approximately the same as that of the flowing liquid. This effect is most pronounced at the very beginning of the discharge. For the first few moments of the discharge, virtually all of the liquid entering the pipeline is vaporized before it reaches the discharge nozzles. The mass flow rate for vapor averages about 75% of the rate for liquid in a given system. Therefore, this initial vaporization limits the flow rate until a type of equilibrium condition is achieved between agent temperature and pipe temperature.

1.3.5

Liquid Flow At the beginning of the discharge, there will be a time delay between the opening of the cylinder valve and the time at which liquid begins to discharge from the nozzles. This delay in “liquid arrival time” at the nozzle is due to three physical phenomena: evacuation of air from the pipe, the time needed for the pressure wave to travel from the cylinder outlet to the nozzles, and vaporization of some liquid Novec 1230 fluid due to heat input from the pipe. The delay for each nozzle to begin discharging liquid may vary in an unbalanced system - nozzles close to the cylinder may begin discharging liquid somewhat before more distant nozzles. After these initial transient conditions, the mass flow rate in the system is relatively constant until the last of the liquid phase leaves the cylinder. The last “slug” of liquid leaving the cylinder is propelled by residual vapor in the cylinder. Transient conditions again take effect as the liquid discharge ends and the nozzles discharge the residual vapor. The end of liquid occurs at slightly different times for the various nozzles. Nozzles closer to the cylinder generally will stop discharging liquid sooner than more distant nozzles.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 4

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1.3.6

Phase Separation As already noted in paragraph 1.3.1, the liquid phase of the discharge, in reality, contains a mixture of both liquid and vapor. In a properly sized pipeline, the velocity will be so great that the flow is in a highly turbulent state and the liquid and vapor phases will be uniformly mixed. However, if the pipe size is too large for the flow rate, the liquid and vapor phase may tend to separate. If such separation does occur, the pipeline flow pattern will take one of two forms - both of them very undesirable: 1) alternate slugs of liquid and vapor will flow through the pipe; or 2) the liquid phase will run along the bottom of the pipeline while the vapor phase flows above it. If such separation were to occur in a branch line leading directly to a nozzle, the discharge from that nozzle would be sporadic due to the alternate flow of the liquid and vapor phases. The computerized flow calculation also uses a friction factor for system piping that is based on turbulent flow conditions. In order to help assure turbulent flow, minimum flow rates are specified based on pipe diameter. The minimum flow rates are tabulated in paragraph 2.1.1.4.

1.4

The Discharge Nozzle The discharge nozzle is the ultimate device that delivers the agent to the hazard area. The nozzle flow rate is dependent upon the velocity, pressure and density of the agent as it enters the nozzle. The flow rate from any nozzle device is limited to the amount of flow that the pipeline can deliver to the nozzle.

1.4.1

Maximum Pipeline Flow The maximum flow rate that can be carried by a pipe at a given velocity, pressure and density condition is determined by the laws of energy conservation. Figure 1.4.1 shows calculated maximum pipeline specific flow rates as a function of total nozzle pressure for the 360 psig (25.8 bar) storage condition. The densities used for this calculation correspond to the average pipeline densities for the various systems with a factor added to compensate for velocity effects. These figures represent the maximum flow rates that might be expected from an open-end pipe at the given pressures. Any orifice attached to the end of a pipe will necessarily restrict the flow rate to something less than these maximum figures.

N O V E C 7 0 lb /c u ft F IL L D E N S IT Y S P E C IF IC N O Z Z L E F L O W R AT E S 70

SPECIFIC RATE (lbs/sec/sq in)

60

50

40

30

20

10

0 0

50

100

150

200

250

300

P R E S S U R E (P S IA)

Figure 1.4.1

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 5

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1.4.2

Nozzle Rating Nozzles are rated in terms of their efficiency relative to “perfect” flow from an open ended pipe. Thus, all nozzle rates will fall between 0 and 100 percent. It is not possible to increase the rate of flow from a pipeline by attaching a nozzle. Hence, it is impossible to have a nozzle with efficiency greater than 100. Because of geometry considerations for the Chemetron 8 port nozzle, the maximum ratio of nozzle orifice area to feed pipe area is limited to 85% for all nozzles except the 1/4" NPT nozzle. The limit is 75% for the 1/4" NPT nozzle. This information has been plotted in Figure 1.4.2. NOTE THE 1/4" NOZZLES ARE NOT UL LISTED NOR FMRC APPROVED.

Figure 1.4.2 Nozzle efficiencies for the Chemetron 8 port nozzle are related to the ratio of total orifice area to feed-pipe area. See Note in Paragraph 1.4.2.

1.4.3

Nozzle Characteristic Curve Test work using a nozzle with radial discharge ports was done to determine the relationship between orifice area, feed pipe area, and nozzle efficiency. The results of this test work are summarized in Figure 1.4.2. This figure shows the relationship between the percent of open-end pipeline flow rate permitted by a nozzle and the ratio of actual orifice hole area to feed pipe cross-sectional area. This data is valid only for the Chemetron Fire Systems’ line of eight port nozzles. Other orifice geometries will yield their own characteristic code vs. area-ratio curve.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 6

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1.4.4

Average Pressure Conditions Since the changing conditions in the storage cylinder throughout the discharge are reflected at the nozzle, an average condition for purposes of calculation must be chosen. The volume of piping, however, has a marked effect on the average pressure, density, and velocity conditions at the nozzle. It is the average conditions at the nozzles that ultimately determine the quantity and duration of agent discharge from each nozzle.

1.4.5

Average Nozzle Pressure The average nozzle pressure is chosen at the point in the discharge when half of the liquid phase of the agent has left the nozzle. The pressure drop between the storage container and nozzle should be calculated for this point in time. In order to choose the proper cylinder pressure for this calculation, the quantity of agent that resides in the pipe must be considered. For example, consider a system in which 20% of the agent weight resides in the pipeline during equilibrium discharge. When 50% of this liquid phase has been discharged from the nozzle, approximately 70% of the agent will have left the storage container. The pressure in the cylinder at this point in time will be that indicated on the storage pressure recession curve for the 70% outage condition. Figure 1.4.5 depicts this situation.

Figure 1.4.5

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 7

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

1.4.6

Liquid Arrival Time The amount of time required for the initial slug of liquid to travel from the cylinder to each of the nozzles is the Liquid Arrival Time. This time is dependent on both the length of pipe between the cylinder and nozzle and the velocity of liquid in the pipe. The difference between the longest and shortest initial vapor time cannot exceed 2 seconds.

1.4.7

Liquid Runout Time As the last slug of liquid leaves the cylinder, residual vapor follows. On an unbalanced piping system there may be a difference in time at which the liquid-vapor interface reaches the various nozzles. The program limit is set at a 6.3 second maximum difference in the liquid runout time.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 8

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2

FLOW CALCULATIONS

2.1

Design Criteria The Chemetron Fire Systems method of flow calculation is embodied in a computer program that is capable of computing flow to a very high degree of accuracy, provided proper input data is supplied.

2.1.1

Limitations Any distribution system that does not employ exactly the same actual and equivalent lengths of pipe from the storage cylinder to each nozzle, and the same orifice sizes for each nozzle has some degree of system imbalance. Such systems are, however, the rule rather than the exception. Due to structural components present at the job site, it is often impossible to install perfectly balanced piping systems. However, it is desirable to maintain balanced piping whenever possible.

2.1.1.1

Splits at Bullhead Tees The mechanical separation of phases that is evidenced at bullhead tees is outside classical thermodynamic theory. In order to predict the amount of agent that will be discharged from nozzles fed by bullhead tees, a correction for this phase separation must be incorporated in the flow calculation. The correction is an empirical factor based on a body of laboratory test data. The empirical correction is adequate for bullhead splits with as little as 25% of the flow going to the “minor” branch. Of course, the upper limit of the correction is a balanced, “50-50” split at a bullhead tee.

2.1.1.2

Splits at Side-Thru Tees A similar empirical correction for side-thru tee phase separation effects is incorporated in the flow calculation program. The empirical correction is adequate for side branch flows from 10% up to 35% of the incoming flow.

2.1.1.3

Discharge Time NFPA 2001 currently requires that 95% of the design quantity shall be discharged within 10 seconds or less from start of discharge. A system must, therefore, be designed to meet this criterion unless the authority having jurisdiction permits a longer discharge time. The Chemetron program is listed for discharge times between 5 seconds and 10 seconds.

2.1.1.4

Minimum Flow Rates The pipe friction factor embodied in the energy conservation equation used to calculate pressure drop for two-phase flow in fire protection systems is based on the premise that highly turbulent flow is present in the pipeline. Also, a high degree of turbulence must be maintained in pipe sections that approach dividing points. The pipe size that can be used for a given flow rate is thus based upon the minimum flow rate required to maintain complete turbulence. This limitation is shown in Figure 2.1.1.4 and is automatically taken into consideration when the computer selects pipe sizes for the system. Flow rates as low as 60% of the minimum rates on the graph may be used in branch lines that lead directly to nozzles with no intervening flow division.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 9

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Table 2.1.1.4 - Pipe Size vs Flow Rate Schedule 40 Pipe Pipe Size Nominal Inches (mm)

Schedule 80 Pipe

Minimum Flow Rate For All Sections Leading to a Tee

60% of Flow Rate For All Sections Ending with a Nozzle

Minimum Flow Rate For All Sections Leading to a Tee

60% of Flow Rate For All Sections Ending with a Nozzle

Lbs/Sec

Kg/Sec

Lbs/Sec

Kg/Sec

Lbs/Sec

Kg/Sec

Lbs/Sec

Kg/Sec

1/4

(8)

0.68

0.31

0.41

0.19

0.30

0.14

0.18

0.08

3/8

(10)

1.55

.70

0.93

.42

1.06

0.48

0.64

0.29

1/2

(15)

2.58

1.17

1.55

.70

1.95

0.88

1.17

0.53

3/4

(20)

4.53

2.05

2.72

1.23

3.68

1.67

2.21

1.00

1

(25)

7.29

3.31

4.37

1.98

6.08

2.76

3.65

1.65

1-1/4

(32)

12.67

5.75

7.60

3.45

10.83

4.91

6.50

2.95

1-1/2

(40)

17.46

7.92

10.48

4.75

15.06

6.83

9.04

4.10

2

(50)

29.82

13.53

17.89

8.12

25.96

11.78

15.58

7.07

2-1/2

(65)

44.06

19.99

26.44

11.99

38.51

17.47

23.11

10.48

3

(80)

71.34

32.36

42.80

19.42

62.96

28.56

37.78

17.13

3-1/2

90

98.32

44.60

58.99

26.76

87.46

39.67

52.48

23.80

4

(100)

129.28

58.64

77.57

35.18

115.87

52.56

69.52

31.53

5

(125)

205.71

93.31

123.43

55.99

187.31

84.96

112.39

50.98

6

(150)

286.54

129.97

171.92

77.98

262.77

119.19

157.66

71.51

NOTE:

The pipe friction factor embodied in the energy conservation equation used to calculate pressure drop for two-phase flow in fire protection systems is based on the premise that highly turbulent flow is present in the pipeline. Also, a high degree of turbulence must be maintained in pipe sections that approach dividing points. The pipe size that can be used for a given flow rate is thus based upon the minimum flow rate required to maintain complete turbulence. This limitation is tabulated in the Table and is automatically taken into consideration when the computer selects pipe sizes for the system. Flow rates as low as 60% of the tabulated minimum rates may be used in branch lines that lead directly to nozzles with no intervening flow division.

NOTE THE 1/4" NOZZLES ARE NOT UL LISTED NOR FMRC APPROVED.

2.1.1.5

Tee Installation Pipe tees supplying branch lines are to be installed with both outlets discharging horizontally. This is to eliminate any possible effect of gravity upon the degree of liquid-vapor separation. This limitation does not apply to manifold piping for groups of cylinders where flow is combining rather than dividing. There must be a minimum of 10 nominal pipe diameters between an elbow and the inlet to any tee (does not apply in manifolds where flow is combining).

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 10

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Figure 2.1.1.5A - Orientation of Tees : Tee outlets should be placed in the gravitational effects on liquid - vapor separation

horizontal plane to minimize

Figure 2.1.1.5B - Minimum Distance From Elbow to Tee: Minimizes centripetal effects on liquid - vapor separation before entering a flow split.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 11

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.1.1.6

Ratio of Agent in Pipe Limit This limit is 99.5%. This was established through testing. This limit is defined as follows: Volume of pipe x density of the agent in storage / quantity of agent in storage

2.1.1.7

Minimum Nozzle Pressures The minimum nozzle pressure for which the Chemetron 8 port nozzle is approved is 75 psia (4.1 bar). If the program is used to calculate an “as-built” system, it will calculate lower nozzle pressures - an error or warning message will result if pressures below the pressures required for the approval agencies are calculated.

2.1.1.8

Maximum Orifice Size A. 360o Nozzle The maximum nozzle orifice size that may be used in the system is limited in two ways. First there is a limit on the ratio of actual nozzle orifice area to cross section area of the feed pipe. This ratio is limited to 85% for all Chemetron 360o - 8 port nozzles except the 1/4" NPT size. The internal geometries of the 1/4" NPT size nozzle are such that the ratio of actual nozzle orifice area to cross sectional area of the feed pipe is 75%. NOTE: The 1/4" nozzle is not FMRC approved or UL listed. This limitation is checked by the computer and could be checked manually. (For details regarding the second limitation, see paragraph C below.) B. 180o Nozzle Due to geometric constraints and the need to keep a sharp-edged orifice, in sizes up to and including 3/4" NPT (19 mm), the 180o sidewall nozzle has a lower ratio of orifice area to feed pipe area. This value is different for each size nozzle through 3/4" NPT. The program checks the calculated orifice area to see if the optimal nozzle calculated is within the acceptable range. If it is not, the program will show “Not Avail.” in the nozzle stock number column. C. Common to Both 360o and 180o Nozzle For both 360o and 180o nozzles there is a limit on the ratio of flow through the nozzle to the theoretical maximum flow that the feed pipe branch could carry under the calculated pressure, density and temperature conditions. This limit is 65% of the maximum feed pipe flow. The computer checks this. This limitation serves two purposes: 1) it insures that the nozzle, and not the equivalent length of the pipe run, will control the amount of discharge from that nozzle; and 2) it provides an automatic check against calculating systems having nozzle flow rates that cannot be achieved under the calculated terminal pressure conditions.

2.1.1.9

Minimum Orifice Area The minimum nozzle orifice area ratio relative to the cross section area of feed pipe is 20%.

2.1.1.10 Transient Effect Limits A program limit is set to permit no more than 2 seconds difference between the shortest and longest liquid arrival times at the system nozzles. If the time difference is greater than 2 seconds, an error message is generated. A similar limit is set for the end of liquid times for the various nozzles in the system. If the maximum difference in calculated end of liquid times is greater than 6.3 seconds, an error message is generated.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 12

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.2

Design Philosophy The basic philosophy underlying the method of flow calculation presented herein is to provide a mathematical model of the events that take place during an actual Novec 1230 fluid discharge. In the final analysis, the main criteria for a good design procedure is that it accurately predict the amount of agent that each nozzle in the system will discharge. The calculating procedure has been tested and shown to be accurate within plus 10% or minus 10% of the actual distribution. All of the considerations mentioned in the first chapter of this manual are taken into account in the computerized method of system design. The following considerations are also made in the computerized design procedure.

2.2.1

Average Cylinder Pressure During Discharge The average pressure in the storage containers for purposes of flow calculation is dependent upon both the cylinder fill density and, as already discussed, percent in the pipe. Calculations may be based upon cylinder fill densities of 35, 40, 50, 60, or 70 lbs/ft3 (560.7, 640.8, 801, 961.2, 1121.4 kg/m3).

2.2.2

Velocity Head The velocity of flow is constantly changing as the agent proceeds from the storage cylinder in route to the nozzles. This conversion of pressure energy to velocity, necessitated by the changing density, is accounted for in the two-phase flow equation. When a change in pipe size is encountered or when the flow branches, an added change in the velocity of flow must occur. If the velocity is increased, there will be a drop in pressure to provide the energy needed for acceleration. If the velocity is reduced, a portion of the velocity head energy is converted back to pressure. These changes are over and above those accounted for in the two-phase energy conservation equation. Correction for these effects is automatically made in the computer program.

2.2.3

Elevation Changes Head pressure corrections are made in each pipe section where a change of elevation takes place. The corrections are based upon the calculated density of the fluid as it enters each such section. When the elevation difference between outlet tees is in excess of 40 feet (12.2 m), consideration should be given to rerouting piping to reduce the elevation difference between tees. Even though sound engineering theory is used to predict pressure changes due to elevation, no actual testing has been performed incorporating the combination of maximum and/or minimum limits with elevations outside this range. 1. If nozzles are located above the container outlet, then the maximum elevation difference between the container outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest) shall not exceed 40 feet (12.2 m). 2. If nozzles are only located below the container outlet, then the maximum elevation difference between the container outlet and the furthest horizontal pipe run or discharge nozzle (whichever is furthest) shall not exceed 40 feet (12.2 m). 3. If nozzles are located both above and below the container outlet, then the maximum elevation difference between the furthest horizontal pipe runs or discharge nozzles (whichever is furthest) shall not exceed 40 feet (12.2 m).

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 13

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.3

Nozzle and Piping Layout The first step in designing the piping distribution system is to prepare a layout of nozzle location, storage location, and piping on a suitable plan drawing of the hazard. Such a layout is illustrated in Figures 2.3A & 2.3B. Note that the nozzles are installed at the same elevation. The following points should be considered:

2.3.1

Nozzle Location The Chemetron Fire Systems line of total flooding nozzles was tested to demonstrate adequate distribution over a nominal area of 1,248 ft2 (115.9 m2). The 360o nozzle cannot be mounted in a corner or against a wall. The maximum discharge radius is 25.0 ft (7.6 m). A single nozzle may be used to flood a rectangular area of a nominal 1,248 ft2 (115.9 m2), with the longest side of this rectangle not to exceed 35.4 ft (10.8 m). Nozzles must be oriented so that a pair of orifice holes parallels the wall of the enclosure. These nozzles should be centered in the area of protection when multiple nozzles are discharged into the same hazard. The maximum throw distance of the 180o nozzle is 35.0 ft (10.7 m). The maximum distance between 180o nozzles is 35.4 feet (10.8 m). The maximum coverage distance from the nozzle to a wall is 17.7 feet (5.4 m). The 180o nozzle must be installed at no more than 6 inches (15.2 cm) from the enclosure wall and at a maximum of 14.0 inches (35.6 cm) down from the ceiling. For UL, ULC, and FMRC, the maximum enclosure height that may be flooded by a single tier of nozzles is 16 feet (4.88 m) with the nozzle located no more than 14.0 inches (35.6 cm) below the ceiling. Before using a single nozzle at the maximum area or volume rating, consideration should be given to whether the contents of the hazard might be damaged by the resultant high velocity discharge. In hazards such as computer rooms or areas where fragile apparatus is stored, the number of nozzles used to flood an area should be increased so as to limit discharge velocities to a safe level. After considering possible damage to the hazard by the Novec 1230 fluid discharge and determining a reasonable area [not to exceed 1,248 ft2 (115.9 m2)] to be covered by each nozzle, the nozzles should be located. The Chemetron 8 port nozzles must be placed in the center of each area. The discharge rate for each nozzle should be based upon flooding the volume protected by that nozzle within the design discharge time.

2.3.2

Underfloor Nozzles The maximum area of coverage for a single nozzle in an underfloor is likewise 1,248 ft2 (115.9 m2) with the same limitations on height and positioning noted in the preceding paragraphs. The MINIMUM height of an underfloor that may be protected is 12 inches (30.5 cm). The coverage possible in an underfloor is dependent upon the density of cables, runways, and other equipment that might be present in the underfloor space. The maximum figures should be used only for underfloors that will be relatively open. This requires some judgment on the part of the designer, but in general, if the horizontal line of sight is more than 70% obstructed in an underfloor, these maximum figures should be reduced by 50%.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 14

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.3.3

Cylinder Storage Location Ideally, the storage cylinder should be located in an area where the ambient temperature is at least 60oF (15.6oC). Since systems are designed for a 70oF (21.1oC) storage condition, optimum performance can be expected if the storage area is kept near 70oF (21.1oC). For unbalanced systems, proper distribution and adequate system performance is approved for storage temperatures of 70oF ±10oF (21.1oC ±5.5oC). Calculations performed on systems where the cylinders are not maintained within this range may not be accurate and the required quantities of agent may not be discharged from one or more nozzles. NOTE THE AMBIENT STORAGE TEMPERATURE MUST BE BETWEEN 0OF (-17.8OC) TO 130OF (54.4OC).

Figure 2.3A Plan View - Above Floor System

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

Figure 2.3B Plan View - Underfloor System

S/N 30000066 Page 15

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.3.4

Pipe Routing The piping between storage containers and nozzles should be by the shortest route, with a minimum of elbows and fittings. Every attempt should be made to keep the system in reasonable balance by supplying the nozzles from a central point, if this can be done without substantially increasing the length and volume of the piping. The maximum pipe run permissible will be somewhat proportional to the total quantity of agent to be discharged. All piping elevation changes should be clearly indicated so that these will not be overlooked in flow calculations.

2.3.5

Pipe Sections The piping system must now be divided into sections and identified for flow calculation purposes. An isometric sketch of the piping is helpful at this point. (Refer to Figures 2.3A and 2.3B.) Beginning at the first storage cylinder, the first piping section shall begin at point 1 within the cylinder and terminate at point 2 where the connector from the cylinder joins the cylinder manifold. The next section, beginning at point 2, must include the entire straight portion of the manifold. A new pipe section is identified whenever there is a change of pipe size or flow rate, or an elevation change. Pipe sections terminate at the junction of each tee in the system and tees are included in the sections that follow them. Nozzles are identified by a series of ID numbers from 301 to 499.

2.4

Hydraulic Flow Calculation Program (CHEM-1230) The next step in system design is to provide the necessary design parameters to the computer program to numerically model the system accurately. The program, CHEM-1230, has been written within the Windows™ environment. (It is our assumption that the user has a basic knowledge of this operating system and its operation will not be directly addressed within this manual.) The computer program will establish pipe sizes, calculate terminal pressures, discharge time, and nozzle drill sizes. The primary requirement for a proper calculation is that the system be modeled into the computer correctly. Therefore, the parameters may be printed out as well as the calculation results. This makes it possible to verify the input data against the intended design parameters and/or the actual installation. It is possible to input either the flow rate required for each nozzle or the existing nozzle drill sizes. The Chemetron flow calculation program for Novec 1230 fluid has been divided into three main areas: Commands Available, Output and File Utilities. NOTE THE CALCULATION INFORMATION CAN BE ENTERED AND DISPLAYED IN US STANDARD OR METRIC UNITS. IT CAN BE CONVERTED AT ANY TIME UPON COMMAND BY SIMPLY USING THE METRIC CHECK BOX.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 16

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.4.1

Commands Available This area has been subdivided into five categories: System Information Hazard Information Piping Model Data Calculate and Display Results Clear All Current Data

Figure 2.4.1 Flow Calc Program - Commands Available

For reference only, a Vol/Lbs/% calculator, a CARDOX valve equivalent length chart, and a minimum flow rate chart have been included.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 17

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.4.1.1

System Information Within the System Information screen there are four submenus: Project Data Revision Cylinder Data Configuration Variables A. The Project Data section consists of the following data: 1.

Project Number: Reference number

2.

Project Name: Name of project or end user

3.

Site Location: Installation location

4.

Hazard Name: Name of protected hazard.

Figure 2.4.1.1.A Flow Calc Program - Project Data

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 18

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

B. Revision: This data field is used to track versions/changes on a specific data file and/or submittal. C. Discharge Time (sec.): By default, this is set to 10 seconds. This box is here for troubleshooting purposes. If you have a calculation that runs longer than 10 seconds, you can decrease this value and the flow calculation will increase the discharge rate to try to accommodate the new discharge time setting. Alternatively, you can set this value higher than 10 in order to attempt to achieve some type of results by decreasing the rate. This is helpful if the pressures drop to 15 psia (1.03 bar).

Figure 2.4.1.1.B Flow Calc Program - Revision Version Data Field

D. The Cylinder Data section consists of the following data: 1. Pounds/Cylinder (Kilograms/Cylinder): This data field is used to input the actual amount of Novec 1230 fluid required per cylinder. 2. Number of Cylinders: The number of cylinders required to contain the amount of Novec 1230 fluid required for a discharge. This value may be entered by one of two means: the value may be directly entered into this field or a value may be selected from the drop-down list, which can be accessed by clicking onto the arrow at the right of the data field. 3. Cylinder Capacity: This data field is used to input the description of the actual type of cylinders to be used. The nominal cylinder capacity is displayed for the chosen cylinder assembly along with its minimum and maximum cylinder capacity. By clicking on the arrow at the right of the field, additional cylinder choices may be viewed. User Specified Beta, Gamma, and Sigma can be selected from the list for special cylinder capacities, in which case the cylinder volume capacity will need to be inputted and either the Beta, Gamma, or Sigma valve selected.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 19

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

WARNING WHEN THE CYLINDER CAPACITY FIELD FOR “USER SPECIFIED” BETA, GAMMA, AND SIGMA CYLINDERS IS USED, FACTORY MUTUAL RESEARCH CORPORATION APPROVAL AND UL LISTING HAVE BEEN VOIDED.

Figure 2.4.1.1.C Flow Calc Program - Cylinder Data

TABLE 2.4.1.1.C - CYLINDER CAPACITY CHART CAPACITY CYLINDER

MINIMUM LBS

CAPACITY MAXIMUM

KG

LBS

CYLINDER

KG

Alpha Cylinders

MINIMUM LBS

MAXIMUM

KG

LBS

KG

Beta Cylinders

Alpha 10#

6

2.7

12

5.4

Beta 40#

21

9.5

41

18.6

Alpha 20#

12

5.4

23

10.4

Beta 55#

28

12.7

55

24.9

Beta 95#

48

21.8

96

43.5

Gamma 150#

82

37.2

163

73.9

Gamma 250#

138

62.6

274

124.3

Sigma 600#

304

137.9

607

275.3

Gamma 400#

211

95.7

421

191.0

Sigma 750#

455

206.4

910

412.8

Gamma 550#

282

127.9

500

226.8

Sigma 1000#

620

281.2

1,000

562.0

Gamma Cylinders

Sigma Cylinders

NOTE: Chemetron Alpha cylinder/valve assemblies are not UL and ULC listed nor FMRC approved.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 20

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

4. Max Capacity: This is a read only field and is intended to inform the user of the maximum capacity of Novec 1230 fluid to which the cylinder selected may be filled. 5. Pipe Temp: The initial average pipe temperature shall be inputted here to accurately calculate the vapor portion of the discharge. UL listing and FMRC approval is based upon a temperature of 70oF ±10oF (21.1oC ±5.5oC). Calculations performed on systems where the cylinders are not maintained within this range may not be accurate and the required quantities of agent may not be discharged from one or more discharge nozzles. 6. Cylinder Volume [ft3 (m3)]: This heading will only appear when either the Beta User Specified, Gamma User Specified, Sigma User Specified, or User Specified cylinder option is selected. This shall be used to accurately compute the minimum and maximum fills for a unique cylinder. NOTE WHEN A BETA CYLINDER IS CHOSEN IN THE CYLINDER CAPACITY DROP DOWN LIST AND THE MAIN AND RESERVE CHECK BOX IS CHECKED, THERE WILL BE NO EQUIVALENT LENGTH CHANGE IN LINE 1 OF THE PIPING MODEL. THIS BECAUSE THE OVERSIZED CHECK VALVE USED HAS A NEGLIGIBLE EQUIVALENT LENGTH. 7. Main/Reserve: Automatically adds the equivalent length of a required check valve for main and reserve systems. E. The Configuration Variables section consists of the following data: 1. Report Title: The data entered here will appear in the general heading area on all printouts. The intended use is to allow Chemetron distributors to incorporate their company name into the printouts. 2. Altitude: This data field allows for the installation of a system from -3000 feet (-.914 km) below sea level up to 10000 feet (3.05 km) above sea level. These values may be selected from the drop-down list. These values are established in NFPA 2001.

Figure 2.4.1.1.E2 Flow Calc Program - Configuration Variables - Altitude

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 21

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

3.

Calculation Method: The calculation may be performed by either Automatic or Manual means. The automatic mode will not allow the user to view the current attempt to solve the data into a satisfactory result and does not require any user interface during the calculation. The manual mode will pause after each attempt to solve the system design parameters. This will allow the user to view the results - acceptable or not - of the previous calculation run. This manual mode may aid the user in troubleshooting a problematic design.

4.

Nozzle Material: Allows the choice of either stainless steel or brass nozzles.

5.

Exclude Pipe Sizes: When selected, it will force the flow calculation module to ignore a given pipe size(s).

NOTE DUE TO PRESSURE AND FLOW RATE LIMITATIONS, THIS MAY INCREASE THE DIFFICULTY IN GETTING VALID CALCULATION RESULTS. 2.4.1.2

Hazard Information Within the Hazard Information screen there are three subcategories: Hazard Data Area Data Area Nozzle List An example of an area would be a room. All nozzles must be in the same room. Individual data must be entered for each area to ensure that the appropriate amount of Novec 1230 fluid is divided accordingly. This portion of the program will model the data for each area. UL and FMRC will accept no less than a 4.2% design concentration in any application. Additional areas may be added to the data list to calculate more than one area simultaneously. Example: room area, underfloor and false ceiling.

Figure 2.4.1.2 Flow Calc Program - Hazard Data

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 22

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

A. Hazard Data The first section is used to input the hazard area name(s) for reference, concentration required and the temperature. 1.

Area Name: Enter the name of the specific area.

2.

Fire Type: Three choices are available - Class A Fire, Class B Fire and Class C Fire. The default design concentration is 4.2%. If Class B Fire is chosen, a form appears that lists all of the Class B fuels that have been tested and the extinguishing concentration required. Simply select the Class B fuel being protected and click the Okay button - the appropriate concentration will be inserted into the hazard data grid. To cancel your selection, click the close button to close the form; the default selections - 4.2% design concentration and Class A Fire - will be inserted into the hazard data grid. Class C fires are defined by NFPA 2001 as “fires that involve energized electrical equipment where the electrical non-conductivity of the extinguishing media Figure 2.4.1.2.A2 - Class B fuels list is important.” This means that if the equipment cannot be de-energized in a fire condition, it must be treated as a Class C fire.

3.

% Concentration: Enter the required concentration here.

4.

Temperature: Enter the temperature for the area.

5.

Total Volume: This field is provided for information only and may not be modified. This field will indicate the total volume of the area as input into the Area Data section below.

B. Area Data Enter the appropriate values in the Length, Width and Height fields and the program will compute the correct room volume and amount of agent required automatically. As you will note, the Width and Height fields are both set to a default of 1. If the volume is known, enter it into the Length data field and leave the Width and Height fields as 1. Once the data has been entered, clicking on the Add button will assign this data to the current hazard. C. Area Nozzle List Each area will have one or more nozzles within it. This section is intended to model the nozzles for a particular area. Each nozzle has a unique ID number. These numbers are automatically assigned and are incremental. Two types of nozzles are included in the program: the 8 Port 360o discharge pattern (Style F) nozzle and the 8 Port 180o discharge pattern (Style J) nozzle. The nozzle IDs available for 360o radial nozzles are 301-399; for 180o radial nozzles, IDs range from 401-499. D. Add and Delete Data In The Hazard Data Screen 1.

ISSUED:

7/1/2004

Add: Once the correct values have been entered into the editing box, clicking on the Add button within that section will temporarily save the data to the screen. Another line of data may then be entered on the blank line created at the bottom of the grid.

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 23

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.

2.4.1.3

Delete: To delete a line of data from the data file, the name of the area containing the data to be deleted must appear in the Current Hazard box of the Hazard Data section. Click on the area name with the mouse so that the appropriate information is reflected on the Current Hazard box. Again, the corresponding data will appear in the Area Data and Area Nozzle List sections. Move the mouse to the appropriate field and click on the line to be deleted. Clicking on the Delete button will delete this data.

Piping Data The Piping Data is the heart of the system model; it’s the area where the pipe and pounds/nozzle data is recorded. Several pieces of information are required. The following is a brief description of each of the columns.

Figure 2.4.1.3 Flow Calc Program - Piping Data

A. Column Headings and Descriptions

ISSUED:

1.

Nodes: These points identify the section of pipe, Figure 2.4.1.3.A3 - Hazard nozzle reference box nozzle or a cylinder that is being modeled.

2.

Start: This indicates the beginning of a pipe, manifold, or cylinder section.

3.

End: This indicates the end of the same section. If this line is a nozzle, clicking the button that appears in this cell will cause a hazard nozzle reference box to be visible. Here the user can scroll through the hazards and select the desired nozzle.

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 24

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

4.

Cyl Qty: The quantity of cylinders flowing through this specific section of piping.

5.

Pipe Len: Total length of pipe expressed in feet or meters, including any elevation changes.

6.

Elev: Change of elevation within the pipe section, expressed in feet or meters. A positive number indicates a rise in elevation. A negative number indicates a drop in elevation. A zero (0) indicates no change in elevation.

7.

Type: Type of pipe to be installed. There are several types available, accessible through the pop-down, for use: a. 40T: Schedule 40 pipe with threaded fittings. b. 40W: Schedule 40 pipe with welded fittings. c. 80T: Schedule 80 pipe with threaded fittings. d. 80W: Schedule 80 pipe with welded fittings. e. 40G: Schedule 40 pipe with grooved fittings.

Figure 2.4.1.3.A7 Flow Calc Program - Piping Data - Type

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 25

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

8.

Size: The size of pipe in the section. By accessing the pop-down window, choices from zero (0) (no fixed pipe size) to 6" (150 mm) are available.

Figure 2.4.1.3.A8 Flow Calc Program - Piping Data - Size

NOTE BOTH THE INTERNAL PIPE DIAMETER AND THE MASS OF THE PIPE ARE USED IN THE HYDRAULIC CALCULATION. IT IS ESSENTIAL THAT THE PIPE USED FOR INSTALLATION HAS A DIAMETER AND WALL THICKNESS (WITHIN TOLERANCES SPECIFIED IN ANSI AND ASTM STANDARD) USED IN THE CALCULATION. THE WEIGHT PER UNIT LENGTH OF THE PIPE IS DIRECTLY RELATED TO THE INTERNAL DIAMETER AND WALL THICKNESS. THE FOLLOWING TABLE GIVES THE NOMINAL PIPE SIZES WITH THE PIPE DIAMETER AND WEIGHT PER UNIT LENGTH USED IN THE HYDRAULIC CALCULATION.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 26

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Table 2.4.1.3.A8 - Pipe Size

Schedule 80

Schedule 40

Pipe Type

ISSUED:

7/1/2004

REV. A

Nominal Pipe Size inch

mm

ID (inches)

Weight (lb/ft)

1/8

6

0.269

0.24

6.83

0.36

1/4

8

0.364

0.42

9.25

0.63

3/8

10

0.493

0.57

12.52

0.85

1/2

15

0.622

0.85

15.80

1.26

3/4

20

0.824

1.13

20.93

1.68

1

25

1.049

1.68

26.64

2.50

1-1/4

32

1.380

2.27

35.05

3.38

1-1/2

40

1.610

2.72

40.89

4.05

2

50

2.067

3.65

52.50

5.43

2-1/2

65

2.469

5.79

62.71

8.62

3

80

3.068

7.58

77.93

11.28

3-1/2

90

3.548

9.11

90.12

13.56

4

100

4.026

10.79

102.26

16.06

5

125

5.047

14.62

128.19

21.76

6

150

6.065

18.97

154.05

28.23

1/8

6

0.215

0.31

5.46

0.46

1/4

8

0.302

0.54

7.67

0.80

3/8

10

0.423

0.74

10.74

1.10

1/2

15

0.546

1.09

13.87

1.62

3/4

20

0.742

1.47

18.85

2.19

1

25

0.957

2.17

24.31

3.23

1-1/4

32

1.278

3.00

32.46

4.46

1-1/2

40

1.500

3.63

38.10

5.40

2

50

1.939

5.02

49.25

7.47

2-1/2

65

2.323

7.66

59.00

11.40

3

80

2.900

10.25

73.66

15.25

3-1/2

90

3.364

12.5

85.45

18.60

4

100

3.826

14.98

97.18

22.29

5

125

4.813

20.78

122.25

30.92

6

150

5.761

28.57

146.33

42.52

REVISED:

10/5/2004

ID (mm)

Weight (kg/m)

S/N 30000066 Page 27

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

9.

Fitting: 90 & 45 degree elbows and tees for installation. a. 90's: Number of 90 degree elbows in the pipe section. When 45 degree elbows are used, they are treated as an equivalent number of elbows. In this case, 0.5 should be included for each 45 degree elbow and included in the 90's field. b. Tees: Used when a separation of agent flow is required.

Fitting

Equivalent Number of Elbows

90 Deg Elbows

1.0

45 Deg Elbows

0.5

Tee Thru

0.6

Tee Side

2.0

i.

None: This is the default value. Choose this or simply press enter in this field if no tees are installed.

ii.

Thru: The beginning of the pipe section begins with a thru tee. If the side branch of a tee is used to provide pressure for tripping a pressure switch or pressure release, it is treated as an equivalent number of elbows. In this case, 0.6 should be included in the 90's field.

iii. Side: The beginning of the pipe section begins with a side tee. If one of the thru branches of a tee is used to provide pressure for tripping a pressure switch or pressure release, it is treated as an equivalent number of elbows. In this case, 2.0 should be included in the 90's field. iv. Blow Out: Choose this option if a tee used in the pipe section is part of a blow out, i.e., the last nozzle on a branch line.

Figure 2.4.1.3.A.9 Flow Calc Program - Piping Data - Fittings

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 28

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

10. Cplng/Union: The number of couplings or unions in the pipe section. 11. Pounds (Kgs) Req'd: The number of pounds (kilograms) required to be discharged from this particular nozzle, when the option Fixed Pounds is selected. If the Fixed Orifice option is selected, the value in this field will represent the nozzle orifice drill diameter in inches. To set the rate for a particular nozzle, select the cell and then either type the flow rate in or use the drop down list and select the “Get Rate” option. The computer will automatically calculate and display the required flow rate needed for that particular nozzle. Alternatively, you can set all the flow rates simultaneously after finishing the piping model by following the above steps, but instead of selecting “Get Rate,” select “Set All.” NOTE THE ALPHA CYLINDER/VALVE ASSEMBLIES ARE CURRENTLY NOT UL & ULC LISTED NOR FMRC APPROVED. HOWEVER, THE EQUIVALENT LENGTH NOTED BELOW FOR THE ALPHA VALVE HAS BEEN DETERMINED BY UL AND FMRC AFTER WITNESSING TESTING. 12. Equiv Length: The equivalent length of a cylinder assembly, check valve, or other unique components that may be needed in some systems.

Equivalent Length (Feet/Meters) Cylinder Single Cylinder

Multiple Cylinders w/check valve

Alpha (1/2" outlet)

30 ft (9.14 m)

N/A

Beta (1-1/4" outlet)

60 ft (18.29 m)

60 ft (18.29 m)

Gamma (2" outlet)

51 ft (15.55 m)

64 ft (19.51 m)

61 ft.

80 ft

B. Add, Copy & Paste, Insert, and Delete 1.

2.

Add: The Add button works similarly to the Add button on the previous screens. Once the data has been entered into the grid, clicking on the Add button will add a blank line to the bottom of the pipe grid so that the next line of piping input can be entered.

Sigma (3" outlet)

(18.59 m) (22.56m) Copy & Paste: Click the Copy button. Alternatively, you can depress the F9 key. Select any cell in the row or rows desired to be copied. If multiple rows are desired to be copied at once, simply click on any cell in the first row to be copied and while continuing to depress the left mouse button, highlight the remaining rows. Select a cell in the row where you want to paste the copied rows. Press the Paste button. Alternatively, you can depress the F10 key.

NOTE ONLY CONSECUTIVE ROWS CAN BE COPIED AT ONCE. THE LINES WILL BE INSERTED STARTING AT THE ROW OF THE CELL THAT IS HIGHLIGHTED. YOU CAN PASTE THIS INFORMATION AT ANY TIME AND AS MANY TIMES AS NECESSARY WITHOUT RESELECTING THE ROWS TO BE COPIED. 3.

ISSUED:

7/1/2004

Insert: The Insert button is used to insert a line of data into the data grid in a specific location. In order to insert a line, click on the highest line in the data grid that must be moved down. Once the line has been chosen, click on the Insert button and the lines in the data grid will be relocated down one line position and a new line (identical to the selected line) will be placed into the open position.

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 29

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

4.

Delete: The Delete button is used to delete a line of data in the data grid. Highlight the data line within the data grid by clicking on it with the mouse. Click on the delete button. A verification message will appear to validate the request. Should you confirm the request, the data line will be deleted and any data lines below it will be moved up to compensate for the deleted line of data.

C. Fixed Weight and Fixed Orifices It is possible to input either the pounds or kilograms required for each nozzle or the existing nozzle orifice drill diameter. The program has the flexibility to calculate an existing system model by allowing the nozzle orifice diameter to be input as data. The combination of both weight required from one nozzle and the orifice diameter of the second nozzle is not permitted and cannot be calculated.

Figure 2.4.1.3.C Flow Calc Program - Piping Data - Fixed Pounds & Fixed Orifices

ISSUED:

1.

Fixed Pounds (Kgs): This radio button should be on when the values in the Pounds (Kgs) Required column indicate the quantity of pounds (Kgs) required to be discharged from a particular nozzle.

2.

Fixed Orifices: This radio button should be on when the values in the Pounds (Kgs) Required column indicate the actual nozzle drill diameter in inches for a particular nozzle.

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 30

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

2.4.1.4

Calculate and Display Results By clicking on the Calculate and Display Results button, the data file will be passed on to the calculation program for processing. If the Automatic mode of calculation has been selected, no input from the user will be required during this operation. If the Manual mode of calculation was selected, the user must press Return at the prompts to do so. In either situation, once the calculation process is completed, the results will be displayed on four different screens: Calculation Results Nozzle Performance Hazard Concentration Results Error Messages A. Calculation Results The calculation results screen depicts the cylinder information and the piping model information. 1.

Conditions a. Storage Pressure: The starting pressure just prior to the cylinder actuation. b. Average Cylinder Pressure: The average cylinder pressure during the discharge. c. Average Initial Pipe Temp: The average ambient pipe temperature at the beginning of the discharge. d. Fill Density: The fill density [lbs/ft3 (kgs/m3)] of the cylinder. For all systems, the range is 35 to 70 lb/ft3 (560.7 to 1121.4 kg/m3). e. Ratio of Agent in Pipe: Established limit defined as the volume of pipe x the density of agent in storage / quantity of agent in storage. f. Average Discharge Time: This value represents the average discharge time of all of the nozzles. g. Cylinders: The quantity of cylinders modeled. h. Lbs/Cyl (Kgs/Cyl): Quantity of Novec 1230 fluid within each cylinder.

ISSUED:

7/1/2004

i.

Total Lbs (Kgs) of Novec 1230 Fluid: The total amount of Novec 1230 fluid within all the cylinders.

j.

Cylinder Type: The type of cylinder selected for the calculation.

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 31

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Figure 2.4.1.4.A Flow Calc Program - Calculation Results

2.

Piping Results a. Section Nodes: The starting and ending nodes for a particular section of the pipe model. b. Nominal Pipe Size: The computed or inputted pipe size and schedule. c. Length: Length of pipe within the section, including elevation changes. d. Elev: The length of an elevation change within the section of pipe. e. EQL: Total equivalent length of the section of pipe. This includes pipe, elbows, tees, couplings, unions, valves, and any additional information inputted into the equivalent length column of the data file. f. Start PSIA (Bar): The pressure at the beginning of the section. g. Term PSIA (Bar): The pressure at the termination of the section. h. Flow Rate: The flow rate through the pipe section.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 32

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

B. Nozzle Performance 1.

Nozzle ID: The identification number given to a specific nozzle.

2.

Size: The selected or computed size and schedule of a nozzle.

3.

Stock Number: The Chemetron Fire Systems’ stock number for the particular nozzle.

4.

Style: The manufacturing designation for the particular configuration of the nozzle.

5.

Drill Diameter: The specific drill diameter in inches (mm) for each of the nozzle ports.

6.

Drill Size: The industry's designation for a particular drill diameter.

7.

Total Orifice Area: The total single orifice area for the nozzle.

8.

Novec Discharged: The quantity of Novec 1230 fluid discharged through a particular nozzle.

Figure 2.4.1.4.B Flow Calc Program - Nozzle Performance

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 33

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

8-Port Styles F and J Nozzle Drill Nos/Diameter Charts

3/8 inch 8-Port Styles F & J Nozzle DRILL # * * * * * * * * * * * * * * * * *

5/64 47 46 45 44 43 42 3/32 41 40 39 38 37 36 7/64 35 34

DRILL DIA inches 0.0781 0.0785 0.0810 0.0820 0.0860 0.0890 0.0935 0.0938 0.0960 0.0980 0.0995 0.1015 0.1040 0.1065 0.1094 0.1100 0.1110

DRILL DRILL DIA # mm 1.984 * 33 1.994 * 32 2.057 * 31 2.083 1/8 2.184 30 2.261 29 2.375 28 2.383 9/64 2.438 27 2.489 26 2.527 25 2.578 24 2.642 23 2.705 5/32 2.779 22 2.794 21 2.819 20

DRILL DIA inches 0.1130 0.1160 0.1200 0.1250 0.1285 0.1360 0.1405 0.1406 0.1440 0.1470 0.1495 0.1520 0.1540 0.1562 0.1570 0.1590 0.1610

DRILL DIA mm 2.870 2.946 3.048 3.175 3.264 3.454 3.569 3.571 3.658 3.734 3.797 3.861 3.912 3.967 3.988 4.039 4.089

NOTES 1) All drill codes apply to Style F (360o) nozzle. 2) Only drill codes in shaded cells apply to Style J (180o) nozzle. 3) Drill codes marked with an asterisk (*) denote nozzles that require a strainer.

1/2 inch 8-Port Styles F & J Nozzle DRILL # * * * * * * * * * *

39 38 37 36 7/64 35 34 33 32 31 1/8 30 29 28 9/64 27 26 25 24 23

DRILL DIA inches 0.0995 0.1015 0.1040 0.1065 0.1094 0.1100 0.1110 0.1130 0.1160 0.1200 0.1250 0.1285 0.1360 0.1405 0.1406 0.1440 0.1470 0.1495 0.1520 0.1540

DRILL DIA mm 2.527 2.578 2.642 2.705 2.779 2.794 2.819 2.870 2.946 3.048 3.175 3.264 3.454 3.569 3.571 3.658 3.734 3.797 3.861 3.912

DRILL # 5/32 22 21 20 19 18 11/64 17 16 15 14 13 3/16 12 11 10 9 8 7 13/64

DRILL DIA inches 0.1562 0.1570 0.1590 0.1610 0.1660 0.1695 0.1719 0.1730 0.1770 0.1800 0.1820 0.1850 0.1875 0.1890 0.1910 0.1935 0.1960 0.1990 0.2010 0.2031

DRILL DIA mm 3.967 3.988 4.039 4.089 4.216 4.305 4.366 4.394 4.496 4.572 4.623 4.699 4.763 4.801 4.851 4.915 4.978 5.055 5.105 5.159

NOTES 1) All drill codes apply to Style F (360o) nozzle. 2) Only drill codes in shaded cells apply to Style J (180o) nozzle. 3) Drill codes marked with an asterisk (*) denote nozzles that require a strainer.

NOTE NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES. EVEN THOUGH THE METRIC OPTION IS CHOSEN, THE CALCULATION WILL BE PERFORMED IN ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 34

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

8-Port Styles F and J Nozzle Drill Nos/Diameter Charts 3/4 inch 8-Port Styles F & J Nozzle DRILL # 29 28 9/64 27 26 25 24 23 5/32 22 21 20 19 18 11/64 17 16 15 14 13 3/16 12 11

DRILL DIA inches 0.1360 0.1405 0.1406 0.1440 0.1470 0.1495 0.1520 0.1540 0.1562 0.1570 0.1590 0.1610 0.1660 0.1695 0.1719 0.1730 0.1770 0.1800 0.1820 0.1850 0.1875 0.1890 0.1910

DRILL DIA mm 3.454 3.569 3.571 3.658 3.734 3.797 3.861 3.912 3.967 3.988 4.039 4.089 4.216 4.305 4.366 4.394 4.496 4.572 4.623 4.699 4.763 4.801 4.851

DRILL # 10 9 8 7 13/64 6 5 4 3 7/32 2 1 A 15/64 B C D E F G 17/64 H

DRILL DIA inches 0.1935 0.1960 0.1990 0.2010 0.2031 0.2040 0.2055 0.2090 0.2130 0.2188 0.2210 0.2280 0.2340 0.2344 0.2380 0.2420 0.2460 0.2500 0.2570 0.2610 0.2656 0.2660

DRILL DIA mm 4.915 4.978 5.055 5.105 5.159 5.182 5.220 5.309 5.410 5.558 5.613 5.791 5.944 5.954 6.045 6.147 6.248 6.350 6.528 6.629 6.746 6.756

NOTES 1) All drill codes apply to Style F (360o) nozzle. 2) Only drill codes in shaded cells apply to Style J (180o) nozzle.

1 inch 8-Port Styles F & J Nozzle DRILL # 19 18 11/64 17 16 15 14 13 3/16 12 11 10 9 8 7 13/64 6 5 4 3 7/32 2 1 A

DRILL DIA inches 0.1660 0.1695 0.1719 0.1730 0.1770 0.1800 0.1820 0.1850 0.1875 0.1890 0.1910 0.1935 0.1960 0.1990 0.2010 0.2031 0.2040 0.2055 0.2090 0.2130 0.2188 0.2210 0.2280 0.2340

DRILL DIA mm 4.216 4.305 4.366 4.394 4.496 4.572 4.623 4.699 4.763 4.801 4.851 4.915 4.978 5.055 5.105 5.159 5.182 5.220 5.309 5.410 5.558 5.613 5.791 5.944

DRILL # 15/64 B C D E F G 17/64 H I J K 9/32 L M 19/64 N 5/16 O P 21/64 Q R

DRILL DIA inches 0.2344 0.2380 0.2420 0.2460 0.2500 0.2570 0.2610 0.2656 0.2660 0.2720 0.2770 0.2810 0.2812 0.2900 0.2950 0.2969 0.3020 0.3125 0.3160 0.3230 0.3281 0.3320 0.3390

DRILL DIA mm 5.954 6.045 6.147 6.248 6.350 6.528 6.629 6.746 6.756 6.909 7.036 7.137 7.142 7.366 7.493 7.541 7.671 7.938 8.026 8.204 8.334 8.433 8.611

NOTE 1) All drill codes apply to both Style F (360o) and Style J (180o) nozzle.

NOTE NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES. EVEN THOUGH THE METRIC OPTION IS CHOSEN, THE CALCULATION WILL BE PERFORMED IN ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 35

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

8-Port Styles F and J Nozzle Drill Nos/Diameter Charts 1-1/4 inch 8-Port Styles F & J Nozzle DRILL # 7/32 2 1 A 15/64 B C D E F G 17/64 H I J K 9/32 L M 19/64 N

DRILL DIA inches 0.2188 0.2210 0.2280 0.2340 0.2344 0.2380 0.2420 0.2460 0.2500 0.2570 0.2610 0.2656 0.2660 0.2720 0.2770 0.2810 0.2812 0.2900 0.2950 0.2969 0.3020

DRILL DIA mm 5.558 5.613 5.791 5.944 5.954 6.045 6.147 6.248 6.350 6.528 6.629 6.746 6.756 6.909 7.036 7.137 7.142 7.366 7.493 7.541 7.671

DRILL # 5/16 O P 21/64 Q R 11/32 S T 23/64 U 3/8 V W 25/64 X Y 13/32 Z 27/64 7/16

DRILL DIA inches 0.3125 0.3160 0.3230 0.3281 0.3320 0.3390 0.3438 0.3480 0.3580 0.3594 0.3680 0.3750 0.3770 0.3860 0.3906 0.3970 0.4040 0.4062 0.4130 0.4219 0.4375

DRILL DIA mm 7.938 8.026 8.204 8.334 8.433 8.611 8.733 8.839 9.093 9.129 9.347 9.525 9.576 9.804 9.921 10.084 10.262 10.317 10.490 10.716 11.113

NOTE 1) All drill codes apply to both Style F (360o) and Style J (180o) nozzle.

1-1/2 inch 8-Port Styles F & J Nozzle DRILL # F G 17/64 H I J K 9/32 L M 19/64 N 5/16 O P 21/64 Q R 11/32

DRILL DIA inches 0.2570 0.2610 0.2656 0.2660 0.2720 0.2770 0.2810 0.2812 0.2900 0.2950 0.2969 0.3020 0.3125 0.3160 0.3230 0.3281 0.3320 0.3390 0.3438

DRILL DIA mm 6.528 6.629 6.746 6.756 6.909 7.036 7.137 7.142 7.366 7.493 7.541 7.671 7.938 8.026 8.204 8.334 8.433 8.611 8.733

DRILL # S T 23/64 U 3/8 V W 25/64 X Y 13/32 Z 27/64 7/16 29/64 15/32 31/64 1/2 33/64

DRILL DIA inches 0.3480 0.3580 0.3594 0.3680 0.3750 0.3770 0.3860 0.3906 0.3970 0.4040 0.4062 0.4130 0.4219 0.4375 0.4531 0.4688 0.4844 0.5000 0.5156

DRILL DIA mm 8.839 9.093 9.129 9.347 9.525 9.576 9.804 9.921 10.084 10.262 10.317 10.490 10.716 11.113 11.509 11.908 12.304 12.700 13.096

NOTE 1) All drill codes apply to both Style F (360o) and Style J (180o) nozzle.

NOTE NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES. EVEN THOUGH THE METRIC OPTION IS CHOSEN, THE CALCULATION WILL BE PERFORMED IN ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 36

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

8-Port Styles F and J Nozzle Drill Nos/Diameter Charts

2 inch 8-Port Styles F & J Nozzle DRILL # 21/64 Q R 11/32 S T 23/64 U 3/8 V W 25/64 X Y 13/32 Z 27/64

DRILL DIA 0.3281 0.3320 0.3390 0.3438 0.3480 0.3580 0.3594 0.3680 0.3750 0.3770 0.3860 0.3906 0.3970 0.4040 0.4062 0.4130 0.4219

DRILL DRILL # DIA 8.334 7/16 8.433 29/64 8.611 15/32 8.733 31/64 8.839 1/2 9.093 33/64 9.129 17/32 9.347 35/64 9.525 9/16 9.576 37/64 9.804 19/32 9.921 39/64 10.084 5/8 10.262 41/64 10.317 21/32 10.490 43/64 10.716

DRILL DIA 0.4375 0.4531 0.4688 0.4844 0.5000 0.5156 0.5312 0.5469 0.5625 0.5781 0.5938 0.6094 0.6250 0.6406 0.6562 0.6719

DRILL DIA 11.113 11.509 11.908 12.304 12.700 13.096 13.492 13.891 14.290 14.684 15.083 15.479 15.875 16.271 16.667 17.066

NOTE 1) All drill codes apply to both Style F (360o) and Style J (180o) nozzle.

NOTE NOZZLE ORIFICES ARE DRILLED USING STANDARD WIRE GAUGE AND FRACTIONAL DRILLS. THE TABLES ON THIS PAGE SHOW THE STANDARD DRILL SIZES AND NOMINAL DIAMETERS IN INCHES AND MILLIMETERS. IF METRIC UNITS ARE CHOSEN IN THE COMPUTER PROGRAM, NOZZLE ORIFICE DIAMETERS WILL BE GIVEN IN INCHES. EVEN THOUGH THE METRIC OPTION IS CHOSEN, THE CALCULATION WILL BE PERFORMED IN ENGLISH UNITS AND THE NOZZLES MUST BE ORDERED IN ENGLISH UNITS (INCHES).

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 37

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

C. Hazard Concentration Results 1.

Hazard: The designation for each area inputted.

2.

Room Volume: The dimensional volume of a particular hazard.

3.

Pounds (Kgs) Discharged: The quantity of Novec 1230 fluid that was discharged into a particular hazard area.

4.

Concentration Requested: Based on the data input, the desired concentration.

5.

Concentration Achieved: Based on the results of the calculation, the concentration that was achieved.

Figure 2.4.1.4.C Flow Calc Program - Hazard Concentration Results

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 38

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

Figure 2.4.1.4.D Flow Calc Program - Error Messages

D. Error Messages This screen will display various piping model input errors and/or system calculation errors. There is a “Help” button located in the upper right corner of this screen which will give suggestions as to how the problems/errors should or could possibly be fixed The following is a list of system design errors that may appear. 1.

Error: Cylinder fill density is greater than 70 lb/cu ft (1121 kg/cubic meter). Resolution: There is too much agent inside of the storage cylinder. Decrease the amount per cylinder in the System Information Screen.

2.

Error: Cylinder fill density is less than 35 lb/cu ft (560.65 kg/cubic meter). Resolution: There is not enough agent inside of the storage cylinder. Increase the amount per cylinder in the System Information Screen.

3.

Error: More than 299 pipe sections in system. Resolution: The calculation module can only account for 299 node points in the piping network. Redesign the system to have fewer pipe sections.

ISSUED:

7/1/2004

REV. A

REVISED:

10/5/2004

S/N 30000066 Page 39

ENGINEERED FIRE SUPPRESSION SYSTEMS WITH 3M™ NOVEC™ 1230 FIRE PROTECTION FLUID DESIGN & FLOW CALCULATION MANUAL

4.

Error: Input file is incomplete. Resolution: The input.tmp file that is read into the calculation module is incomplete. Please check your input, save the file, and try again.

5.

Error: Pipe data sections are out of order - correct input FILE Resolution: The calculation module must have the piping sections typed in order in the Piping Model screen. Start the data input in the Piping Model screen starting with the cylinder, and enter each piping section in order.

6.

Error: Pipe schedule code in sec ## - ## is outside acceptable range. Pipe data code is given as ###. Check Input Data File Column 5(E) Resolution: A pipe schedule not listed in the pipe type pull down list was chosen. Pick a valid pipe schedule from the pipe type pull down list.

7.

Error: Pipe diameter code must be >0 and
View more...

Comments

Copyright ©2017 KUPDF Inc.
SUPPORT KUPDF